Exi Fault Code - Full Check List Flashcards
Exi Fault Codes - Includes Grade of Inspection (32 cards)
FAULT CODE A.1
Circuit and/or equipment documentation is appropriate to the EPL/Zone requirements. : DETAILED, CLOSE, VISUAL
FAULT CODE A.2
Equipment installed is that specified in the documentation. : DETAILED, CLOSE
FAULT CODE A.3
Circuit and/or equipment category and group correct. : DETAILED, CLOSE
FAULT CODE A.4
IP rating of equimpent is appropriate to the Group III material present. : DETAILED, CLOSE
FAULT CODE A.5
Equipment temperature class is correct. : DETAILED, CLOSE
FAULT CODE A.6
Ambient temperature range of the apparatus is correct for the installation. : DETAILED, CLOSE
FAULT CODE A.7
Service temperature range of the apparatus is correct for the installation. : DETAILED, CLOSE
FAULT CODE A.8
Installation is clearly labelled. : DETAILED, CLOSE
FAULT CODE A.9
Enclosure, glass parts and glass-to-metal sealing gaskets and / or compounds are satisfactory. : DETAILED
FAULT CODE A.10
Cable glands and blanking elements are the correct type, complete and tight. Cable Glands are of correct type and correctly installed for the location, and type of enclosure. : DETAILED, CLOSE,VISUAL
FAULT CODE A.11
There are no unauthorized modifications. : DETAILED
FAULT CODE A.12
There is no evidence of unauthorized modifications. : CLOSE, VISUAL
FAULT CODE A.13
Diode safety barriers, galvanic isolators, relays and other energy limiting devices are of the approved type,
installed in accordance with the certification requirements and securely earthed where required. : DETAILED, CLOSE, VISUAL
FAULT CODE A.14
Condition of enclosure gaskets is satisfactory. : DETAILED
FAULT CODE A.15
Electrical connections are tight. :DETAILED
FAULT CODE A.16
Printed circuit boards are clean and undamaged. : DETAILED
FAULT CODE A.17
The maximum voltage Um of the associated apparatus is not exceeded. : DETAILED, CLOSE
FAULT CODE B.1
Cables are installed in accordance with the documentation. : DETAILED
FAULT CODE B.2
Cable screens are earthed in accordance with the documentation. : DETAILED
FAULT CODE B.3
There is no obvious damage to cables. : DETAILED, CLOSE, VISUAL
FAULT CODE B.4
Sealing of trunking, ducts, pipes and/or conduits is satisfactory. : DETAILED, CLOSE, VISUAL
FAULT CODE B.5
Point-to-Point connections are all correct (Initial inspection only). : DETAILED
FAULT CODE B.6
Earth continuity is satisfactory (e.g. connections are tight, conductors are of sufficient cross-section)
for non-galvanically isolated circuits. : DETAILED
FAULT CODE B.7
Earth connections maintain the integrity of the type of protection. : DETAILED