Unit 5: Box and Raceway Sizing Flashcards

Evaluate box fill calculations, analyze raceway sizing factors, and apply NEC 2023 guidelines for compliance.

1
Q

Fill in the blank:

In Class II, Division 1 locations, where pendant mounted luminaires are suspended by rigid metal conduit (RMC) or intermediate metal conduit (IMC) and a means for flexibility is not provided, the conduit stems shall have a length of not more than _________.

A

12 in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

All hydromassage bathtub metal piping systems and all grounded metal parts in contact with the circulating water associated with the bathtub shall be bonded together using a solid copper bonding jumper not smaller than _________.

A

8 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

Where power-limited fire alarm (PLFA) circuit conductors pass through wall or floor, the conductors shall be protected by a metal raceway or nonmetallic conduit up to a height of at least _________ above the floor, unless other means of protection is provided.

A

7 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

Luminaires installed in exposed or concealed locations under metal-corrugated sheet roof decking shall be installed and supported so there is no less than _________ clearance from the lowest surface of the roof decking to the top of the luminaire where the sheet metal is not covered with 2 inches of concrete.

A

1½ in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

Transformers with ventilation openings shall be installed so the ventilating openings are not blocked by walls or other obstructions. The required clearances shall be _________.

A

clearly marked on the transformer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

Where a one-family or two-family dwelling unit has a three (3) car attached garage, the NEC® requires a minimum of _________ 125-volt, single-phase, 15- or 20-ampere receptacles to be installed in the garage.

A

three

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fill in the blank:

With respect to messenger-supported service-drop conductors and open overhead wiring operating at 0 to 750 volts to ground, the minimum vertical clearance that must be maintained from the base of a swimming pool diving board and the conductors is _________.

A

22½ feet

200 amperes (load)/.75 (temp. cor.) x .8 (adj. factor) .6 = 200 = 333 amperes

Size 400 kcmil conductors with an ampacity of 335 amperes
should be selected from Table 310.16.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Determine the required size 75 deg. C rated conductors to be used to supply a demand load of 200 amperes where provided with a 208Y/120-volt,3-phase 4-wire, electrical system. Consider all four (4) conductors to be current-carrying and the ambient temperature is 120 deg. F.

A

400 kcmil

6 AWG ungrounded conductors - 3 x 5.00 cu. in. = 15.00 cu. in.
6 AWG grounded conductors - 3 x 5.00 cu. in. = 15.00 cu. in.
8 AWG grounding conductor - 1 x 3.00 cu. in. = 3.00 cu. in.
12 AWG ungrounded conductors - 3 x 2.25 cu. in. = 6.75 cu. in.
12 AWG grounded conductors - 3 x 2.25 cu. in. = 6.75 cu. in.
12 AWG grounding conductor - 1 x -0- cu. in. = -0- cu. in.
TOTAL = 46.50 cu. in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

A metal junction box to be installed will contain the following conductors:

  • three - size 6 AWG ungrounded conductors
  • three - size 6 AWG grounded conductors
  • one size 8 AWG grounding conductor
  • three - size 12 AWG ungrounded conductors
  • three - size 12 AWG grounded conductors
  • one - size 12 AWG grounding conductor

The junction box is required to have a volume of at least _________.

A

46.50 cubic in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Fill in the blank:

In regard to permanently installed swimming pools, where necessary
to employ flexible connections to a pool pump motor, _________ shall be permitted as the wiring method(s).

I. UF cable
II. liquidtight flexible metal conduit (LFMC)

A

II only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

For legally required standby systems, the transfer switches shall be _________ and marked for emergency system or legally required standby used and approved by the authority having jurisdiction.

A

automatic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

In commercial vehicle repair garages, lamps and lamp holders for fixed lighting located over lanes through which vehicles are commonly driven, shall be located not less than _________ above the floor level, unless the luminaires are of the totally enclosed type.

A

12 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Determine the initial permitted operational setting of an adjustable inverse time circuit breaker used for branch-circuit, short-circuit and ground-fault protection of a 10 hp, 208-volt, 3-phase, squirrel cage, Design B, continuous-duty motor. Assume the motor will start at this setting without tripping the circuit breaker.

A

77.0 amperes

FLC of 10 hp motor = 30.8 amperes x 250% = 77 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fill in the blank:

Where transformer vaults are not protected with an automatic fire-suppression system, they shall be constructed of approved materials that have a minimum fire-resistance rating of _________.

A

3 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

At a truck plaza, every electrified truck parking space intended to provide an electrical supply for transport refrigerated units (TRUs), shall be equipped with a _________ receptacle outlet.

I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire
II. 60 ampere, 208-volt, 3-phase, 3-pole, 4-wire

A

either I or II

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the maximum distance allowed to support intermediate metal conduit (IMC) from a junction box where structural members do not readily permit fastening?

17
Q

Fill in the blank:

All hydromassage bathtub metal piping systems and all grounded metal parts in contact with the circulating water associated with the bathtub shall be bonded together using a solid copper bonding jumper not smaller than _________.

18
Q

Fill in the blank:

Where conductors of solar photovoltaic (PV) systems are exposed to ambient temperatures greater than 30°C (86°F), the ampacities of these conductors shall be corrected in accordance with Table _________ of the Code.

A

690.31(A)(3)(2)

19
Q

Determine the maximum standard size inverse time circuit breaker permitted for branch-circuit, short-circuit, and ground-fault protection for a 50 hp, ac motor, when given the following related information.

A

250 amperes

FLC of 50 hp motor = 65 amperes x 400% = 260 amperes

20
Q

In general, where is a grounded conductor not permitted to be connected on the load side of the point of grounding in a separately derived system, such as a transformer?

A
  • equipment grounding conductors
  • normally noncurrent-carrying metal parts of equipment
  • ground the earth
21
Q

Fill in the blank:

The life safety branch of the essential electrical system of a health care
facility shall provide power to _________.

I. automatic doors used for building egress
II. illumination of electrical equipment rooms

22
Q

Fill in the blank:

Intrinsically safe apparatus, associated apparatus, and other equipment shall be installed in accordance witht the _________.

A

control drawings

23
Q

Fill in the blank:

The grounded conductor of a 3-phase, 3-wire, delta service shall have an ampacity not less than _________.

A

that of the ungrounded conductors

24
Q

Fill in the blank:

Where a 150 kVA service transformer has a 480Y/277-volt, 3-phase primary and a 208Y/120-volt, 3-phase secondary, the full-load ampere rating on the primary side of the transformer is _________.

A

180 amperes

I = kVA x 1,000/E x 1.732 = 150 x 1,000/480 x 1.732 = 150,000/831.36 = 180.32 amperes

25
# Fill in the blank: Direct-buried cables or conductors located in a trench below 2 inch thick concrete or equivalent shall have a minimum cover requirement of \_\_\_\_\_\_\_\_\_.
18 in.