FAULT CODE A.1
Equipment is appropriate to the EPL/Zone requirements of the location. : DETAILED, CLOSE, VISUAL
FAULT CODE A.2
Equipment Group is correct. : DETAILED, CLOSE
FAULT CODE A.3
Equipment temperature class is correct (gas only). : DETAILED, CLOSE
FAULT CODE A.4
Equipment maximum surface temperature is correct (dust only). : DETAILED, CLOSE
FAULT CODE A.5
Degree of protection (IP) of equipment is appropriate for the level of protection/group/conductivity. : DETAILED, CLOSE, VISUAL
FAULT CODE A.6
Equipment circuit identification is correct. : DETAILED
FAULT CODE A.7
Equipment circuit identification is available. : DETAILED, CLOSE, VISUAL
FAULT CODE A.8
Enclosure, glass parts and glass-to-metal sealing gaskets and / or compounds are satisfactory. : DETAILED, CLOSE, VISUAL
FAULT CODE A.9
There is no damage or unauthorized modifications. : DETAILED
FAULT CODE A.10
There is no evidence of unauthorized modifications. : DETAILED, CLOSE
FAULT CODE A.11
Bolts, cable entry devices (direct & indirect) and blanking elements are of the correct type, are complete and tight.
Cable Glands are of correct type and correctly installed for the location, and type of enclosure. : DETAILED, CLOSE, VISUAL
FAULT CODE A.14
Condition of enclosure gaskets is satisfactory. : DETAILED
FAULT CODE A.15
There is no evidence or ingress of water or dust in the enclosure in accordance with the IP rating. : DETAILED
FAULT CODE A.17
Electrical Connections are tight. : DETAILED
FAULT CODE A.18
Unused terminals are tightened (gas only). : DETAILED
FAULT CODE A.19
Enclosed-break and hermetically sealed devices are undamaged (‘n’ only). : DETAILED
FAULT CODE A.20
Encapsulated components are undamaged (gas only). : DETAILED
FAULT CODE A.21
Flameproof components are undamaged (gas only). : DETAILED
FAULT CODE A.22
Restricted breathing enclosure is satisfactory (type ‘nR’ only). : DETAILED
FAULT CODE A.23
Test port, if fitted, is functional (type ‘nR’ only). : DETAILED
FAULT CODE A.24
Breathing operation is satisfactory (type ‘nR’ only). : DETAILED
FAULT CODE A.25
Breathing and draining devices are satisfactory (gas only). : DETAILED, CLOSE
FAULT CODE A.26
Fluorescent lamps are not indicating end-of-life effects. : DETAILED, CLOSE, VISUAL
FAULT CODE A.27
HID lamps are not indicating end-of-life effects. : DETAILED, CLOSE, VISUAL