15 - IFSTA Chapter 15 Flashcards
Within the two basic categories of apparatus testing, driver operators are mostly involved with?
Performance
If NFPA 1901 is being used for manufacturer specifications, choose the three required tests prior to delivery of apparatus:
Pump certification, road, hydrostatic
The road test for apparatus requires a top speed of at least 50mph as well as:
Acceleration from start to 35mph within 25 seconds
And
Come to a full stop from 20 mph within 35 feet
-During the hydrostatic test, the pump and associated piping should be able to withstand:
500 psi / 10 mins
Performance testing covered under NFPA 1911, requires fire pumps to be tested at least once a year as well as:
Completion of major pump or powertrain repair
According to NFPA 1911, while undergoing performance testing using a hydrant or static water source, choose the answer that is NOT included
A static water source is the only acceptable source for testing
During hose testing a scribe mark should be made next to the coupling on the hose, what is the max acceptable distance the hose can pull away before the test must be stopped.
3/8 inch
Performance test service gauges must be calibrated how often:
Within 60 days of the testing
During service testing, safety measures should include all of the following EXCEPT:
Utilizing 4 persons or greater
After conducting an engine speed check, it is determined that the tested speed is 35 rpm lower than the rated speed when the apparatus was new, this indicates:
The variant is within normal limits
When conducting performance testing, which test do many fire departments conduct first:
Vacuum test
NFPA 1911 states fire pumps of 1250 gpm and 1500 gpm must achieve prime within which time frames:
30 sec / 45 sec
Pumpers with a tank capacity of greater than 500 gallons must flow at least 500 gpm, this is determined during the:
Tank-to-Pump Flow test
All of the following are problematic issues during service testing EXCEPT:
Lift higher than 15 feet
Foam Proportioning Equipment Testing is generally done by one of two methods
Testing the rate which foam concentrate is consumed in ratio to water flow
Or
Testing the foam-to-water concentration produced by the system
A refractometer is used in which aspect of testing:
Foam Solution Testing
An Engine Speed Check should be done:
Under no-load conditions
When testing the Discharge pressure gauge and flow meter during the operational tests, the Flowmeter cannot be more than ____ off of the pitot gauge.
10%
During the Internal Intake Pressure Relief Valve Test all of the following are true EXCEPT:
A second pumper is not required
When using a pitot gauge, if the gauge is too close to the nozzle a higher reading will result, what is the correct distance from the nozzle:
1/2 nozzle diameter
What are the two basic categories of testing grouped as?
Preservice and performance
What are the two specific tests that the manufacturer is required to perform in addition to the pump certification tests?
The road test and the hydrostatic test
The engine speed interlock test is part of which test?
Pump certification test
If the apparatus fails to perform to the requirements outlined in the bid specifications, what should take place?
It should be rejected by the purchaser