Test 2.1 Question
Answer
Torch cutting and welding if sprinkler piping shall: (NFPA 13, 2007, 13-30, 6.5.2.2.5, NFPA 13,2002,13-26, 6.5.2.12)
Not be permitted as a means if modifying or repairing sprinkler systems
When welding is performed on sprinkler piping the following procedures shall be completed: (NFPA 13, 2007, 13-31, 6.5.2.4.6, NFPA 13,2003, 13-36, 6.5.2.9 (1)(2)(4) )
Holes in piping outlets shall be cut to the full inside diameter of fittings prior to welding in place of the fittings prior to welding in place of the fittings / Discs shall be retrieved / Fittings shall not penetrate the internal diameter of the piping
According to the ASME B1.20.1, the number of threads per inch that properly threads a 2-inch pipe should have: (NFPA 13, 2007, 13-30, 6.5.1.1, NFPA 13, 2002 - - - 13-26, 6.5.1.1)
11-1/2-threads per inch
Of the following types if valves an indicator valve would be:
Butterfly valve
When an oxy-acetylene torch is used for making a brazed joint the type if flame that should be used is:
Reducing flame
The limiting length that determined whether a length of pipe that is threaded on both end is considered either as cut pipe or nipple is:
12-inch
Listed indicating valves shall not close in less than ________ when operating at maximum possible speed from the fully open position: (NFPA 13, 2007, 13-32, 6.7.1.2,, NFPA 13, 2002 - - - 13-27, 6.7.1.2)
5-seconds
A welding procedure shall be prepared and qualified, before any welding is done, for all welding installed in a fire suppression piping system: (NFPA 13,2007, 13-31, 6.5.2.5.1, NFPA 13, 2002 - - - 13-26, 6.5.2.13.5 and 6.5.2.13.6)
The licensed master fire suppression piping contractor / Fabricators
Of the following types of copper tubing the one that has the greatest wall thickness:
Type “K”
In order for a synchronous motor to operate properly a motor must be supplied with:
Both A.C. and D.C.
Of the following classifications of electrical motors a general purpose motor that would most likely be used where operating conditions are relatively clean and dry is the:
Open drip-proof motor
Soldered joints shall be permitted for _____ wet pipe systems in light hazard occupancies where the temperature classification of the installed sprinklers is of the ordinary-or intermediate-temperature classification: (NFPA 13,2007, 13-31, 6.5.4.3, NFPA 13,2002 - - - 13-27, 6.5.4.3)
Exposed
Solder joints shall be permitted for wet pipe systems in light hazard and ordinary hazard (Group 1) occupancies where piping is ____________, irrespective of sprinkler temperature ratings: (NFPA 13, 2007, 13-31, 6.5.4.4NFPA 13, 2002 - - - 13-27, 6.5.4.4)
Concealed / Exposed / Non-exposed
Of the following types of filler metals for brazing the one which can produce highly toxic fumes when brazing:
Bag-2
Waterflow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed in the system will result in an audible alarm on the premises within _____ after such flow begins and until such flow stops: (NFPA 13, 2007 - - - 13-32, 6.9.1)
5-minutes
In sprinkler systems, all control, drain and test connections valves shall be provided with: (NFPA 13,2007, 13-32, 6.7.4.1)
Permanently marked weatherproof metal / Rigid-plastic identification signs
Of the following types if heat detectors the one that is commonly used in automatic sprinkler and often used to release fire is the: (NFPA 72, 2002, 72-16, 3.3.43.7 & 72-112, A 3.3.43.7)(“NFPA Fire Handbook”Automatic fire detectors”)
Fixed-Temperature-detector
Seamless steel pipe has been specified to be used in the installation of a sprinkler system. The maximum distance between hangers for supporting a horizontal 1-inch diameter pipe: (NFPA 13,2002 - - - 13-85, Table 9.2.2.1)
12-feet
For class 1 and class 111 systems, the minimum flow rate for the hydraulically most remote standpipe shall be: (NFPA 14, 2003, S-76, 7.10.1.1.1)
500-gpm
In the installation of a centrifugal fire pump when the suction pump and suction flange are not the same size it is recommended practice that they be connected with:(NFPA 20, A-9.6)
Eccentric flanged eccentric reducer
Of the following statements pertaining to sprinklers the one that is most applicable to an upright sprinkler is that an upright sprinkler: (NFPA 13, 2007, 13-20, 3.6.3.6, NFPA 13,2002 - - - 13-17, 3.6.3.6)
Installed in such a way that the water sprayed is directed upward against the deflector
Of the following statements pertaining to sprinklers, the one that is most applicable to a pendant sprinkler, is that a pendent sprinkler is designed to be: (NFPA 2007, 13-20, 3.6.3.3, NFPA 13,2002, 13-17, 3.6.3.3)
Installed in such a way, that the water stream is directed downward against the deflector
A sprinkler in which all or part of the body, other than the shank thread, is mounted within a recessed housing: (NFPA 13,2007, 13-20 3.6.3.4, NFPA 13, 2002, 13-17, 3.6.3.4)
Recessed