FINALS: RA 9514 FIRE CODE Flashcards
(15 cards)
Every exit of buildings or structures shall be arranged and maintained to provide free and unobstructed
egress from all parts thereof at all times. _________________ that would prevent escape from the
inside of any building shall be installed
No lock or fastening device
Every exit shall be _____________. The route to the exit shall be ______________ in such a manner that
every occupant of a building or structure will readily know the direction of escape.
clearly visible | conspicuously marked
A door from a room to an exit or to a way of exit access shall be of the _________________. It shall swing with exit travel.
side-hinged, swinging
type
The minimum headroom shall not be less than ______________nor any projection from the
ceiling be less than _____________________ from the floor
two meters (2 m)
Signage letters must be at least _________high with a stroke width of _______
15 cm high | 19 mm
n emergency evacuation plan shall be posted on strategic and conspicuous locations in the building. This shall be drawn with a ______________________ to be readable in case of power failure.
photoluminescent background
The minimum dimension for emergency evacuation plan shall be ____________ in height and __________ in width.
8 ½ inches | 11 inches
fire alarm boxes shall be so located that from any part of the building not more than
_____________________________ horizontal distance on the same floor must be traversed in order to reach a fire
alarm box.
thirty meters (30 m) horizontal distance
The main exit shall be of sufficient
width to accommodate _____________ of the total occupant load, but shall be not less than the total
required width of all aisles, exit passageways and stairways leading thereto, and shall connect to a
stairway or ramp leading to a street.
one-half (1/2)
Each level of an assembly occupancy shall have access to the main exit and an addition shall be
provided with exits of sufficient width to accommodate ___________________ of the total occupant load served by that level.
two-thirds (2/3)
The width of any exit access corridor serving 50 or more persons shall not be less than one
________________.
hundred twelve centimeters (112 cm)
The letters “NO SMOKING” shall be made readable and recognizable within a minimum distance of __________________ at any given time,
fifteen and one fourth meters (15.25 m)
The letters “NO SMOKING” shall be made readable and recognizable within a
minimum distance of fifteen and one fourth meters (15.25 m) at any given time, at least _____________ high
ten centimeters (10 cm)
The letters “NO SMOKING” shall be made readable and recognizable within a minimum distance of fifteen and one fourth meters (15.25 m) at any given time, at least ten centimeters (10 cm) high preferably with _____________________________________________
white-colored letters upon a red background
In no case shall a signage of “SMOKING AREA” be of _______________________ from the “NO SMOKING” sign.
different color