RPS: Reactor Protection System Flashcards

1
Q

What is the RRS design basis?

A

Load Rejection of any magnitude
10% step change
5%/min ramp change

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What does NNN-D12 provide for the RRS?

A

Power to RRS overall
Hot Leg instruments (Loop 1 and Loop 2)
Control Channel 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What happens to the RRS if NNN-D12 is lost?

A
RRS loses power
No input to CEDMCS = no auto rod control
Tave signal to PLCS fails low (33%-lose letdown)
Lose power to both Th instruments
Lose power to TLI #2
Lose power to Control Channel #2
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does NNN-D11 provide for RRS?

A

Cold Leg instruments (Loop 1 and Loop 2)

Control Channel 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens to the RRS if NNN-D11 is lost?

A

Lose power to both Tc instruments
Lose power to TLI #1
Lose power to Control Channel #1
You’ll get an AMI if selected to Average

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How can you tell which Tave inputs are being used by the RRS in the Control Room?

A

Lights on B05 - if both are on the average of the Tave’s is being used

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is used by the RRS to develop Tref?

A

TLI - B06 1st stage pressure is not the input to RRS

Tref = 564F to 587F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where can you read the two first stage pressure instruments (MTN-PT-11A/B) that input into the RRS for TLI?

A

At the RRS Test Cabinet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the TLI range for RRS?

A

0% - 125%

RRS can only use a 100% reading though. This results in a max Tref of 587F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How is the Temperature Error for the RRS generated?

A

Tave - Tref = Et

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What function does the Lag Network serve for the RRS?

A

Gives higher amplification to a parameter that is rapidly changing. Adds stability to the temperature control loop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What Total Error in the RRS will generate a low insertion demand?

A

+ 3F

Resets at + 2.84F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What Total Error in the RRS will generate a withdraw demand?

A
  • 3F

Resets at - 2.84F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What Total Error in the RRS will generate a high insertion demand?

A

+ 4.53F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What Total Error in the RRS will generate a high withdraw demand?

A
  • 4.53F

However, rods will not withdraw in Auto at the high rate.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When reading a voltage at the RRS Test Panel, what must be done before selecting the desired input?

A

You must push the “Test Probe” button to verify the voltmeter reads zero.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What happens in RRS if Tc fails HIGH while selected to AVERAGE?

A
AWP
AMI
PLCS Setpoint to 52.6%
RC Loop Temp HI
Tave-Tref Hi-Lo
18
Q

What happens in RRS if Tc fails HIGH while selected to the affected channel?

A
AWP
Hi Rate Insertion Demand - rods go in if in AS
PLCS Setpoint to 52.6%
Possible Rx Trip on Low PZR Pressure
Possible Rx Trip on Low SG Pressure
Possible SIAS
RC Loop Temp HI
Tave-Tref Hi-Lo
19
Q

What happens in RRS if Tc fails HIGH while selected to the unaffected channel?

A

AWP

RC Loop Temp HI

20
Q

What happens in RRS if Tc fails LOW while selected to AVERAGE?

A

Tave-Tref Hi-Lo
AMI
PLCS Setpoint to 38%

21
Q

What happens in RRS if Tc fails LOW while selected to the affected channel?

A

Tave-Tref Hi-Lo
PLCS Setpoint to 33%
High Withdraw Demand - at 100% usually ARO

22
Q

What happens in RRS if Tc fails LOW while selected to the unaffected channel?

A

Light on the RRS Test Panel

23
Q

What happens in RRS if Th fails HIGH while selected to AVERAGE?

A
Tave-Tref Hi-Lo
RC Loop Temp HI
AWP
AMI
PLCS Setpoint to 52.6%
24
Q

What happens in RRS if Th fails HIGH while selected to the affected channel?

A
Tave-Tref Hi-Lo
RC Loop Temp HI
AWP
High Insert Demand - rods go in if in AS
PLCS Setpoint to 52.6%
Possible Rx Trip on Low PZR Pressure
Possible Rx Trip on Low SG Pressure
Possible SIAS
25
What happens in RRS if Th fails HIGH while selected to the unaffected channel?
RC Loop Temp HI | Light on the RRS Test Panel
26
What happens in RRS if Th fails LOW while selected to AVERAGE?
Tave-Tref Hi-Lo AMI PLCS Setpoint to 33%
27
What happens in RRS if Th fails LOW while selected to the affected channel?
Tave-Tref Hi-Lo PLCS Setpoint to 33% High Withdraw Demand - at 100% usually ARO
28
What happens in RRS if Th fails LOW while selected to the unaffected channel?
Light on the RRS Test Panel
29
What happens in RRS if TLI fails HIGH while selected to AVERAGE?
Tave-Tref Hi-Lo AMI Light on the RRS Test Panel
30
What happens in RRS if TLI fails HIGH while selected to the affected channel?
Tave-Tref Hi-Lo | Withdraw Demand - at 100% usually ARO
31
What happens in RRS if TLI fails HIGH while selected to the unaffected channel?
Light on the RRS Test Panel
32
What happens in RRS if TLI fails LOW while selected to AVERAGE?
Tave-Tref Hi-Lo AWP AMI Light on the RRS Test Panel
33
What happens in RRS if TLI fails LOW while selected to the affected channel?
``` Tave-Tref Hi-Lo AWP High Insert Demand - rods go in if in AS Possible Rx Trip on Low PZR Pressure Possible Rx Trip on Low SG Pressure Possible SIAS ```
34
What happens in RRS if TLI fails LOW while selected to the unaffected channel?
Light on the RRS Test Panel
35
What happens in RRS if a Control Channel Power fails HIGH while selected to AVERAGE?
Light on the RRS Test Panel | AMI
36
What happens in RRS if a Control Channel Power fails HIGH while selected to the affected detector?
Light on the RRS Test Panel
37
What happens in RRS if a Control Channel Power fails HIGH while selected to the unaffected detector?
Light on the RRS Test Panel
38
What happens in RRS if a Control Channel Power fails LOW while selected to AVERAGE?
Light on the RRS Test Panel | AMI
39
What happens in RRS if a Control Channel Power fails LOW while selected to the affected detector?
Light on the RRS Test Panel | AMI
40
What happens in RRS if a Control Channel Power fails LOW while selected to the unaffected detector?
Light on the RRS Test Panel