Class 3 Flashcards
(199 cards)
The distance between the floor and the underside of the roof deck within the storage area: (NFPA 13, 2007 — 13-22, 3..18)
Roof height
What is the minimum size ball drip permitted on a check valve: (NFPA 14, 2007 - - -S-28, 4.8.2.2 Q (i) - - - NFPA-14,2003 - - - S-50,4.8.2.2 (i) )
3/4-inch
The sprinkler pipes in which the sprinklers are placed, either directly or through risers: (NFPA 13, 2007 — 13-19 3.5.1)
Cross main
Class III standpipe systems shall be installed throughout the following building; in buildings 3-stories or more in height with floor area of: (NYC Building Code 2014, 905.3.1 (2), 214 - - - NFPA 14, 2003 - - - S-68A,905.3.1 (2) )
7,500-Sq. ft.
All the equipment, material and labor required for testing a system or parts thereof of a fire system: (NFPA 14, 2007, S-78, 11.1.3)
Installing contractors shall complete and sign appropriate contractor’s material and test certificate(s)
Express piping to high zone siamese connections shall not be installed in STAIRWAY enclosures but may be in any other: (NFPA 14, 2007 - - - S-S-29, 4.8.2.2Q(j)(1) - - - NFPA 14,2003 - - - S-50, 4.8.2.2(i)(j) )
Protected shaft
Within a year a certain material rose from $250.00 to $270.00 for the same quantity. The percentage price increase was:
8%
Unless the requirements of 6.7.3.1, 6.7.1.3.2 or 6.7.1.3.3 are met, all valves controlling connections to water supplies and to supply pipes to sprinklers shall be listed: ( NFPA 13,2007 — 13-32, 6.7.1.3 & 3.1*-)
underground gate valve equipped with a listed indicator post / indicating valves
On a set of drawings a line is drawn 12-1/2-inch long. If the scale is 1/8 of an inch to the foot, what is the actual length of the pipe
100-feet
The main reason why the outer ends of all external and internal screw threads for a firehouse connection are terminated by a higbee-cut-blunt start on a full thread is to:
To avoid cross threading of the threads
Each two-way fire department connection for standpipe systems shall be provided with caps painted: (NFPA 14, 2007, S-46, 6.4.2Q)
Red
Horizontal piping from the standpipe to hose connections that are more than _____ (457-mm) in length shall be provided with hangers: (NFPA 14, 2003, S-66, 6.4.2.1)
18-inches
Class 1 and class 111 standpipes in building with floor heights less than 150-feet (45 720-mm) above grade plane shall be at least: (NFPA 14, 2007 - - - S-53, 7.6.1Q - - - NFPA 14,2003 - - - S-71, 7.6.1 and S-71, Table 1)
4-inches in diameter
The nominal pipe size of the pipe refers to the pipes:
Area of pipe
(18) In the sentence “ the working drawings shall be coordinated with…” in the above paragraph. The word coordinate means most nearly:
In agreement
Mains supplying risers or cross mains: (NFPA 13, 2007 — 13-19, 3.5.3)
Feed Main
Bolts shall be provided with a: (NFPA 13, 2007 — 13-93, 9.1.1.6.8)
Flat washer / Nut
The vertical supply pipes in a sprinkler system: (NFPA 13, 2007 — 13-19, 3.5.5)
Riser
According to the N.Y.C. Building code the maximum number of sprinkler heads that a N.Y.C. Master PLumber is authorized to install on any one building off a domestic water line: (“Plumbing work”)
30
Two pipes are running full of water and going into one pipe. One pipe is carrying 47-gallons of water per minute and the other Carrying 53-gallons of water per minute. What is the amount of water coming through the third pipe
100-gallons/minute
Which document established the minimum requirements for the periodic inspection, testing, and maintenance of water-based fire protection systems and the actions to undertake when changes in occupancy,use, process, materials, hazard, or water-supply that potentially impact the performance of the water-based system are planned or identified:
NFPA 25
Of the following type of hangers, the one that is most commonly used in piping work is the: (NFPA 13,2007 — 13-277)
Clevis- Hanger type
Riser control valve in standpipe systems, shall where practicable, be located within required stair enclosure serving the: (NFPA 14, 2007 — S-41, 6.2.2Q(1) — NFpa 14, 2003 — S-59, 6.2.2 (1) )
Entrance floor
An air compressor is primarily used for: (NFPA 13,2007 - - - 13-34, 7.2.6.2*)
Forcing water through fire sprinklers in a building