PLUMBING CODE III Flashcards
(119 cards)
Maximum number of slip joint fitting that may be used on the outlet side of a trap
Correct answer: 1
Source: RNPCP, Chapter 10
“No more than one (1) approved slip joint fitting may be used on the outlet
side of a trap”
Elastomeric gasketed and rubber-ring joints shall comply with _____ installation standard
Correct answer: IAPMO (International Association of Plumbing and Mechanical officials)
Source: RNPCP, Chapter 13
ASTM
American Society for Testing and Materials
ANSI
American National Standards Institute
NAMPAP
National Master Plumbers Association of the Philippines
What is the maximum length allowed for a vent stack serving 48 DFU?
Correct answer: 55 m
Source: RNPCP, Chapter 7
length of vent can accommodate 24 DFU
37 m
length of vent can accommodate 84 DFU
65 m
What will be the size of 0.5% sloped circular bottom gutter serving a roof area of 180 sqm, and the rainfall intensity around the area is 76 mm/hr?
Correct answer: 178 mm
Source: RNPCP, Chapter 11
Additional Info:
You may refer to Table 11-2a, however, do not expect that the board exam includes table for reference.
You may use the formula taught in our classes to solve this kind of problem.
A water that stands in or passes through the ground
Correct answer: Ground water
Source: RNPCP, Chapter 2
runs off over the surface of the ground
Surface water
runs off over the earth surface after a storm
Storm water
Minimum water seal of a grease trap
Correct answer: 51 mm
Source: RNPCP, Chapter 10
water seal of an interceptor or clarifier
152 mm
The size of a vent pipe is determined by _____.
Correct answer: FU and length
Source: RNPCP, Chapter 7, Table 7-5, and Chapter 9
Which of the following may be true about the sovent system?
Correct answer: it has lesser maintenance cost
Additional info:
- Among the choices, “it has lesser maintenance cost” is the best answer. In some cases, sovent may also require lesser up-front cost as it requires lesser space, labor, and pipe network. There are also fewer maintenance points.
- Sovent system does not require more space for installation, as it eliminates the need for more branch/group venting, and the main vent. Hence, the sovent system does not also use more pipe network.
- Aerator and deaerator fittings help maintain air pressure. The stack is also terminated at the roof.
Wet venting is limited to _____ fixtures
Correct answer: 4
Source: RNPCP, Chapter 8
limit of wet venting
1 and 2 fixture unit trap arm
What is the estimated sewage flow rate of bowling alleys with snack bar only?
Correct answer: 283.9 LpD per lane
Source: RNPCP, Annex B
You may convert the values to Gallons for easier memorization.
_____ are recommended for oil handling piping works.
Correct answer: Neoprene gaskets
Source: RNPCP, Chapter 13
a mechanical connection which depends on an internal retention device to prevent pipe or tubing separation
Pressure-Lock Type
used for hubless cast iron
Shielded Coupling
used for high-pressure applications such as air-conditioning, refrigeration
Brazing
In getting the roof area for the computation of rainwater piping size, for two walls opposite of differing heights, add ____ of wall area above top of lower wall to the roof area.
Correct answer: 50%
Source: RNPCP, Chapter 12