Power Supply Nuke Service pump A
P 480V ES
Power Supply Nuke Service pump B
S 480V ES
NS V 15 power supply
1 C ESV MCC
NS-V-35
1B ESV MCC
NS-V-4
1A ESV MCC
NS-V-32
1C ESV
NS-V-52/53 a,b,c power supply
1E DC, 1F DC, 1M DC
why shouldn’t you cross connect decay closed and nuke service?
because nuke service is pressurized, overflow decay closed
what is NS-V-135 for?
excess flow check valve
scenario: lowering level in nuke service, get low level alarm in, then get an ES.
you need to push the button to reset or that interlock will stay active
IC-V-2,3,4, and 6 power supply
1B ES, 1E ES, M DC, M DC
intermediate closed pump power supply
A and B ES MCC
intermediate closed filters purpose
protect CRDM by trapping ferrous material
if you lose CRDM cooling, how long to hit trip criteria (time) and temp, and how many?
about 7 mins, 2 stators of 180F +
if IC-V-1’s are mid travel and lose power
it stops where it’s at
RCDT cooler permissive IC-V-4 operating temp
90-105
3 conditions to clsoe Ic-v-74
2 closes, 3 closes, or 4 and 6 both close
RM-L-9 location
spent fuel pool as well as surge tank
main steam stop check valves location and power supply
intermediate building, power supply C ES valves
condensor vacuum interlock
less than 23” of vacuum or less than 2 circ water pumps, MS-V-3’s close and steam goes to atmosphere
stop check valves location and alarm actions/setpoints
intermediate building. if alarm go to 90% if you can’t get it back open, go to 15%.
MS-V-13a/B open sequence/time
a opens immediately, then 53 seconds later b opens to prevent overspeeding
MS-V-10, DC operated when?
when you have low steam pressure
normal conditions of ms-v-10a/b
valves closed, breakers open