Exd: FAULT CODE A1 :
Equipment is appropriate to the EPL/Zone requirements of the location.

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Exd: FAULT CODE A2 :
Equipment Group is correct.

A

DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Exd: FAULT CODE A.3 :
Equipment temperature class is correct (only for gas).

A

DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Exd: FAULT CODE A.5 :
Degree of protection (IP grade) of equipment is appropriate for the level of protection/group/conductivity.

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Exd: FAULT CODE A.6 :
Equipment circuit identification is correct.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Exd: FAULT CODE A.7 :
Equipment circuit identification is available.

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Exd: FAULT CODE A.8 :
Enclosure, glass parts and glass-to-metal sealing gaskets and / or compounds are satisfactory.

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Exd: FAULT CODE A.9 :
There is no damage or unauthorized modifications.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Exd: FAULT CODE A.10 :
There is no evidence of unauthorized modifications.

A

CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Exd: FAULT CODE A.11 :
Bolts, cable entry devices (direct & indirect) and blanking elements are of the correct type, are complete and tight.
Cable Glands are of correct type and correctly installed for the location, and type of enclosure

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Exd: FAULT CODE A.12 :
Threaded covers on enclosures are of the correct type, are tight and secured.

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Exd: FAULT CODE A.13 :
Joint surfaces are clean and undamaged and gaskets, if any, are satisfactory and positioned correctly.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Exd: FAULT CODE A.14 :
Condition of enclosure gaskets is satisfactory.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Exd: FAULT CODE A.15 :
There is no evidence of ingress of water or dust in the enclosure in accordance with the IP rating.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Exd: FAULT CODE A.16 :
Dimensions of flange joint gaps are:
- within the limits in accordance with manufacturer’s documentation or
- within maximum values permited by relevant construction standard at time of installation or
- within maximum values permited by site documentation

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Exd: FAULT CODE A.24 :
Breathing operation is satisfactory - (type “nR” only)

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Exd: FAULT CODE A.25 :
Breathing and draining devices are satisfactory

A

DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Exd: FAULT CODE A.27:
HID lamps are not indicating end-of-life effects.

A

DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Exd: FAULT CODE A.28 :
Lamp type, rating, pin configuration and position are correct.

20
Q

Exd: FAULT CODE A.29 :
Motor fans have sufficient clearance to enclosure and / or covers, cooling systems are undamaged, motor foundations have no indentations or cracks.

A

DETAILED, CLOSE, VISUAL

21
Q

Exd: FAULT CODE A.30 :
The ventilation airflow is not impeded.

A

DETAILED, CLOSE, VISUAL

22
Q

Exd: FAULT CODE A.31 :
Insulation resistance (IR) of the motor windings is satisfactory.

23
Q

Exd: FAULT CODE B.1 :
Type of cable is appropriate.

24
Q

Exd: FAULT CODE B.2 :
There is no obvious damage to cables.

A

DETAILED, CLOSE, VISUAL

25
Exd: FAULT CODE B.3 : Sealing of trunking, ducts, pipes, conduits is satisfactory.
DETAILED, CLOSE, VISUAL
26
Exd: FAULT CODE B.4 : Stopping boxes and cable boxes are correctly filled.
DETAILED
27
Exd: FAULT CODE B.5 : Integrity of conduit system and interface with mixed system is maintained.
DETAILED
28
Exd: FAULT CODE B.6 : Earthing connections, including any supplementary earthing bonding connections are satisfactory (for example connections are tight and conductors are of sufficient cross-section).
DETAILED, CLOSE, VISUAL
29
Exd: FAULT CODE B.7 : Exd: FAULT loop impedance (TN systems) or earthing resistance (IT systems) is satisfactory.
DETAILED
30
Exd: FAULT CODE B.8 : Automatic electrical protective devices are set correctly (auto-reset not possible).
DETAILED
31
Exd: FAULT CODE B.9 : Automatic electrical protective devices operate within permitted limits.
DETAILED
32
Exd: FAULT CODE B.10 : Specific conditions of use (if applicable) are complied with.
DETAILED
33
Exd: FAULT CODE B.11 : Cables not in use are correctly terminated.
DETAILED
34
Exd: FAULT CODE B.12 : Obstructions adjacent to flameproof flanged joints are in accordance with IEC 60079-14. (IIA = 10 mm, IIB = 30 mm, IIC = 40 mm).
DETAILED, CLOSE, VISUAL
35
Exd: FAULT CODE B.13 : Variable voltage / frequency installation in accordance with documentation.
DETAILED, CLOSE
36
Exd: FAULT CODE B.14 : Temperature sensors function according to manufacturer's documentation
DETAILED
37
Exd: FAULT CODE B.15 : Safety cut off devices function according to manufacturer's documentation
DETAILED
38
Exd: FAULT CODE B.16 The setting of the safety cut off is sealed
DETAILED, CLOSE
39
Exd: FAULT CODE B.17 : Reset of a heating system safety cut off possilbe with tool only
DETAILED, CLOSE
40
Exd: FAULT CODE B.18 : Auto-reset is not possilbe
DETAILED, CLOSE
41
Exd: FAULT CODE B.19 : Reset of a safety cut off under fault conditions is prevented
DETAILED
42
Exd: FAULT CODE B.20 : Safety cut off indepedent from control system
DETAILED
43
Exd: FAULT CODE B.21 : Level switch is installed and correctly set, if required
DETAILED
44
Exd: FAULT CODE B.22 : Flow Switch is installed and correctly set, if required
DETAILED
45
Exd: FAULT CODE C.1 : Equipment is adequately protected against corrosion, weather, vibration and other adverse factors.
DETAILED, CLOSE, VISUAL
46
Exd: FAULT CODE C.2 : No undue accumulation of dust and dirt.
DETAILED, CLOSE, VISUAL