Important Values, Figures, and Thresholds Flashcards

(8 cards)

1
Q

Combustible Gas Detector (CGD) Alarm Threshold

A

Must alarm when detecting combustible gas concentrations exceeding 10% Lower Explosive Limit (LEL). If measured concentrations exceed 10% LEL, the auditor must inform homeowners, advise evacuation, leave the home, and notify emergency services/fuel providers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Ambient Carbon Monoxide (CO) Action Levels

A

70 ppm or greater: Immediately terminate inspection, notify homeowner/occupant to evacuate building, auditor immediately leaves, notify emergency services from outside.

36 ppm - 69 ppm: Advise homeowner/occupant of elevated levels, open windows/doors, recommend turning off all possible CO sources, and contact a qualified professional if source is a permanently installed appliance.

9 ppm - 35 ppm: Advise CO detected, recommend checking all possible CO sources, opening windows/doors, and contacting a qualified professional if source is a permanently installed appliance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Minimum Required Slope of a Vent Connector (Combustion Appliances)

A

One-quarter inch per linear foot of positive rise from the appliance to the vertical flue.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Minimum Clearance for Water Heaters in a Garage

A

Must be a minimum of 18 inches above the floor, unless listed as flammable vapor ignition resistant (FVIR)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Maximum Allowable BTUh for Unvented Heaters

A

Overall: Maximum 40,000 BTUh.
In a bedroom: Not more than 10,000 BTUh.
In a bathroom: Not more than 6,000 BTUh

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

CO Thresholds for Fossil Fuel-Fired Combustion Appliances (Air-Free unless noted)

A

400 ppm air free: Central Furnace, Boiler, Floor Furnace, Gravity Furnace, Wall Furnace (Direct Vent), Clothes Dryer, Gas Log (installed in wood burning fireplace).
200 ppm air free: Wall Furnace (BIV), Vented Room Heater, Unvented Room Heater, Water Heater.
225 ppm as measured: Oven/Broiler.
25 ppm as measured: Refrigerator, Gas Log (gas fireplace)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Recommended Minimum R-Value for Duct Insulation

A

R-8 for ducts in vented attics and other unconditioned zones, including encapsulated attics and semi-conditioned crawl spaces. In humid climate zones, metal cooling system ducts and plenums inside the thermal boundary shall be insulated to R-8 to prevent condensation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Duct Leakage Action Level (Qualitative Testing with Pressure Difference)

A

If pressure difference exceeds 3 Pa, duct sealing shall be recommended