PEC 1 Flashcards
the maximum electrical trade size of intermediate conduit (mm)
100 mm
is a type of permit needed before starting any installation work, alternation, repair or extension on any electrical system
Electrical permit
The PEC is intended for _________ applications by government bodies exercising legal jurisdiction over electrical installation
mandatory
Equipment for instal lation in hazardous locations must be tested and approved for use
according to the classification of the hazardous involved. These are divided into ______
3 groups
Individual branch circuits using type FCC (Flat Conductor Cable) shall have ratings not exceeding \_\_\_\_(A)
30 A
__________ is applicable for underground service entrance conductors
USE type conductor
If there are three wires of 150 mm2 connected to one terminal entering a cabinet or a
switchboard, the bending space at each terminal shall NOT be less than _______,(mm) provided the conductors do not enter or leave the enclosure through the wall opposite i ts terminals.
250 mm
A clearance of not less than ______(mm) shall be secured between bare current carrying metal
parts and any metal surface of an auxiliary gutter
26 mm
No box shall have an internal depth of less than _____(mm)
12 mm
Which of the following electrical conductor has the highest resistance?
(3.5 mm2, 8.0 mm2, 2.0 mm2, 5.5 mm2).
Note: Resistance is inversely proportional to the cross -sectional area of the conductor wire
2.0 mm2
_______ is a device or equipment which is suspended from overhead either by means of a
flexible cord carrying the current, or otherwise.
Pendant
In the schedule of loads for motor circuits, which of the following is NOT included?
(Type of motor, Motor ’s manufacturer , Motor as numbered or identified in the power layout,
number of phase).
Motor ’s manufacturer
____(A) is the allowable ampacity of THW insulated copper conductor with an area of 8.0 mm2
and exposed to an ambient temperature of 30C.
45 A
For two conductors inside the conduit, the ampacity of the conductors shall be derated to
what percent?
(90%, 80%, 70%, none of these).
Note: Derating is appl icable only if there
are 3 or more wires.
none of these
Electrical equipment may best be mounted on a concrete wall by using an ________
expansion bolt.
What is the neutral load of a range that has a demand load of 10.4 kW?
7.28 kW
Neutral Load =70% of demand load (0.7) (0.4 kW) = 7.28 kW
If the project is extensive and requires more time for checking and for computations of
fees, the issuance of the electrical permi t need not be issued immediately. However, the
delay shall not be longer than ________
5 working days
Splices in ground conductors shall be as few as practicable and shall be attached so as to
withstand a pull test of
890 Newtons
______ locations are hazardous because of the presence of combustible dust.
Class II
Al l located parts within _____(mm) of the lighting protection system shall be bonded
thereto.
1,800 mm
_______ is an operation at substantially constant load for an indefinitely long time. (April 2016)
Continuous duty
Transformer exceeding 112.5 kVA, shall not be located within ______(mm) from combustible materials of the building.
300 mm
Electrodes of iron or steel plates shall be at least______(mm) in thickness.
6.4 mm
The frame of the vehicle-mounted generator shall be permitted to serve as the grounding electrode for a system supplied by a generator located on the vehicle under the following conditions:
- The vehicle of the generator is bonded to the vehicle frame.
- The generator supplies only equipment located on the vehicle.
- The non-current carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame