Fire Pumps Flashcards

(244 cards)

1
Q

Fire pumps are rated for a net pressure of ____ or more

A

40 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fire pumps rated for 5000 gpm and over are subject to individual review by

A

Authority having jurisdiction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When installing fire pumps, steel pipe must be used ______

A

Above ground

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is tuberculation

A

Small Knobs or buttons of rust on the inside of the pipe

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is used to prevent tuberculation

A

Galvanized or painted on the inside of piping

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is not permitted with pipe & fittings

A

Thick bituminous linings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Steel piping is joined by

A

Screwed
Flanged
Welded
Grooved

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When can slip type fittings be used

A

-When piping is mechanically secured to prevent slippage
-When pump and its suction supply are on separate foundations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

NFPA 51B is the standard for

A

Fire prevention in use of cutting and welding process

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

All pump discharge pipes are required to be _____

A

Hydrostatically tested

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What must be installed in the pump discharge assembly

A

Back-flow preventor or check valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What can large systems experience when a fire pump shuts down

A

Water hammer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What shall be installed on the system side of the check valve

A

Butterfly or gate valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A clearance of not less then ____ inch is required around all pipes that pass through walls or floors

A

1”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Holes through the pump room fire walls should be packed with

A

Mineral wool

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Holes through fire pump floor may be filled with

A

Asphalt mastic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Gauge located on or near discharge casting size

A

3-1/2” diameter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Gauge located on or near discharge pressure scale and units

A

-At least twice the rated working pressure of the pump, not less then 200psi
-Must read in Bar, or PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Suction pipe gauge is a

A

Vacuum and compound pressure gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Suction pipe gauge size

A

3-1/2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Suction pipe gauge must read in what units and have a scale of

A

-Inches of mercury (Hg) or PSI
-2x rated maximum suction pressure, not less then 100psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Fire pump is any device which does what

A

Takes water from any type of source and increases the pressure of that water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Jockey pumps are also referred to as

A

Pressure maintenance pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Why are jockey pumps installed

A

To increase system pressure without turning fire pump on

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Jockey pump is designed so it
Comes on before fire pump and returns system to its minimum static pressure
26
Jockey pumps are usually ____ pressure and ______ flow pumps
High pressure, Low flow pumps
27
2 types of pumps found in fire protection are
Centrifugal and positive displacement
28
Most common kind of pump in fire protection is
Centrifugal pump
29
What is the most important part of a centrifugal pump
Impeller
30
What guides water from the eye to the discharge to avoid turbulence
Vanes
31
Vanes on impeller are curved
Away from the direction of rotation
32
Single suction impeller is
Water enters the eye on one side
33
Double suction impeller is
Water enters the eye on both sides
34
What allows the shaft to pass through the pump while maintaining an air tight seal
Packing
35
Each entrance and exit of shaft must have
Packing
36
Packing material is designed to be lubricated with
Water
37
What happens if the packing gland is over tightened
Packing will dry out, crumble, cause pump damage
38
How often should pump run to lubricate packing
Once a week
39
Pumps with only one impeller are how many stages
1 stage
40
Volume and pressure rating in single stage pump are determined by
Size of impeller Speed at which it rotates
41
Pumps with more then one impeller on same shaft are
Multiple stage pumps
42
Number of impellers on shaft determines what
Number of stages
43
Multiple stage pumps can operate in 2 different manners which are
In series, and in parallel
44
Pumping in parallel increases
Total flow from pump
45
Pumping in series increases
Total pressure output of the pump
46
Multistage pumps are often used in
Series
47
Horizontal pump is
Shaft between the engine and the impeller is run in horizontal plane
48
Vertical pump is
A pump where the shaft between engine and the impeller is run in a vertical plane
49
What is a end suction pump
Single suction pump On opposite side of stuffing box
50
Horizontal split case pump is
Horizontal pump where the casing is split along the same axis as the shaft between engine and impellers
51
in-line pump is
Any pump with suction and discharge flanges along centreline
52
Vertical (shaft) turbine pump is
Pump with impellers suspended by conductor system. Vertical shaft is along the same axis as the discharge from impeller
53
What is the only pump exempt from needing Postive pressure at the suction
Vertical (Line) shaft turbine pump where
54
What pump is designed to bring water from a static source
Vertical (Line) shaft turbine pump
55
Can pump is slang for
Vertical in line type pump or any vertical pump installed in a pipe for boosting pressure rather then from a static source
56
Why is an eccentric tapered reducer used on suction side of fire pump
Avoids turbulence and air pockets
57
How should eccentric reducer be installed
Flat side on TOP
58
If suction can go below 20 psi, what is needed
Compound gauge capable of registering negative pressure on suction
59
When taking suction from a tank the suction pressure cannot drop below
0 psi while pump is @ 150%
60
What can happen if a negative suction pressure happens
-Fire pump and piping could Cavitate -infiltration of ground water
61
Discharge pressure gauge is beneficial to be
Liquid filled (they dampen the pressure fluctuations)
62
What does an automatic air release do
Reales air in casing that could cause impeller damage
63
Relief valves are not intended too
Control pressure, they are intended to relief pressure from overspeed
64
What is a way to look at discharge with relief valve
Sight glass
65
What is the purpose of the discharge check valve
keep pressurized liquid from coming back through fire pump
66
What is necessary for a jockey to keep pressure on system
Check valve
67
Valve on test header is supervised in the normally ____ position
Closed
68
Most common way of testing a fire pump
Test header
69
What’s the purpose of a flow metre
Measure flow rate from fire pump if in a loop piped back to the pump suction
70
If a flow metre is used, what must be done every 3 years
Discharge performance test
71
Fire pump controllers purpose is too
Monitor, start/stop fire pump.
72
What kind of switch is used to tell the controller to start the fire pump
Mercoid or pressure transducer
73
Jockey pump must have its own
Controller
74
Where is fire pump sensing line connected
One end to Myceroid/pressyrw transducer within controller and other end to FP piping between discharge check and control valve
75
When May jockey pumps require 2 check valves
With high pressure fire pump. (Check holds pressure on the system so when fire pump is on the pressure does not go through Jockey)
76
FDC should be installed where with fire pumps
Downstream of the fire pump discharge check valve
77
How is back pressure avoided with exhausts
Proper sizing and fittings
78
Purpose of fire pump bypass
Allows the water supply to provide some pressure to the system should the fire pump fail
79
Diesel engine battery have how much capacity
2x the capacity at 40F, sufficient to maintain cranking speed
80
Battery’s must be capable of
- 3 minute attempt to start cycle -15 seconds of cranking & 15 seconds of rest - 6 times
81
Where is heat exchanger fed from
Pump discharge
82
Controllers should be located
Within sight of the motors
83
Controllers will show net pressure up too
400psi
84
Pump house maintained at
40F
85
Electric monthly pump run time
10 minutes
86
Fuel tanks shall be kept a minimum of
2/3rds full
87
Most common cooling method is
Constant flow heat exchanger
88
Diesel fire pump run for how long
30 minutes
89
Engine must reach operating speed within
20 seconds
90
Annual fire pump test (electric driven pumps) when is voltage and amperage recorded
Each of the 3 phases
91
How is pump speed measured
A tachometer or speed counter
92
Annual pump test is how long
30 minutes
93
Power failure condition should be simulated at
Peak load (150%)
94
The controller should provide a crank cycle for how long
3-15 seconds
95
Lubricating oils should be replaced after how many hours
50
96
NFPA for generators
NFPA 110
97
Sensing line pipe size
Not less then 1/2” -brass, copper, series 300 stainless steel
98
If a water pulsation causes erratic operation, what is required
Supplemental air chamber, or pulsation damper
99
How many check valves in sensing line and what is in them
- 2 check valves - 3/32 hole in clapper
100
When can check valves with 3/32 hole for sensing line be omitted
With clean water, ground face unions with non corrosive diaphragms drilled at 3/32 instead
101
Where is a pump coupling used
To connect the rotating pump shaft to the drive shaft of the motor
102
When is a pump coupling not required
If a pump is close coupled (on single shaft)
103
A close coupled to pump has the impeller directly mounted to the
Motor shaft
104
Rigid coupling is
Coupling that permits little to no movement between the shafts (Best for precise alignment)
105
Flexible coupling is
Any coupling that can permit some degree of relative motion between the shafts
106
Sleeve or muff coupling is
-Simplest of the rigid couplings -cast iron sleeve -gib head key is used to restrict relative motion
107
Flange coupling is
Coupling with flange put onto each shaft
108
What is a Gear coupling
-Similar to flange coupling but is flexible -can accommodate misalignment of 0.25-0-5mm (2 degrees)
109
What is a universal joint (hooked joint)
For when 2 shafts are parallel, and intersect at a small angle
110
Oldham coupling is
-used exclusively for lateral shaft misalignment
111
Diaphragm coupling is
Great all rounder shaft coupling. Can accommodate misalignment as well as high angular and axial misalignment
112
Jaw coupling is
-Material fabric coupling -low power transmission and motion control applications.
113
Beam coupling is
-Machined coupling -high flexibility -the best for low power transmission
114
Churn pressure is
No flow, pump is running but no water moving
115
What is rated pressure
100% of pump demand
116
What is peak demand
150% of pump demand
117
Net pressure is
Pressure produced by a pump
118
Rating of fire pump is determined by
The hydraulic calculation and available water supply
119
Lantern ring is only installed where supply is less then
30 psi
120
Dual impeller design
670’ of head rated for 290psi
121
Vertical In line impeller orientation
Rotates horizontal
122
Net pressure for vertical in line pumps
175psi
123
End suction pumps max gpm and net pressure
1500gpm 159psi
124
Cannot get an End suction pump less then how many gal in fire protection
500gal
125
Horizontal split case impeller orientation
Rotates on vertical plane
126
Horizontal split case gpm and psi
250-5000gal Net 640psi
127
Size of circulation relief valve for pumps not more then 2500gpm
3/4”
128
Size of circulation relief valve for pumps 3000-5000gpm
1”
129
Pumps connected to adjustable speed drivers shall have
Listed relief valve
130
2 types of relief valves are
Spring loaded Pilot operated diaphragm
131
The relief valve shall NOT be piped too
The pump suction of supply connection
132
Hose valves shall have the
NH standard external thread as per NFPA 1963
133
Metering devices/fixed nozzles for fire pump testing shall be listed for water flow of not less then
175% of pumps rated capacity
134
Where is the water inlet for an end suction pump
The water inlet is at the end, rather then on the side
135
Where is the motor mounted for a horizontal shaft split case pump
Beside the pump
136
Horizontal pump 3 designs are
Split case End suction In Line
137
The motor and pump are usually mounted on ______ for Horizontal shaft split case pump
A common base plate and connected W/ a coupling
138
Where is the electric motor mounted for the horizontal split case vertically mounted in pump
On top/above pump
139
Inline pump is defined as
Variation of end suction style, with the inlet and outlet connections in a straight line
140
As capacity increases, the total Pressure that the pump is capable of developing is
Reduced
141
When is the highest point of pressure with a fire pump
Churn
142
The gauge at a pump suction tank shall be capable of
Dropping to -3psi with the lowest water level after
143
Size of bypass around fire pump
At least as large as the pipe size required for the discharge pipe
144
Elbows with the centreline plane parallel to the pump should be
Avoided, unless the distance between suction flange and elbow is 10x suction pipe diameter
145
Horizontal shaft pumps are usually what volute type
Double suction
146
Suction supply control valve must be what kind of valve
OS&Y
147
If a butterfly valve is used on fire pump discharge, they must not be installed within
50 feet of the pump suction flange
148
What is cavitation
Formation of air bubbles, or cavities that collapse into yep they reach high pressure
149
What does cavitation do to fire pumps
-Produce high pressure surges -blast particles out of impeller -cause a drop in efficiency -vibration can cause bearing failure, shaft breakage
150
Where suction supply is from public water mains, the gate valve should be located
As far as practical from suction flange on pump
151
Where the suction comes from a stored water container, the gate valve should be located
At the outlet of container
152
Exceptions of devices in suction piping
-Shut off valve -Check valves/backflows -Pressure sensitive flow control valves
153
Pumps that are automatically controlled must be provided with a
Listed float operated air release not less then 1/2” in size
154
When is an automatic air release not required
For end suction pumps with top centre line discharge valve or in line pumps
155
Pumps rotate which direction
Both clockwise and counter clockwise
156
Diesel engines are commonly stocked and supplied to rotate
Clockwise
157
The pump and driver shall be mounted on a
Common base plate
158
The foundation top for fire pump pad should be how far below desired finish and why
3/4”-1 1/2” for grout
159
Prior to grouting what is done to pad
Roughen the foundation top with chisel
160
After pad is grouted, alignment is checked after how long
48 hours
161
Purpose of flexible coupling is
Compensate for temperature change, permit end movement of shafts
162
What is angular misalignment
Shafts with axis that are concentric but not parallel
163
Parallel misalignment is
Shafts with axis that are parallel but not concentric
164
Angular alignment is checked with
Taper gauge or feeler gauge
165
How do you check parallel alignment
Placing straightedge across both coupling and rims at the top bottom and both sides
166
Are are misalignments corrected
Shims under motor mounting feet
167
The best method final accurate alignment for coupling halves is done with
Dial indicator
168
What does the arrow on pump indicate
The direction of the rotation of the pump
169
After unit has been in operation for 10 hours or three months what is done
Final check for misalignment
170
Horizontal shaft pumps after lubricated with
Water
171
If pump is forced to operate and the packing gland is too tight, how much x the normal current is need
6x
172
Minimum churn pressure is
101% of rated pressured
173
Max churn pressure is
140% of rated pressure
174
How far apart are the check valves in sensing line
Minimum 5 feet apart
175
The turbine pump is what kind of pump
Vertical shaft centrifugal pump
176
The column pipe in a turbine pump as serves as
Support for the shaft and bearings
177
Turbine pump is suitable for when water source is
Below ground
178
What kind of turbine pump protects the pump from sandy/dirty water
Oil lubricated pumps
179
When a vertical shaft turbine pump is in a well, the pump bowl assembly shall not be less then
Second impeller is 10 ft below the pumping water level @ 150% of rated capacity (Submergence must increase 1 foot every 1000ft of elevation)
180
When a vertical shaft turbine pump is used in a wet pit, where is the pump bowl
Second impeller from the bottom is Below the lowest pumping water level in the open body of water
181
The distance between the bottom strainer and the Bottom of the wet pit shall be at least
One half the pump bowl diameter but not less then 12”
182
Minimum size of air release on vertical shaft turbine pump
1-1/2”
183
All vertical pump installations are required to have a
Non-reverse ratchet
184
Current carrying parts on controllers shall not be less then how far from ground
12”
185
A fire pump controller cannot be used as what
Junction box for any other equipment
186
Most controllers for sprinkler systems are
Automatic
187
A pressure switch must have the capability of having how much pressure put on it
400 psi or 133% of the controllers rated operating pressure
188
Pressure switch cannot contain a
Pressure snubber or restricted orifice
189
Pump must start within how long after alternate power is put on
15 seconds
190
If more then one pumping unit is used, the units shall start at intervals of
5 to 10 seconds
191
If a controller is set for an automatic shut down, after everything returns to normal, what is the minimum timer
10 minutes
192
Spark ignited Internal combustion engines are not permitted for installations since when
1974
193
What type of battery for diesel
Lead acid
194
Battery location for diesel
Must be rack supported Min 12” from floor
195
Where is the supply cooling water for the engines heat exchanger taken from
Discharge side of pump on pump side of the discharge check
196
Each clean filter in bypass for cooling water line shall permit full water flow for how long
3 hour
197
Waste outlet from heat exchanger size
Not be less then one size larger then inlet line. If more then 15 feet of pipe is used/outlet is more than 4 feet higher than the heat exchanger, pipe must be increased by 1 size
198
Fuel supply line must be located where
5% above bottom of tank
199
A seamless, flexible connection of not less then ____ between the engine exhaust outlet and the pipe
12”
200
If exhaust is longer then 15 feet what must be done
Increase one pipe size larger then engine exhaust outlet (Plus for every 5 feet past the 15 feet, additional 1 pipe size is added)
201
Engine jacket heater temp
120F
202
At what temp do diesel engines require water and oil heaters
70F
203
What is the “attempt to start” cycle
Six crank periods 15 second duration or cranking 15 second rest period
204
What is the jockey pump start & stop point
Stop - Churn pressure + minimum static pressure Start - 10psi below stop
205
Fire pump start point
5 psi less then jockey
206
Min pressure @ peak performance is
Cannot be less then 65% of pump demand (rated pressure)
207
Main role of lantern ring
Stop air from being sucked into suction casing
208
Pump packing drip minimum
1 drip per second
209
Packing materials
Rope with Polytetrafluorethylene Rope with Graphite
210
What kind of flow is best?
Laminar
211
Each valve on test header (2 1/2) is capable of how much gpm
250
212
Controllers are rated for what HP
30hp
213
Controller voltage
600v or less
214
Most common controller for electrical pump
Full service
215
How many phases on automatic controller
3 phase
216
What kind of motors on electric fire pump
Squirrel cage or wound Rotor motors
217
Diesel pump room maintained at what temp
70F
218
Electric fire pump room min temp
40F
219
Clearance requirements for controller
3 feet
220
Types of impellers
Open Semi closed Closed
221
Types of driver mounting methods for centrifugal pumps
Frame mounted Close coupled Separately coupled
222
What supports the electric motor on a vertical pump
C-Frame
223
2 different types of positive displacement pumps are
Reciprocating & Rotary
224
What type of pump is a diaphragm pump
Reciprocating
225
What type of pump traps fluid and rotates it to the discharge outlet
Rotary
226
What type of pump is an excess pressure pump
Rotary external gear pump
227
What type of bearing configuration does an end suction pump have
Overhung impeller
228
Where should a pressure relief valve be installed on a fire pump
Between discharge flange and check valve
229
What must be provided in all valve rooms
Heat Lighting Drain Ventilation
230
Where are positive displacement pumps used
Wet systems Foam systems Water mist systems
231
Types of fire pumps that an electric driver motor can be attached too
Vertical inline/Turbine Horizontal split case Vertical split case End suction
232
What additional equipment do you need when installing electric driven fire pumps
-Variable speed controller -Generator
233
What do you need if a power source is not deemed adequate for a fire pump
Power transfer switch Alternate power
234
Types of fire pumps that can be connected to a diesel engine driver
-Horizontal split case -End suction -Vertical Turbine with right angle gear drive
235
Three methods for starting diesel driven fire pumps
Battery Hydraulic Pneumatic
236
Testing pressure for all piping serving fire pumps
200 psi or 50 psi in excess of normal pressure
237
What device is used to keep fire pump cool during a churn test
Circulation relief valve
238
Minimum distance backflow shall be from suction of fire pump
10x pipe diameter
239
How often are test gauge calibrated for fire pump flow test
Annually
240
Where is the test connection located on the discharge side of a fire pump
Between discharge check and discharge control valve
241
Another term used for churn pressure
Shut off
242
What component helps reduce velocity and increase pressure
Volute casing
243
What is the required minimum velocity when flushing piping serving a fire pump
15ft/sec
244
4 most common couplings we used are
Disc coupling Jaw coupling Grid coupling Universal Joint coupling