Fill in the blank:
For individual dwelling units with single-phase, 120/240-volt electrical systems of not over 400 amperes, the NEC® permits the service conductors to have an ampacity not less than _________ of the service ampere rating.
83%
Fill in the blank:
Where multiple driven ground rods, driven pipes or buried plate grounding electrodes are installed to meet the rules set forth by the NEC®, the electrodes shall not be spaced less than _________ apart.
6 feet
Fill in the blank:
When an ac general-use snap switch is used as a controller for a single-phase, 2 hp, 240-volt, ac motor, the switch is required to have an ampere rating of at least _________.
15 amperes
15 Ampere switch x 80% = 12 amperes
FLC of motor – 12 amperes x 125% = 15 amperes
Fill in the blank:
Conductors shall be permitted to be tapped to feeder conductors without overcurrent protection at the tap where the length of the tap conductors does not exceed 25 feet. However, the tap conductors are to have an ampacity of not less than _________ of the ampacity of the feeder conductors to which they are tapped.
one-third
Fill in the blank:
Luminaires are permitted to be supported by framing members of suspended ceilings when securely fastened to the ceiling framing members by mechanical means such as _________, _________, and _________.
screws, rivets, listed clips
Which of the following listed is not a requirement for an intersystem bonding termination?
a.Consist of not less than three (3) terminals.
b.Connected to the meter enclosure only with a minimum size 8 AWG conductor.
c.Terminals shall be listed for grounding and bonding.
d. Be accessible for connection and inspection.
b. Connected to the meter enclosure only with a minimum size 8 AWG conductor.
Fill in the blank:
Polyvinyl chloride conduit (PVC) larger than electrical trade size _________ shall not be used.
6 in.
Fill in the blank:
Nonmetallic sheathed cable, Type NM, is permitted to enter the top of surface-mounted cabinets and boxes through non flexible raceways of not less than 18 inches in length and not more than _________ in length, provided all the mandated conditions are met.
ten feet
Fill in the blank:
Flat cable assemblies (Type FC) shall be permitted for use as _________.
branch circuits not exceeding 30 amperes.
Fill in the blank:
As a general NEC® rule, where a building or structure is supplied with a 3-phase, 480Y/277-volt electrical system, each disconnecting means rated at least _________ or more shall be provided with ground-fault protection.
1,000 amperes
Fill in the blank:
Power-limited fire alarm (PLFA) circuit conductors shall be protected from physical damage up to _________ above the floor when passing through a floor or wall.
7 feet
Fill in the blank:
A fused disconnecting means for a 3-phase, 480-volt motor shall have an ampere rating of not less than _________ of the full-load current rating of the motor.
115%
Fill in the blank:
A minimum separation between heating elements of electric space-heating cables installed in ceilings and the edge of outlet boxes and junction boxes used for surface-mounted luminaires shall not be less than _________.
8 in.
Where multiple driven ground rod electrodes make up the entire grounding electrode system for a building or structure having a 480Y/277-volt, 1,200 ampere rated service, what is the minimum size wire-type copper conductor required to bond the ground rods together?
6 AWG
Fill in the blank:
Where conduits or other raceways enter floor-standing switchboards,panelboards or switchgear from the bottom, the conduits or raceways,including their end fittings, shall not rise more than _________ above the bottom of the enclosure.
3 in.
Which of the following statements about the emergency shut-off device provided for gasoline motor fuel dispensers is true?
a.It must simultaneously disconnect all grounded conductors of the circuit, and ungrounded conductors, if any, from the source of supply.
b.It must be a 2-pole circuit breaker.
c.It must be located at least 6 ft. above final grade.
d.All of these statements are true.
a. It must simultaneously disconnect all grounded conductors of the circuit, and ungrounded conductors, if any, from the source of supply.
In motion picture studios, television studios and similar locations, each receptacle of dc plugging boxes shall be rated not less than how many amperes?
30 amperes
Fill in the blank:
Where sizes 1/0 AWG through 4/0 AWG single conductor cables are installed in ladder type cable tray, the maximum allowable rung spacing for the ladder type cable tray shall be _________.
9 in.
Fill in the blank:
Type UF cable is not permitted to be used as _________.
service-entrance conductors
Fill in the blank:
When applying the general method of calculations for dwelling units, the permitted demand factor, in percent, on the feeder and service conductors for five (5) household clothes dryers is _________.
85%
Fill in the blank:
Where installed in commercial occupancies or industrial facilities, the minimum height (headroom) of working spaces about service equipment,switchboards, switchgear, panelboards, motor control centers and similar equipment of 1000-volts or less is _________ or the height of the equipment,whichever is greater.
78 in.
Fill in the blank:
As required by the NEC®, plate grounding electrodes shall be installed not less than _________ below the surface of the earth.
30 in.
Fill in the blank:
Size 14 AWG branch circuit tap conductors that serve individual outlets other than receptacles, are permitted to be tapped from 20-ampere rated branch circuit conductors when the _________.
size 14 AWG conductor length is not more than 18 in.
Fill in the blank:
The branch-circuit, short-circuit and ground-fault protection for a hermetic motor-compressor shall have a rating or setting not exceeding_________ of the motor-compressor rated-load current or branch-circuit selection, whichever is greater, where the protection specified is sufficient for the starting current of the motor and modifications are not necessary.
175%