BCIT 5th class boiler engineer quiz 3 Flashcards
A gas fired boiler is started up from cold, and a small amount of water is observed draining from the reversing chamber which stops soon after. This may be due to
a) excessive pressure.
b) condensation of water in the flue gases on the cold boiler surfaces.
c) too high water level.
d) a tube leak in a watertube boiler.
e) too high firing rate.
b) condensation of water in the flue gases on the cold boiler surfaces.
CH011 Q016
When fuels containing hydrogen (such as natural gas) are burned, water is formed. Normally this water is in the form of steam and is carried with the flue gases and discharged up the stack. When a boiler is cold, this water can be condensed on the cold heating surfaces and may drain from the bottom of the boiler for a short time until the boiler warms up. If this drainage is caused by a tube leak it will continue and may become worse as the boiler pressure increases.
Before filling a steam boiler in a plant with other boilers operating you should adjust valves as follows
(select 3 items)
a) open the drum vent.
b) close the gauge glass valves.
c) close the low water cutoff steam and water valves.
d) open the water column steam and water valves.
e) open the main steam outlet valve.
f) close the blowoff valves.
a) open the drum vent.
d) open the water column steam and water valves.
f) close the blowoff valves.
CH011 Q034
Make sure that handhole and manhole covers and/or washout plugs are in place and properly tightened. Check that blow - off valves and drains on the water column, gauge glass, and low - water cutoffs are tightly shut. Valves on the gauge glass must be open. The main steam outlet is not opened until the boiler is up to pressure.
When installing manhole covers after boiler maintenance you should (Select 3 Items)
a) ensure that the surfaces are thoroughly cleaned.
b) ensure that the surfaces are freshly painted.
c) install new gaskets if old ones are severely damaged.
d) apply an adhesive to ensure that a tight seal is produced.
e) use gasket compound or graphite to coat gaskets.
f) ensure that an even gap exists between the opening and the raised part of the manhole cover.
a) ensure that the surfaces are thoroughly cleaned.
e) use gasket compound or graphite to coat gaskets.
f) ensure that an even gap exists between the opening and the raised part of the manhole cover.
CH011 Q018
The surfaces where the manhole cover and manhole opening contact must be cleaned to ensure a good seal.
The gasket must be installed so that there is an even gap all around between the raised part of the manhole cover and the manhole opening.
The gasket should be coated with gasket compound or graphite to ensure easy removal on the next shutdown.
No adhesive is used because the gasket ensures a tight seal and that would make the gasket difficult to remove on the next shut down.
A new gasket is always used no matter how good the old one looks.
The inner surfaces of a boiler are not painted including the manhole opening although the cover may be painted.
Select tasks from below that must be preformed before a watertube steam boiler startup is attempted. (select 5 items)
a) Close boiler up replacing manhole and handhole covers.
b) Start circulating pump to circulate water through heating system.
c) Set combustion controls to low fire position.
d) Close drains and fill boiler after adding startup chemicals.
e) Inspect to ensure maintenance is completed and tools and debris removed.
f) Reset Limit Controls that may have been tripped on shutdown.
g) Close vent valve on boiler steam drum.
h) Operate sootbowers to ensure boiler surfaces are clean.
a) Close boiler up replacing manhole and handhole covers.
c) Set combustion controls to low fire position.
d) Close drains and fill boiler after adding startup chemicals.
e) Inspect to ensure maintenance is completed and tools and debris removed.
f) Reset Limit Controls that may have been tripped on shutdown.
CH011 Q006
Before a steam boiler can be started by a programming control, the following conditions must be fulfilled:
Inspect the fireside and water side to ensure all maintenance is completed and all foreign material has been removed.
Close up boiler ensuring that manhole and handhole surfaces are clean and new gaskets are installed.
Add startup chemicals and fill boiler with treated water. For steam boilers, the water in the boiler drum must be above the cut - off point of the low - water fuel cut – off.
For steam boilers, open water supply to condensate storage feed valve if so equipped. Switch feedwater pump to automatic position and open inlet valve to boiler.
The steam pressure or water temperature must be at or below the cut - in setting of the operating control so its switch is closed. The switch for the high limit control will also be closed.
The main power switch or breaker must be closed so the electronic circuit in the programming control panel is energized, and power is available to the motor starting relays.
Check setting of automatic controls and reset any limit switches that may have been tripped (eg low gas pressure, high steam pressure, flame failure)
On boilers with high-low firing control set controls to low fire. On boilers with modulating control, set selector to manual and adjust flame control switch to low fire position.
The water level in a boiler must be maintained above the highest heating surface at all times because
a) the water keeps tubes from overheating which could rapidly result in damage.
b) excessive scale formation occurs if the heating surfaces are allowed to dry out.
c) the boiler is able to handle rapid load changes with more water volume.
d) the gauge glass is above the highest heating surface.
e) the maximum amount of steam can be produced.
a) the water keeps tubes from overheating which could rapidly result in damage.
CH011 Q044
Overheating of the heating surfaces can lead to disastrous explosions. Normally the water in the boiler covering these surfaces keeps the temperature of the boiler metal well below the danger point, but lack of water causes the temperature of the metal to rise to the point where the metal weakens and the internal pressure ruptures the material, resulting in a massive escape of pressurized steam and water.
To prevent overheating as a result of a low water condition the Boiler Code requires that every automatically fired steam and hot water heating boiler which is not under continuous attendance by a certified operator shall be equipped with an approved low - water fuel cut - off device, that is designed to shut off the fuel and air supply to the burner before the water level drops to a dangerous low level.
After vacation you have returned to work in a low pressure steam plant on night shift. To determine if any major incidents have occurred you should first
a) contact the boiler inspector.
b) talk with the building manager.
c) check the controls.
d) make a thorough inspection of plant equipment.
e) read the log book.
e) read the log book.
CH011 Q054
Actions in taking over and running the shift in a low pressure steam heating plant are:
Examine the log book to see if there have been any unusual happenings during the previous shift.
Check the boiler, i.e., fire, water level, leaks.
Test the automatic controls, i.e., stack switch or scanner, low water cut-out, pump control, and pressure limit control.
Inspect the feed pump, injector, boiler valves, piping and fittings for leaks and proper operation.
Check for leaks in the system and check that all sections of the system are hot. If any section is cold the cause should be determined and remedied.
Check all other equipment of the system, i.e., pumps, traps, piping controls, etc.
Make required tests and take appropriate action based on the results of these tests.
Maintain log book.
There are two types of explosions of boilers that can cause catastrophic results. These are
(Select two Items)
a) delayed explosions.
b) furnace explosions.
c) thermal explosions.
d) chemical explosions.
e) pressure explosions.
b) furnace explosions.
e) pressure explosions.
Boiler explosions may be listed under two general classifications: furnace explosions and pressure explosions.
Furnace Explosions
These are explosions which occur when an accumulation of combustible gases ignites and explodes within the furnace or gas passages of the boiler. This may be caused by:
- Insufficient purge of the furnace before lighting up.
- Admission of the fuel to the main burner before the pilot flame or other ignition source is established.
- A weak pilot flame.
- Failure of the main fuel valve to close when the main burner flame is lost.
- An insufficient amount of combustion air resulting in incomplete combustion.
Pressure Explosions
Pressure explosions occur when a pressure part of the boiler such as the shell, furnace, or firetube bursts due to too high a steam pressure or a structural weakening of the metal. This weakening may be caused by:
- The effects of corrosion.
- Overstressing of the material due to heating the boiler up too quickly during start-up.
- Overheating of the heating surfaces due to a low water condition (low -water fuel cut-off failure).
- Scale and sludge build up.
- Also, failure of the boiler operating controls combined with an inoperative safety valve may cause the pressure to rise far above the maximum allowable working pressure.
In either case, the results of an explosion are almost always loss of life and/or extensive damage to property.
When a boiler is heated up too quickly, uneven expansion can result in stress in the metal called
a) thermal stress.
b) tube warp.
c) expansive reaction.
d) tensile reaction.
e) expansion stress.
a) thermal stress.
CH011 Q024
Thermal Shock When metal is subjected to a sudden change in temperature, the temperature change will not be even throughout the metal and expansion and contraction will not be equal in all parts of the metal. This will cause strong internal stresses in the metal, called thermal shock. The larger the temperature change and the heavier the metal, the greater the internal stresses will be.
The heating surfaces of boilers, such as furnace walls, firetubes, and tubesheets, are subjected to thermal shock when the fire is started since rapid temperature changes take place. If a cold boiler is started up and the maximum firing rate is applied, the thermal shock may be so strong that it will result in the appearance of tiny cracks in the metal, especially in the tube ends and tubesheets. This condition is worsened by the stresses set up by uneven expansion and by scale build-up.
Thermal shock is also caused by a rapid drop in temperature. This occurs when the water in a hot water boiler is up to operating temperature (90-115°C, 194-239°F) and the operator allows it to be replaced in a matter of minutes by a large flow of cool water from a heating system that has been out of operation.
To reduce the effects of uneven expansion and thermal shock and to protect a boiler against damage, the following precautions should be taken:
Always warm up the boiler slowly.
Keep the boiler free from scale build-up.
Cover the tubesheet with a lining of refractory to protect it from direct contact with the hot gases.
Do not allow a full flow of cool circulating water to pass through a warm hot water boiler. Bypass part of the flow around the boiler until the water temperature difference between the supply and return lines has reached its normal operating value.
Unless otherwise recommended by the manufacture’s instructions, a high/low fire control should be set to low fire when starting.
True
False
True
CH011 Q022
When lighting off a burner, too much fuel can result in a puff that can cause high furnace pressure. Also, a boiler should be warmed up slowly to reduce thermal stress. Therefore it is normal procedure to start a burner on the low fire or minimum fire setting.
In heating system a sudden increase in the amount of water treatment chemicals required would most likely indicate
a) a loss of air cushion in the expansion tank.
b) water is being lost in the system.
c) that scale has formed on boiler tubes.
d) the quality of water supply has deteriorated.
e) the heating load has increased.
b) water is being lost in the system.
CH011 Q040
When water losses from a steam or hot water boiler and heating system become abnormal, as indicated by the makeup water supply meter or by an increased requirement of water treatment chemicals to maintain normal concentrations in the boiler, an investigation should be made immediately to determine the cause. Proper repairs should be made at once rather than simply increasing the water treatment.
When checking the boiler, it is noticed that the water level is below the gauge glass. The correct action to take is
a) shut off the fuel and fill the boiler before restarting.
b) fill the boiler immediately up to the center of the glass.
c) shut down the boiler and inspect for signs of overheating.
d) call the chief boiler inspector and ask for advice.
e) fill the boiler slowly and check the low water cutoff device.
c) shut down the boiler and inspect for signs of overheating.
CH011 Q042
Low Water Level
A rapidly falling water level in the boiler may be caused by a faulty feedwater level controller, feedwater or condensate pump failure, interruption of the water supply to the pump, or leakage from the boiler due to ruptured fire tubes or leaking blow - off valves.
Normally, when the level drops to the low - water cut - off point, the boiler will shut down automatically. However, should the cut - off fail to shut the boiler down, the water level may drop dangerously.
If the operator finds the boiler in operation while unable to see the water level in the gauge glass, it may be that the glass is either completely full or empty. This should be checked quickly by opening the drain on the glass. If the level is found to be below the gauge glass, the boiler must be shut down immediately.
Caution:
Do not feed water into the boiler to raise the level, and do not open the safety valve or vent valve to release pressure.
Let the boiler cool slowly until it is at hand - touch temperature. Drain the boiler and open it to inspect for damage due to overheating. If no damage is found, the boiler can be closed up again and filled. However, it should not be put back into operation until the cause of the feedwater shortage and the failure of the low - water cut - offs to shut the boiler down is found and corrected.
If it appears that damage has been done, the Boiler Inspector must be notified.
To drain a hot water boiler after isolating it, you must open the blowoff valve and
a) close the continuous blowdown.
b) open the gauge glass drain.
c) open the return valve.
d) open the expansion tank drain valve.
e) open the vent.
e) open the vent.
CH011 Q032
If the boiler has to be opened for maintenance or inspection of the waterside, open the blow - off and vent valve after the boiler has completely cooled down. If the boiler is connected to an expansion tank common with other boilers, close the valve in the line connecting the boiler and tank before opening the blowoff valve. After the boiler is drained, remove the manhole and handhole covers or drain plugs and wash the boiler out with a stream of high pressure cold water.
During the annual inspection a boiler operator is not required to provide any information on known boiler defects to the inspector
True
False
False
CH012 Q006
The boiler operator is required to assist the inspector as necessary and to disclose any defect of which they are aware.
To remove baked on scale inside a cast iron boiler would require
a) dismantling sections and scraping.
b) chemical cleaning.
c) scraping and wire brushing.
d) turbining tubes.
e) wire brushing.
b) chemical cleaning.
CH012 Q002
The maintenance requirements for a cast iron boiler at the end of the heating season are: Thoroughly clean boiler of soot and ashes. Trash and other debris should not be allowed to accumulate around the outside of the boiler. Check to make sure that there is room for expansion between the sections. The tie-rod nuts should not be tight but should be backed off several turns or compression washers should be used with the nuts. If sludge and loose scale are present within the boiler, remove plugs from rear and front sections and flush with clean water. Boiler may have to be cleaned chemically if scale is baked on. Fill boiler completely with treated water to prevent corrosion during summer months. If danger of freezing, store dry. Remove fuses from firing circuit. Check all piping, fittings, etc. for cracks, corrosion, or signs of leakage. Thoroughly overhaul gauge glass and low water cut - outs.
The instrument shown in the figure below is used tomeasure
a) furnace pressure.
b) steam flow.
c) boiler pressure.
d) furnace temperature.
a) furnace pressure.
CH013 Q022
U -Tube Draft Gauge
A simple gauge for measuring draft consists of a glass U - tube containing water. One end is open to the atmosphere and the other end is connected to the inside of the furnace or to the flue gas outlet of the boiler. The difference in the levels of the water in the two legs of the U - tube will be the draft in millimetres of water or inches of water depending on the scale used. This type of gauge is also known as a manometer.
The U- tube gauge is connected to measure furnace draft or pressure. If the furnace pressure is less than atmospheric pressure, the atmosphere pushes upon the water so that the level in the U - tube leg connected to the furnace is higher than the level in the leg open to atmosphere. The difference in the levels is approximately 0.75 inches so that the value of the furnace pressure or draft is - 0.75 inches of water. The disadvantage of the simple U - tube draft gauge is the difficulty in reading slight pressure variations.
Advantages of oil when compared to coal as a fuel include (Select 3 Items)
a) less expensive than coal in fuel grades.
b) no storage is required.
c) more is available in nature than coal.
d) flow to furnace more easily controlled.
e) cleaner burning with less ash.
f) less handling equipment is required.
d) flow to furnace more easily controlled.
e) cleaner burning with less ash.
f) less handling equipment is required.
CH013 Q002
Fuel oil has certain advantages over coal as a boiler fuel:
1. Less storage space required.
2. Amount fed to furnace more easily controlled.
3. Less handling equipment and less labour required.
4. Cleaner and more efficient to use.
However, coal is less expensive than oil and there is a much greater abundance of coal.
Select the correct balanced, equation below that represents the incomplete combustion of carbon
a) C + O→CO
b) 2 C + O2→2 CO
c) C + O2→CO2
d) 2 C + O2→CO
e) C2+ O2→2 CO
b) 2 C + O2→2 CO
CH013 Q008
The combustion process can be expressed in simple chemical equations which representthe combination of these combustible elements with oxygen during complete combustion.
Carbon + Oxygen→Carbon Dioxide + heat
C + O2→CO2+ heat
Hydrogen + Oxygen→Water Vapor + heat
2H2+ O2→2H2O + heat
Sulphur + Oxygen→Sulphur Dioxide + heat
S + O2→SO2+ heat
Heat is stated in writing as being a product of the combustion equations. It is not included as a product in the printing of the combustion equations. Note that combustion of sulphur produces sulphur dioxide which is a toxic gas and causes acid rain. Also the heating value of sulphur is very low. Therefore it is considered an undesirable component of fuels.
Before burning, oil must be divided into fine droplets in a spray pattern. This is known as
a) educting.
b) atomizing.
c) aspirating.
d) reduction.
e) oxidation.
b) atomizing.
CH014 Q010
Oil must be broken up into a fine spray before entering hte furnace so that it can be heated and vaporized quickly for combustion. This process is called atomizing.
Two mediums that are used to atomize oil in high pressure oil burners are
(Select 2 Items).
a) boiler steam.
b) natural gas.
c) steel pellets.
d) compressed air.
e) high pressure nitrogen.
a) boiler steam.
d) compressed air.
CH014 Q012
Air atomizing burners require a compressed air supply. Usually a small rotary air compressor is mounted on or near the front of the boiler. The compressor is driven either directly by a small electric motor or by a V-belt and motor combination which also drives a fan supplying the secondary air to the furnace.
This type of burner can be used for light oils and also for heavier oils that are preheated.
Most industrial burners use steam for atomization instead of air (primary air). Basically the principle of operation of a steam atomizing burner is much the same as that of the air atomizing burner.
One advantage that cast iron has over steel as a piping material is that it is
a) stronger.
b) easier to bend.
c) more resistant to erosion.
d) lighter.
e) easier to weld.
c) more resistant to erosion.
CH015 Q006
Steel
Advantages: Steel piping is moderately priced as compared to piping made of other materials.
Disadvantages: Low resistance to the corrosive effects of water.
Cast Iron
Advantages: Has a high resistance to corrosion and to abrasion.
Disadvantages: It is quite brittle and not suitable for the pressure piping of most building systems.
Copper
Advantages: Copper and copper alloys offer great resistance to corrosion.
Disadvantages: Much more expensive than carbon steel and its use is restricted to low and moderate temperature service.
Plastic
Advantages: Plastic piping is reasonably inexpensive, light weight, easy to assemble and it offers great resistance to corrosion.
Disadvantages: Its use is restricted to low and moderate temperature and low and moderate pressure service. Also it is not permitted in commercial buildings in some jurisdictions – check local building codes before use.
To prevent leakage of flanged joints, they are normally sealed using
a) gaskets.
b) grease.
c) Teflon tape.
d) packing.
e) caulking.
a) gaskets.
CH015 Q014
In order to prevent leakage at flanged connections, the flange faces which butt together would have to be absolutely flat and smooth. While it is theoretically possible to grind the faces to this condition it is a time consuming and expensive proposition. Therefore, ring - shaped gaskets are usually used between flange faces. These are made of a comparatively soft material which, when the flanged connection is tightened, will fill any small depressions in the flange faces and thus prevent leakage.
The figure below represents
a) a float trap.
b) a bimetallic trap.
c) a thermodynamic trap.
d) an inverted bucket trap.
e) a thermostatic trap.
e) a thermostatic trap.
CH017 Q004
Thermostatic Steam Trap
This trap consists of a chamber containing an element consisting of a flexible bellows containing a small amount of volatile liquid. A valve is attached to the bottom of the bellows. As shown, the trap is open and condensate flows through and out the outlet. Air will also be allowed to escape. When steam enters the chamber, the steam heats the bellows causing the volatile liquid to evaporate pressurizing the bellows. This causes the bellows to expand forcing the valve down against the seat and trapping the steam. If the trap again fills with condensate or air, it will cool off and the volatile liquid will condense allowing the valve to open, expelling the air or condensate.
A valve which allows flow in one direction but closes if the flow is reversed is the
a) gate valve.
b) check valve.
c) needle valve.
d) globe valve.
e) butterfly valve.
b) check valve.
CH018 Q004
The check valve is a valve which prevents reversal of flow in piping. The flow of the fluid keeps the check valve open while reversal of flow will cause the valve to close. The swing check valve features a straight line flow and therefore offers little resistance to flow. The disc which is hinged at the top, swings freely in an arc from the fully open to closed position. The flow holds the disc opened but if reversed, the disc drops closed by gravity and will be held closed by the higher pressure on the downstream side of the valve.
The reason for leaving the suction valve on the standby pump of a hot oil system open is to
a) keep the pump hot and ready for start-up.
b) prevent contaminants from blocking the suction strainer.
c) prevent air bubbles from forming in the pump.
d) ensure the safety valve protects the pump from excessive pressure.
a) keep the pump hot and ready for start-up.
CH019 Q014
The suction valve of the standby pump should be left open all the time to allow a small amount of hot oil to flow backwards through the pump around the discharge check valve. This is recommended in order to maintain the standby pump at operating temperature, as it would otherwise be difficult to start in cold weather because of the high viscosity of the hot oil at low temperatures.