What is the power supply for the Train A BOP-ESFAS Cabinet?
PNA and PKA auctioneered
Both converted to 24VDC
2 fans - 1 AC and 1 DC
What is the power supply for the Train B BOP-ESFAS Cabinet?
PNB and PKB auctioneered
Both converted to 24VDC
2 fans - 1 AC and 1 DC
What two RU monitors are responsible for the FBEVAS Actuations?
RU-31 (A)
RU-145 (B)
What happens if just RU-31 alarms?
FBEVAS A and B
CREFAS A and B
Happens if FBEVAS A is manually initiated from B05?
Just FBEVAS A will actuate
No cross trips
A FBEVAS only actuates. Along with starting the required equipment, what else happens?
Fuel Building Normal Supply and Exhaust Fans stop.
A Fuel Building Normal Dampers Close
B FBEVAS only actuates. Along with starting the required equipment, what else happens?
Fuel Building Normal Supply and Exhaust B dampers close. This is bad because the fans are still running and will overheat.
Both trains of FBEVAS are running and a SIAS occurs. What happens?
The Fuel Building Essential AFUs will swap their suctions from the Fuel Building to the Aux Building.
What two RU monitors are responsible for the CPIAS Actuations?
RU-37 (A)
RU-38 (B)
What happens if just RU-38 alarms?
CPIAS A and B
CREFAS A and B
What two RU monitors are responsible for the CREFAS Actuations?
RU-29 (A)
RU-30 (B)
What is the basis for the CREFAS?
To maintain whole body exposure < 5 REM.
A CREFAS only actuates. Along with starting the required equipment, what else happens?
Control Room Normal Supply and Exhaust Fans stop.
B CREFAS only actuates. Along with starting the required equipment, what else happens?
Control Room Normal Supply and Exhaust dampers close. This is bad because the fans are still running and will overheat.
What other equipment starts on a CREFAS along with the Control Room Essentials?
SP
EW
EC
CT (A and B)
Along with the RU monitors, what else will actuate a CREFAS?
Either train of FBEVAS or CPIAS will actuate both trains of CREFAS. (unless the trip was initiated manually)
What must be reset prior to resetting CREFAS?
FBEVAS and CPIAS
What RU monitors actuate CRVIAS?
CRVIAS doesn’t have field inputs.
What actuates a CRVIAS?
Manual actuation at B05 or at the BOP-ESFAS Cabinets
The outside air dampers for the Control Room Essentials are open on a CREFAS. CRVIAS is initiated from B05. What happens to the outside air dampers?
They close. CRVIAS overrides SIAS and CREFAS
What other equipment starts on a CRVIAS along with the Control Room Essentials?
SP
EW
EC
CT (A and B)
Explain the layout for the UV relays on the Class 4160V buses.
4 degraded voltage relays and 4 loss of voltage relays come off of each PB bus. 1 DV relay and 1 LOV are paired to make one channel. One relay from each channel is enough to trip the channel. LOP actuation logic is 2/4 channels.
What are the relay pair numbers for the Undervoltage Relays for the PB buses?
Channel 1 - 1/5
Channel 2 - 2/6
Channel 3 - 3/7
Channel 4 - 4/8
What happens on a LOP in the BOP-ESFAS?
2/4 logic met on the Class UV relays. Sends signal to DGSS module resulting in a DG start. Signal also sent to Sequencer which generates 1 second Load Shed Pulse to keep from overloading the DG.