Module 2 Test Questions Electrical Study Deck Flashcards
Service entrance conductors run from the service drop to the service box or service panel. T/F
True
The service size is determined by the amperage and voltage ratings of the service. T/F
True
Is the service drop overhead or underground?
overhead
Are service laterals overhead or underground?
underground
The drip loop is typically part of the service drop. T/F
False
The wire size for the service drop must be the same as the wire size for the service entrance conductors. T/F
False
How many wires would you typically find in a 240-volt service drop?
3
What would 4 wires mean?
Three phase electricity
What would 2 wires usually mean?
120 volts service
List 7 common problems with service drops.
overhead wires too low, damaged or frayed wires, trees or vines interfering with wires, wires too close to doors or windows, wires not well secured to the house, poor connection between service drop & service entrance, inadequate clearance from roofs
List clearances above ground, swimming pools, and roofs.
above roadway-18 ft
above driveway-12 ft
above flat roof-8-10 ft
above sloped roof-18 inches
away from water in pool-22 1/2 ft in any direction
3 feet above sloped roof w/pitch greater than 4 in 12
above walkway-10 ft
The service entrance conductors run from the __ to the __.
from service drop to the service box
All service entrance conductors must be in conduit. T/F
False
All service entrance conductors must be attached above roof level. T/F
False
The drip loop should be as close to the roof surface as possible. T/F
False
List 10 common problems with service entrance conductors.
No drip loop
No mast head
Mast head not weather-tight
Mast or conduit bent
Mast or conduit rusted
Mast rotted
List 4 common areas of water penetration into service entrances.
Conduit joints, mast head, roof flashing, meter base
List 2 functions of the drip loop.
prevents water entry into the conduit or service entrance, shows that the service drop wires are not straining the splice (???)
Roughly 999 out of 1,000 houses have __ volts available
240
Roughly 999 out of 1,000 houses have __ service entrance wires
Three
Load calculations are part of a home inspection. T/F
False
Implications of an undersized service include:
a. shock hazard
b. fire hazard
c. shock & fire hazard
d. melting insulation
e. nuisance tripping of the main fuses or breakers
nuisance tripping of the main fuses or breakers
What is the largest single-phase service that you are likely to find in a home?
400 amps
What size copper wire would you expect to find on the service entrance for:
a. A 60-amp service
b. A 100-amp service
c. A 200-amp service
a. 6 gauge
b. 4 gauge
c. 2-0 gauge