Exd Fault Code - Full Check List Flashcards
Exd Fault Codes - Includes Grade of Inspection (46 cards)
Exd: FAULT CODE A1 :
Equipment is appropriate to the EPL/Zone requirements of the location.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A2 :
Equipment Group is correct.
DETAILED, CLOSE
Exd: FAULT CODE A.3 :
Equipment temperature class is correct (only for gas).
DETAILED, CLOSE
Exd: FAULT CODE A.5 :
Degree of protection (IP grade) of equipment is appropriate for the level of protection/group/conductivity.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.6 :
Equipment circuit identification is correct.
DETAILED
Exd: FAULT CODE A.7 :
Equipment circuit identification is available.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.8 :
Enclosure, glass parts and glass-to-metal sealing gaskets and / or compounds are satisfactory.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.9 :
There is no damage or unauthorized modifications.
DETAILED
Exd: FAULT CODE A.10 :
There is no evidence of unauthorized modifications.
CLOSE, VISUAL
Exd: FAULT CODE A.11 :
Bolts, cable entry devices (direct & indirect) and blanking elements are of the correct type, are complete and tight.
Cable Glands are of correct type and correctly installed for the location, and type of enclosure
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.12 :
Threaded covers on enclosures are of the correct type, are tight and secured.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.13 :
Joint surfaces are clean and undamaged and gaskets, if any, are satisfactory and positioned correctly.
DETAILED
Exd: FAULT CODE A.14 :
Condition of enclosure gaskets is satisfactory.
DETAILED
Exd: FAULT CODE A.15 :
There is no evidence of ingress of water or dust in the enclosure in accordance with the IP rating.
DETAILED
Exd: FAULT CODE A.16 :
Dimensions of flange joint gaps are:
- within the limits in accordance with manufacturer’s documentation or
- within maximum values permited by relevant construction standard at time of installation or
- within maximum values permited by site documentation
DETAILED
Exd: FAULT CODE A.24 :
Breathing operation is satisfactory - (type “nR” only)
DETAILED
Exd: FAULT CODE A.25 :
Breathing and draining devices are satisfactory
DETAILED, CLOSE
Exd: FAULT CODE A.27:
HID lamps are not indicating end-of-life effects.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.28 :
Lamp type, rating, pin configuration and position are correct.
DETAILED
Exd: FAULT CODE A.29 :
Motor fans have sufficient clearance to enclosure and / or covers, cooling systems are undamaged, motor foundations have no indentations or cracks.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.30 :
The ventilation airflow is not impeded.
DETAILED, CLOSE, VISUAL
Exd: FAULT CODE A.31 :
Insulation resistance (IR) of the motor windings is satisfactory.
DETAILED
Exd: FAULT CODE B.1 :
Type of cable is appropriate.
DETAILED
Exd: FAULT CODE B.2 :
There is no obvious damage to cables.
DETAILED, CLOSE, VISUAL