Control Elment Drive Mechanism Control System (CEDMCS) Flashcards
What is CEDMCS used for ?
-Develops control voltage to withdraw, hold, or insert CEAs
What’re Control Element Assemblies(CEA), also known as control rods, used for?
Used to control fission rate of reactor power
What does CEDMCS allow CEA groups to compensate for reactivity changes ?
CEA movement controls:
-power in core
-variations in moderator temp & boron concentrations
-Dampens axial xenon oscillations
How does CEDMCS allow CEAs to drop into the core ?
CEAs drop into core upon interruption of power to Control Element Drive Mechanism(CEDM) Coil Stack
What system does CEDMCS send a signal too upon a reactor trip ?
-Main Turbine
-Feedwater control system
-Steam bypass control system
-Emerg. Response Facility Digital Acquisition Display System(ERFDADS)
-SRP Plant Multiplier
Why does CEDMCS provide signals for CEA positioning ?
CEA position is used as an indication to assure reactivity control has maintained plant within safety limits
What provide powers the Legacy CEDMCS system ?
Non-Class 480VAC Load Centers
-NGN-L03
-NGN-L10
What is the generators output voltage for the Legacy CEDMCS ?
Out out of generator is 240VAC that is sent through load contractor & circuit interrupters
What is the normal operation for the Legacy CEDMCS Motor generator set?
Both of the Motor Generators are operating in parallel
What does Reactor Protection System do for the CEDMCS system ?
Reactor Protection System will interrupt power going through Reactor Trip Switchgear Breakers deenergizing CEDMCS cabinets to trip reactor
What is a Power Switch Assembly used for on the Legacy CEDMCS ?
Rectifies 240VAC into 60VDC and sends it to Control Element Drive Mechanisms(CEDM) coil stacks in the associated subgroups
Where does CEDMCS accept CEA motion signals from ?
-Reactor Regulating System(RRS)for automatic control
-Operators module on board 4 manual control
What does the Power Switch Assembly do when it’s receives a CEA motion signal demand ?
PSA will supply appropriate power to the CEDM coils to either hold, withdraw, or insert CEAs
Where does CEDMCS receive demand control signals for CEA operations for Legacy CEDMCS ?
-Reactor Power Cutback system
-Plant Computer
What do the Legacy Motor Generator Sets do ?
Convert 480VAC power from NG system into 240VAC power from CEDMCS system
What is the generator rated at ?
-200kW
-240VAC
-60HZ
-601Amperes
What’re the Flywheels meant for on the Motor Generators ?
Provide rotational inertia for MG set during momentary transients
If MG set loses all power for 1 second, what’re the parameters it should maintain supplying full load?
-voltage shouldn’t decrease more than 5% below 240VAC
-Frequency shall not decrease below 58Hz
What set points do under voltage and under frequency relay initiate a MG trip ?
-Under voltage will trip at 210VAC
-Under frequency will trip at 57Hz
Why should both MG sets be running before moving CEAs?
They have to be running before CEAs are moved in:
-Auto Sequential
-Manual Group
-Manual Sequential
How is CEA motions limited to when only ONE MG set is operating ? Why must motion be limited ?
-Limited to Manual Individual to minimize potential of slipping or dropping rod
Whatre the controls in Square Black Line meant for on the each MG set control panel ?
The controls inside the square black line are meant to control the other MG set
What’re the controls located inside the MG set control panel ?
3 MG set overloads reset pushbuttons
-Motor Running Overload
-Motor Starter Overload
-Generator Running Overload
Two MG set high vibration resets located on each MG set
What should be done when there are a row of red alarm lights going across MG control cabinet ? How’re the red lights reset ?
Problem should be addressed via:
-Operating procedure
-Alarm Response Procedure
Pushbutton on each MG set control cabinet is for manually resetting local light and alarm input