2002 NRC Flashcards
(104 cards)
When Rod Control was placed in AUTO during a Unit 2 power escalation the following conditions were noted:
• Nuclear Instrumentation Power Range Channels 15% and rising
• Power Range Low Power Trip NOT Blocked
• Intermediate Range Trip NOT Blocked
• Control rods withdrawing at 64 steps per minute
Which ONE of the following actions are required in accordance with 02-OHP-4022-012-003, Continuous Control Bank Movement?
a. Trip the reactor if rods do not automatically stop at the 20% Low Power Rod Stop.
b. Trip the turbine and initiate emergency boration.
c. Trip the turbine and verify automatic reactor trip.
d. Trip the reactor if rod motion continues when Rod Control is placed in MANUAL.
d. Trip the reactor if rod motion continues when Rod Control is placed in MANUAL.
The following plant conditions exist:
• Rod H-8 in Control Bank D is at 200 steps.
• The remaining Control Bank D rods are at 219 steps.
• Reactor power is 73%
• A faulty card has been replaced.
• Reactor Engineering has directed that Control Bank D be aligned to Rod H-8.
Which ONE of the following states the action(s) to be taken to perform this recovery?
Open disconnect switch for…
a. rod H-8, select Control Bank D on rod control, set Group Demand Counters to 200 steps, and reposition Control Bank D.
b. rod H-8, select Manual on rod control, and reposition Control Bank D. Group Demand Counters do not need to be changed.
c. Control Bank D rods except H-8, select Bank D on rod control, set Group Demand Counters to 200 steps, and reposition rod H-8.
d. Control Bank D rods except H-8, select Manual on rod control, and reposition rod H-8. Group Demand Counters do not need to be changed.
b. rod H-8, select Manual on rod control, and reposition Control Bank D. Group Demand Counters do not need to be changed.
A Component Cooling water leak inside containment has caused reduced flow to the RCPs.
The following conditions exist:
• Unit 1 is at 100% power.
• Temperatures / RCP # 11 12 13 14
Motor Bearing 196°F 178°F 189°F 173°F
Lower Bearing Water 195°F 184°F 201°F 184°F
Seal Leakoff 187°F 176°F 177°F 179°F
• Ann 107 Drop 52, RCP Vibration High - NOT LIT
Which ONE of the following set of actions must be taken?
a. Immediately Trip the Reactor, then trip RCP#11.
b. Open QRV-150, No. 1 Seal Bypass Valve.
c. Perform a rapid Plant Shutdown and stop RCP#13 within 30 minutes.
d. Immediately Trip the Reactor, then trip RCP#13.
a. Immediately Trip the Reactor, then trip RCP#11.
Following a rapid power reduction from 80% power due to a Feedwater pump trip, the following plant conditions exist on Unit 1:
• Reactor power is 59%.
• Turbine Power is 620 Mwe.
• Rod Control is in MANUAL.
• All other controls in AUTO.
• Feedwater and Steam Flows are equal.
• An Emergency Boration is being performed per 01-OHP-4021-005-007, Operation Of Emergency Boration Flow Paths, due to the ROD BANK D LOWLOW (Rod Insertion Limit) alarm being lit.
The procedure states “Check for indication of negative reactivity addition.”
Given these conditions, which ONE of the following would be used to verify that negative reactivity is being added?
a. Tref lowering
b. Tavg lowering
c. ROD BANK D LOW-LOW alarm clearing
d. A flow of 44 gpm indicated on QFI-410
b. Tavg lowering
The Emergency Remote Shutdown Procedure 2-OHP-4025-R-3-5, Sharing 1E CCW, limits total CCW flow to the CCW Heat Exchangers in BOTH units to no greater than 9,000 GPM, if only one CCW pump is in operation and supplying both units.
This limitation…
a. ensures sufficient CCW capacity to the UNAFFECTED unit.
b. precludes placing BOTH units in jeopardy by overloading the operating CCW pump.
c. minimizes thermal transients on the AFFECTED unit’s equipment.
d. precludes exceeding the design flow limits through BOTH unit’s CCW Heat Exchangers.
b. precludes placing BOTH units in jeopardy by overloading the operating CCW pump.
The Unit 2 reactor failed to automatically trip when the reactor coolant pumps tripped.
The following conditions exist after a MANUAL Turbine Trip is attempted per 2-OHP-4023-FRS-1, Response to Nuclear Power Generation/ATWS step 3.
• Turbine Stop Valve Closed Status Lights - 1 and 3 Lit
• Turbine Stop Valve Closed Status Lights - 2 and 4 NOT Lit
• MAIN TURBINE STOP VALVE CLOSED alarm - Lit
• AMSAC INITIATED alarm - Lit
Which ONE of the following is the NEXT action the operator is required to take?
a. Manually reduce turbine load.
b. Shut the Main Steam Stop Valves.
c. Verify AFW Pumps running.
d. Manually actuate AMSAC.
a. Manually reduce turbine load. (Runback)
Upon entry into OHP-4023-FR-S-1, Response to Nuclear Power Generation/ATWS, which ONE of the following is the fastest method of adding negative reactivity to the core prior to locally opening the Reactor Trip breakers?
a. Manual insertion of control rods
b. Initiation of Emergency Boration
c. Manual actuation of Safety Injection
d. Initiation of maximum AFW flow to the SGs
a. Manual insertion of control rods
During a secondary side fault, following completion of Steam Generator blow down, it is important to minimize and control the amount of RCS heatup in OHP-4023-ES-1-1, SI Termination, to prevent:
a. PZR overfill and water relief through the PZR PORVs and avoid exceeding tech spec heatup limits.
b. exceeding minimum DNBR limits and limit the DP across the faulted SG tubes.
c. exceeding minimum DNBR limits and avoid exceeding tech spec heatup limits.
d. PZR overfill and water relief through the PZR PORVs and limit the DP across the tubes of the faulted SG.
d. PZR overfill and water relief through the PZR PORVs and limit the DP across the tubes of the faulted SG.
A station emergency battery is supplying DC bus loads without a battery charger online. If the equipment on the DC bus does NOT change, which ONE of the following statements describes a vital battery’s discharge rate (amps) as the battery is expended?
a. The discharge rate will be fairly constant until the design battery capacity (amphours) is exhausted and then will rapidly decrease.
b. The discharge rate will increase steadily until the design battery capacity is exhausted.
c. The discharge rate will decrease steadily until the design battery capacity is exhausted.
d. The discharge rate will initially decrease until approximately 50% design capacity had been expended and then increase until the battery has been exhausted.
b. The discharge rate will increase steadily until the design battery capacity is exhausted.
Given the following Unit 1 plant conditions:
• 1-OHP-4023-ECA-0-0, Loss of All AC Power, is in effect.
• Depressurization of Unit 1 steam generators is in progress.
1-OHP-4023-ECA-0-0, step 19 requires the depressurization to be stopped if at least one SG narrow range level cannot be maintained greater than 8%.
Which ONE of the following is the concern behind this requirement?
a. Loss of adequate heat sink due to reduced heat transfer area
b. PTS due to excessive cooldown
c. RCS voiding due to rapid depressurization
d. Loss of natural circulation due to accumulator nitrogen injection
a. Loss of adequate heat sink due to reduced heat transfer area
Given the following:
• Unit 2 is operating at full power.
• A HIGH alarm is received on R-19, SG Blowdown Sample Radiation monitor.
Which ONE of the following describes automatic response of the Blowdown System to this alarm?
a. Blowdown discharge isolation (DRV 350) trips closed, Blowdown Sample Isolation valves (DCR 301 - 304) trip closed.
b. Blowdown discharge isolation (DRV 350) trips closed, Blowdown Sample Isolation valves (DCR 301 - 304) remain open.
c. Blowdown treatment pump trips, Blowdown Containment Isolation valves (DCR-310 - 340) trip closed.
d. Blowdown treatment pump trips, Blowdown Containment Isolation valves (DCR-310 - 340) remain open.
a. Blowdown discharge isolation (DRV 350) trips closed, Blowdown Sample Isolation valves (DCR 301 - 304) trip closed.
Which ONE of the following describes a procedural requirement of 02-OHP-4022-019-001, ESW System Loss / Rupture, in the event that ESW cannot be IMMEDIATELY restored?
a. Open the doors to the Motor Driven Auxiliary Feedwater Pump rooms.
b. Stop all Upper Containment Ventilation fans.
c. Place both CTS Pumps in Pull-to-lock.
d. Stop all Control Room Air Conditioning Units and place system in ISOLATE.
a. Open the doors to the Motor Driven Auxiliary Feedwater Pump rooms.
While operating at full power, the operators in Unit 1 Control Room respond to the following:
• Annunciator Panel 101 / Drop 41, ’FIRE’ alarm.
• Annunciator Panel 101 / Drop 94, ’REACTOR COOLANT PUMP FIRE OR ABN’ alarm.
• Below the #11 RCP control switch, the operators note the following status lights LIT:
• (White) OPEN/LEAK
• (Red) FIRE
Which ONE of the following describes the status of the #11 RCP fire protection system?
a. NESW water is being sprayed on #11 RCP.
b. #11 RCP fire protection system is ready for manual initiation.
c. Fire Suppression System water is being sprayed on #11 RCP.
d. #11 RCP fire protection system will automatically initiate spray water to the RCP approximately 2 minutes after the red and white lights both illuminate.
b. #11 RCP fire protection system is ready for manual initiation.
Given the following:
• Unit 1 is in Mode 5.
• The U-1 AB EDG is available.
• The U-1 CD EDG is available.
• The U-1 East Motor Driven AFW pump is available.
• The U-1 West Motor Driven AFW pump is Tagged Out
• Unit 2 is in Mode 1.
• The U-2 East AFW Pump is Tagged Out for discharge valve replacement.
• All other equipment is operable.
Maintenance requests to tag out the U-1 CD EDG for a Governor replacement.
Without any compensating measures (fire watches), would this be allowed or disallowed per the requirements of 01-OHP-4030-066-4025, Unit 1 Appendix R and Ventilation Requirements for Unit 2 surveillance and why?
a. Allowed, because either U-1 EDG is acceptable per the Appendix R Surveillance.
b. Allowed, because NO U-1 EDG power is required as long as an AFW pump from each train is available (U-2 West and U-1 East).
c. Disallowed, because the U-1 CD EDG is required to support the U-1 East AFW pump availability to U-2 since a U-2 fire could cause a loss of Unit 1 Offsite power.
d. Disallowed, because the U-1 CD EDG is required to support the U-1 East AFW pump availability to U-2 whenever the U-2 East AFW pump is inoperable.
c. Disallowed, because the U-1 CD EDG is required to support the U-1 East AFW pump availability to U-2 since a U-2 fire could cause a loss of Unit 1 Offsite power.
The operators are performing OHP-4023-FR-Z-1, Response to High Containment Pressure, in response to containment pressure of 4.6 psig during an accident.
The operators are required to check if feedwater should be isolated to any SG in order to:
a. prevent possible SG overfill from over pressurizing the steamlines.
b. raise containment integrity by reducing the number of open penetrations.
c. minimize containment pressure rise due to faulted SG(s).
d. reduce the potential for causing a feed line break due to thermal stresses.
c. minimize containment pressure rise due to faulted SG(s).
Which ONE of the following conditions represents a LOSS of CONTAINMENT INTEGRITY in accordance with Technical Specification 3.6.1.1, Containment Integrity?
a. While in MODE 1, an electrician opens the outer airlock door at the lower containment access without prior approval.
b. While in MODE 3, during an inspection of an equipment hatch, it is determined that the equipment hatch is NOT sealed.
c. While in MODE 4, Containment internal pressure is found to be -0.5 psig prior to placing Containment Purge in service.
d. While in MODE 5, during performance of the Overall Integrated Containment Leakage Rate Test, Containment leakage exceeds the maximum allowable Technical Specification leakage rates.
b. While in MODE 3, during an inspection of an equipment hatch, it is determined that the equipment hatch is NOT sealed.
Given the following:
• A 800 gpm LOCA has occurred on Unit 1.
• A number of failures occurred with ECCS equipment which resulted in Core Exit Temperatures reaching 1255°F 20 minutes ago.
• Restoration efforts have been ineffective so far.
• Containment radiation level is 2.37 R/Hr.
• Containment Pressure is 4.6 psig.
• DAP is inoperable.
Which ONE of the following represents the correct Emergency Plan Classification and impact to the fission product barriers? (PMP-2080-EPP-101, Emergency Classification, attached)
a. Alert due to LOSS of RCS. Cladding and Containment are INTACT.
b. Site Area Emergency due to LOSS of RCS and POTENTIAL LOSS of Cladding. Containment is INTACT.
c. General Emergency due to POTENTIAL LOSS of RCS, LOSS of Cladding, and LOSS of Containment.
d. General Emergency due to LOSS of RCS, LOSS of Cladding, and POTENTIAL LOSS of Containment.
d. General Emergency due to LOSS of RCS, LOSS of Cladding, and POTENTIAL LOSS of Containment.
The following conditions exist:
• The Unit 1 reactor tripped 10 minutes ago and a LOCA is in progress.
• RCS wide range pressure is 1800 psig and slowly lowering.
• No CCPs are running.
• RCS Core Exit Temperatures are 755°F.
• Containment pressure is 3.5 psig and stable.
• PZR level is 56% and rising.
• RWST level is 55% and lowering.
With these indications, PZR level is …
a. NOT a valid indication of RCS inventory and RWST level is as expected at this point in the accident.
b. NOT a valid indication of RCS inventory and RWST level is lower than expected at this point in the accident.
c. a valid indication of RCS inventory but RWST level is lower than expected at this point in the accident.
d. a valid indication of RCS inventory and RWST level is as expected at this point in the accident.
b. NOT a valid indication of RCS inventory and RWST level is lower than expected at this point in the accident.
A Safety Injection (SI) occurred 20 minutes ago due to a large break LOCA, with a failure of reactor trip breaker “B” to open.
Which ONE of the following describes the SI signal response after pushing both SI reset pushbuttons?
a. “A” train SI is reset, and “B” train SI is NOT reset.
b. Both “A” train and “B” train SI’s are reset.
c. Neither “A” train nor “B” train SI’s is reset.
d. “B” train SI is reset, and “A” train SI is NOT reset.
a. “A” train SI is reset, and “B” train SI is NOT reset.
A steam line break has occurred on Unit 1 SG #11. The break was isolated and Safety Injection (SI) has just been terminated. The following plant conditions exist:
• East CCP aligned to VCT with normal charging and letdown in service
• SI and RHR pumps shutdown
• RCPs are stopped
• Pressurizer pressure = 1800 psig and rising
• Pressurizer level = 64% and rising
• RCS Core Exit temperature = 533 F and rising
• Containment pressure = 0.1 psi
• SG levels (NR) 0%(#11) 13%(#12) 20%(#13) 20%(#14)
• SG pressures (psig) 0 (#11) 825(#12) 830(#13) 830(#14) and stable
Which ONE of the following actions are required for plant recovery and why?
a. Raise AFW flow to stabilize the heatup to prevent pressurizer overfill.
b. Raise Charging flow to raise the Pressurizer level to 82% to enable RCP start.
c. Reinitiate High Head SI flow to stop the heatup.
d. Close SG PORVs to allow plant to return to normal temperature and pressure.
a. Raise AFW flow to stabilize the heatup to prevent pressurizer overfill.
Given the following:
• The crew has entered OHP-4023-FR-C-2, Response to Degraded Core Cooling.
• RCS Hot Leg Temperatures are 300°F.
• RVLIS NR indication 37%.
Which ONE of the following would be most effective in restoring core cooling?
a. Depressurizing SGs to Atmospheric Pressure.
b. Aligning BIT flow from the Opposite Unit.
c. Starting a Residual Heat Removal Pump.
d. Starting a Reactor Coolant Pump.
c. Starting a Residual Heat Removal Pump.
The following conditions exist:
• Reactor has tripped from 100% power due to a loss of off-site power.
• Natural circulation has been verified.
Which ONE of the following describes the response of core Delta T if the plant remains in hot shutdown?
a. Delta T will lower due to the smaller heat generation over time.
b. Delta T will rise as the water in the SGs heats up.
c. Delta T will rise due to lack of cooling to the upper vessel head.
d. Delta T will lower due to the addition of cold AFW to the SGs.
a. Delta T will lower due to the smaller heat generation over time.
Unit 2 operators are performing 2-OHP-4023-ES-0-2, Natural Circulation Cooldown.
• 2-OHP-4023-ES-0-2, Natural Circulation Cooldown, has been entered because offsite power had been lost.
• The EDGs started and energized the AC emergency buses.
• The CRDM cooling fans cannot be manually loaded onto the AC emergency buses.
• Condensate Storage Tank water inventory is adequate for the cooldown.
Which ONE of the following describes HOW the inoperability of the CRDM fans affects the cooldown and depressurization?
a. It has no effect because the amount of RCS heat removed by running the CRDM fans is insignificant compared to the heat removed by steaming the secondary plant.
b. The total upper head area cooldown rate will be less, so greater subcooling must be maintained.
c. Transition to 2-OHP-4023-ES-0-3, Natural Circulation Cooldown with Steam Void in Vessel, will be required because cooldown and depressurization will cause formation of a void in the upper head area.
d. Less subcooling should be maintained to enhance the cooldown of the upper head area, which reduces the formation of voids.
b. The total upper head area cooldown rate will be less, so greater subcooling must be maintained.
The second step of OHP-4023-ES-0-3, Natural Circulation Cooldown With Steam Void in Vessel, directs the operator to try to start a Reactor Coolant Pump in accordance with OHP-4023-SUP-010, Starting Reactor Coolant Pump(s).
Assuming that RVLIS indicates less than full, why is Pressurizer Level required to be raised to 82% prior to starting a RCP?
a. Ensure that the RCP will have sufficient Net Positive Suction Head for the given plant conditions.
b. Ensure that when the RCP is started a subsequent decrease in Pressurizer Level will not uncover the heaters and/or result in a loss of pressure control.
c. Ensure that there is sufficient mass in the Pressurizer to fill the vessel head should a bubble form, to prevent allowing saturated fluid from entering the SG tubes.
d. Ensure that the Pressurizer will be able to maintain RCS pressure high enough to prevent Nitrogen injection from the Accumulators.
b. Ensure that when the RCP is started a subsequent decrease in Pressurizer Level will not uncover the heaters and/or result in a loss of pressure control.