1
Q

FAULT CODE A.1

A

Circuit and/or equipment documentation is appropriate to the EPL/Zone requirements. : DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

FAULT CODE A.2

A

Equipment installed is that specified in the documentation. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

FAULT CODE A.3

A

Circuit and/or equipment category and group correct. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

FAULT CODE A.4

A

IP rating of equimpent is appropriate to the Group III material present. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

FAULT CODE A.5

A

Equipment temperature class is correct. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

FAULT CODE A.6

A

Ambient temperature range of the apparatus is correct for the installation. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

FAULT CODE A.7

A

Service temperature range of the apparatus is correct for the installation. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

FAULT CODE A.8

A

Installation is clearly labelled. : DETAILED, CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

FAULT CODE A.9

A

Enclosure, glass parts and glass-to-metal sealing gaskets and / or compounds are satisfactory. : DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

FAULT CODE A.10

A

Cable glands and blanking elements are the correct type, complete and tight. Cable Glands are of correct type and correctly installed for the location, and type of enclosure. : DETAILED, CLOSE,VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

FAULT CODE A.11

A

There are no unauthorized modifications. : DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

FAULT CODE A.12

A

There is no evidence of unauthorized modifications. : CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

FAULT CODE A.13

A

Diode safety barriers, galvanic isolators, relays and other energy limiting devices are of the approved type,
installed in accordance with the certification requirements and securely earthed where required. : DETAILED, CLOSE, VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

FAULT CODE A.14

A

Condition of enclosure gaskets is satisfactory. : DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

FAULT CODE A.15

A

Electrical connections are tight. :DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

FAULT CODE A.16

A

Printed circuit boards are clean and undamaged. : DETAILED

17
Q

FAULT CODE A.17

A

The maximum voltage Um of the associated apparatus is not exceeded. : DETAILED, CLOSE

18
Q

FAULT CODE B.1

A

Cables are installed in accordance with the documentation. : DETAILED

19
Q

FAULT CODE B.2

A

Cable screens are earthed in accordance with the documentation. : DETAILED

20
Q

FAULT CODE B.3

A

There is no obvious damage to cables. : DETAILED, CLOSE, VISUAL

21
Q

FAULT CODE B.4

A

Sealing of trunking, ducts, pipes and/or conduits is satisfactory. : DETAILED, CLOSE, VISUAL

22
Q

FAULT CODE B.5

A

Point-to-Point connections are all correct (Initial inspection only). : DETAILED

23
Q

FAULT CODE B.6

A

Earth continuity is satisfactory (e.g. connections are tight, conductors are of sufficient cross-section)
for non-galvanically isolated circuits. : DETAILED

24
Q

FAULT CODE B.7

A

Earth connections maintain the integrity of the type of protection. : DETAILED

25
FAULT CODE B.8
Intrinsically safe circuit earthing is satisfactory. : DETAILED
26
FAULT CODE B.9
Insulation resistance is satisfactory. (Sample Inspections only). : DETAILED
27
FAULT CODE B.10
Separation is maintained between intrinsically safe and non-instrinsically safe circuits in common distribution boxes or relay cubicles. (between terminals, minimum clearance 50mm). : DETAILED
28
FAULT CODE B.11
Short-circuit protection of the power supply is in accordance with the documentation. : DETAILED
29
FAULT CODE B.12
Specfic conditions of use (if applicable) are complied with. : DETAILED
30
FAULT CODE B.13
Cables not in use are correctly terminated. : DETAILED
31
FAULT CODE C.1
Equipment is adequately protected against corrosion, weather, vibration and other adverse factors. : DETAILED, CLOSE,VISUAL
32
FAULT CODE C.2
No undue external accumulation of dust and dirt. : DETAILED, CLOSE,VISUAL