125VDC and 240/120VAC Auxiliary Control Power System(EPK/EPF) Flashcards
(47 cards)
What is the purpose of the 125VDC and 240/120VAC Auxiliary Control Power System(EPK/EPF)?
The purpose of the 125VDC and 240/120VAC Auxiliary Control Power System is to supply control power to non-safety related equipment and the Operator Aid Computer.
What is the system designator for the 125VDC Auxiliary Control Power System?
EPK
What is the system designator for the 240/120VAC Auxiliary Control Power System?
EPF
What are the major system components of the 125VDC Auxiliary Control Power System?
- Two 125VDC Batteries
- Two Normal Battery Chargers
- One Standby Battery Charger
- Two 125VDC Distribution Centers
What are the designators for the 125VDC Batteries?
CBA
CBB
What are the designators for the Normal Battery Chargers?
CCA
CCB
What is the designator for the Standby Battery Charger?
CCS
What are the designators for the 125VDC Distribution Centers?
CDA
CDB
What is the purpose of the 125VDC Battery Chargers?
The Battery Chargers provide the normal power to the 125VDC Distribution Centers(CDA and CDB).
Where are the 125VDC Battery Chargers powered from?
The Normal Battery Chargers are powered from Blackout Load Centers:
- CCA is powered from LXI
- CCB is powered from LXH
The Standby Battery Chargers is powered from LXC
What are the local indications and controls on the Battery Chargers?
- Output Volts
- Output Amps
- FLOAT and EQUALIZE pushbuttons
What is the precaution associated with aligning a battery charger to a bus with no battery aligned?
A battery charger is not aligned to any bus unless a battery is connected. The battery chargers lack sufficient voltage stability to serve as the sole power source to a DC system.
What is the purpose of the 125VDC Batteries?
- The 125VDC Batteries provide backup power for the CDA and CDB Distribution Panels.
- They will automatically assume load on a loss of AC power or a loss of a battery charger.
- The batteries are normally maintained on a FLOAT charge.
What is the capacity of the 125VDC Batteries?
The Auxiliary Control Power Batteries are capable of carrying their associated loads for at least 2 hours.
Which Battery Charger is aligned for an Equalizing Charge?
The Standby Battery charger will be aligned to a battery requiring an Equalizing Charge.
When does “Cell Reversal” occur?
80-85% of normal battery voltage
Can “Cell Reversal” be corrected?
NO
What affect can “Cell Reversal” have on equipment?
- Damage to the remaining cells of a battery bank.
2. Damage to equipment being supplied by the battery.
How do we prevent “Cell Reversal”?
- Minimize drain on the battery
A. Removed non-vital loads from the DC bus.
B. Placing AC portions of these systems on alternate power supplies.
C. Consulting station management for recommended loads to remove from a DC bus. - Remove a battery from service when the battery’s voltage drops below 105VDC.
What are the typical loads off of the 125VDC Distribution Panels?
- 600V Non-Essential Load Center Control Power
- CM System Control Power
- Exciter Control Power
- FWPT Control Power
- Mulsifyre System
- AFWP Control Power
- D/G Control Panels
- D/G CO2 Fire Protection
- 4160V Blackout Switchgear
- 125VDC EMC Disconnect Switch
- Control Rod Drive Control Panel
- Static Inverters(KXIA and KXIB)
- Auctioneering Diode that feeds OAC power
Where is control power provided from if power from 125VDC Distribution is lost?
CDA normally feeds:
- Control Power for LXI(600V Blackout Load Center)
- 4160V Blackout Switchgear
- CAPT Power
If power is interrupted to any one of these loads, ALL of them will automatically be transferred to a center tap on the 250VDC Battery.
What action is required to restore the 125VDC loads back to CDA following a power swap?
When normal power is restored loads can be manually transferred back to CDA by pushing the RESET pushbutton on the Control Power Transfer Cabinet in the Blackout Switchgear Room.
What type of ground detection instrumentation/controls are located at each 125VDC Distribution Panel?
- Ground Voltmeter
- Ground Indication Lights
- Battery Voltage to Ground Volt Meter Selector Switch
- Battery Undervoltage Relay
- Undervoltage Relay Test Switch(I&E only)
- Battery Ground Detector Test Switch(I&E only)
Where are ground alarms received?
- Control Room
2. Operator Aid Computer