Unit 8: Single Family Dwelling Service Calculations Flashcards

Understand service load calculations, apply NEC 2023 factors, and evaluate compliance for residential installations. (25 cards)

1
Q

Fill in the blank:

An acceptable color for conductors intended for use as ungrounded conductors is _________.

A

orange

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

A metal underground water pipe is permitted for use as a grounding electrode where the water pipe is in direct contact with the earth for at least _________ or more.

A

10 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

For low-voltage lighting systems operating not exceeding 30 volts ac or 60 volts dc, the output circuits of the power supply are to be rated for not more than _________ under all load conditions.

A

25 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where a 12-kW portable generator is used for temporary wiring on a construction site, which receptacle outlets are mandated to provide ground-fault circuit interrupter protection for personnel?

A
  • 125/250-volt receptacles
  • 15-ampere receptacles
  • 20-ampere receptacles
  • 30-ampere receptacles
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

An unintentional, electrically conducting connection between an ungrounded conductor of an electrical circuit and the normally non-current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment or earth is referred to as a _________ in the NEC®.

A

ground-fault

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

Where GFCI protection is not provided, ceiling-suspended (paddle) fansare is not permitted to be located _________.

A

indoors, over a spa or hot tub, less than 12 ft. above the maximum water level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which of the following underground installed buried metal pipes is approved for use as a grounding electrode?

I. A water pipe, in direct contact with the earth for 8 ft.
II. A gas pipe, in direct contact with the earth for 30 ft.

A

neither I nor II

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fill in the blank:

For an overhead type motor fuel dispensing device located at a service station or a convenience store, the space within the dispenser enclosure shall be classified as a _________ location.

A

Class I, Division 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Disregarding exceptions, and assume the modification of the value you selected is not necessary, determine the maximum trip setting permitted for the overload devices used to protect a 3-phase, 10 hp, 208-volt, continuous-duty motor with a FLA of 28 amperes and a temperature rise of 42°C marked on the motor nameplate.

A

32.2 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the primary function of the neutral conductor in an electrical system?

A

It is connected to the neutral point of an electrical system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

The overcurrent protection for feeders and branch circuits that serve electric vehicle supply equipment, shall be sized at not less than _________ of the maximum load of the electric vehicle supply equipment.

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

Stationary ac motors require the _________ where installed in a Class I, Zone 2 atmosphere that is considered a hazardous or classified location.

A

frame of the motor shall be grounded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Given: A rigid metal conduit (RMC) originates in an area that is unclassified, then passes through a Class I, Division 1 area, and finally terminates in a panelboard located in an unclassified area. The RMC is without any connections or fittings when passing through the Class I,Division 1 area or within a foot on either size of the boundary of the Class I,Division 1 location. How many seal-off fittings are required in this conduit run?

A

none

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Given: A 3-phase, 240-volt delta system is balanced with a 15 kVA load per phase (45,000 VA total load). What is the line current in amperes?

A

108.2 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blanks:

Generally, where switches or circuit breakers are used as the main disconnecting means for a building service, they shall be installed such that the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than _________, _________ above the floor or working platform.

A

6 feet, 7 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Fill in the blank:

The service equipment for a mobile home shall have an ampere rating of not less than _________ at 120/240-volts, single-phase.

17
Q

What is the required characteristic of an intersystem bonding termination?

A

It shall be connected to the meter enclosure only, with a minimum size 8 AWG conductor.

18
Q

Fill in the blank:

For 120-volt, 15- and 20-ampere branch circuits, the rating of any one(1)cord-and-plug connected utilization equipment not fastened in place shall not exceed _________ of the branch circuit ampere rating.

19
Q

Fill in the blank:

The National Electrical Code® requires ventilation of a battery room where batteries are being charged to prevent _________.

A

an accumulation of an explosive mixture

20
Q

Where a building has a service rated at 1,200 amperes and multiple driven ground rods are used as part of the grounding electrode system, what is the minimum size copper conductor that may be used to bond the ground rods together?

21
Q

Fill in the blank:

All 15- and 20-ampere, 125- and 250-volt, non locking receptacles located in a wet location shall be listed _________ type.

A

weather-resistant

22
Q

Fill in the blank:

Where liquidtight flexible metal conduit (LFMC) is used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation _________.

A

a wire-type equipment grounding conductor shall be installed

23
Q

Fill in the blank:

Luminaires shall be installed so that adjacent combustible material is not subjected to temperatures in excess of _________.

24
Q

Fill in the blank:

A household gas furnace with a one (1) hp motor protected with a circuit breaker accessible to the user, does not require a disconnecting means if provided with a _________.

A

unit switch that disconnects all ungrounded conductors

25
# Fill in the blank: In switchboards and panelboards, a 3-pole circuit breaker or fusible switch shall be considered as \_\_\_\_\_\_\_\_\_.
3 overcurrent protection devices