National Building Code Flashcards
NBCP (100 cards)
P.D 1096
National Building Code of the Philippines
Maximum height of a combustible stand.
2.70 m
Minimum spacing for seats in a chair type measurement from back to back
0.85 m
Maximum line of travel to an exit of an aisle.
45.00 m
Maximum slope of an aisle
One is to Eight (1:8)
In standard seating, the minimum spacing of rows measured from back to back.
0.84 m
Minimum width of any seat.
0.45 m
Minimum area of a double acting door view panel.
1,300 sq.mm / 1.30 sq.m
Minimum clear width of an exit door way.
0.70 m
Maximum width of an exit door leaf.
1.20 m
Minimum width of an exit corridor.
1.10 m
Minimum number of exit for floors above the first storey having an occupant load of more than 10
2
Number of exit for occupant load of 599-999
3
Minimum downward projection of a draft curtain..
0.30 m
Maximum floor area for an attic made of combustible materials.
250 sq.m
Maximum center to center spacing of a draft curtain sprinkler.
1.80 m
Maximum floor area for an attic made of incombustible materials.
750.00 sq.m
Standard gauge for metal hoods in barbeques.
Ga 18
Minimum height of a Siamese connection above grade.
300 mm
Standard maximum distance of a standpipe from an opening in a stairway.
300 mm
Minimum wall thickness of a fireplace.
200 mm
Minimum number of exit for a projection room.
2
Minimum extended portion of a chimney above the roof.
600 mm
Minimum air space between walls of a masonry chimney above the roof.
2” / 50 mm