When asked to find conductor ampacities of two different wires in the same conduit, explain how to find their ampacities

A

Use tables 1-4 to find individual ampacities based on lowest temperature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What table do you use to find conductor ampacities in raceway or free air

A

1-4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What table to use for ambient temperatures above 30 degrees

A

5A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How do you use the ambient temperature multiplier?

A

You apply the multiplier to individual temperatures of insulation, NOT the lowest when given multiples.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What table do you find ampacities for neutral support cable?

A

Table 36A and 36B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What rule applies to neutral support cable allowable ampacities?

A

4-004 5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What rule applies to allowable ampacities for conductors sharing the same raceway?

A

4-004 14

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What rule applies to marked and unmarked equipment temperatures?

A

4-006

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Which rule will you find information about pull box or junction boxes?

A

12-3036

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is Table 22? What code rule is related?

A

Space for insulated conductors in boxes. Rule 12-3034

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is table 23 and what rule is related?

A

Number of insulated conductors in boxes. Rule 12-3034

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which section would you find information on installation of a TX?

A

Section 26, installation of electrical equipment.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What does section 2 outline?

A

Administrative

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where can you find marking of equipment?

A

2-100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What does code rule 2-128 Fire Spread state?

A

Electrical installations made so probability of fire spread is made minimum
Cable shall be properly closed or sealed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What does code rule 2-138 Insulation Integrity state?

A

All wiring shall be free from short circuits and grounds

17
Q

What rule is fire spread?

18
Q

What rule is insulation integrity?

19
Q

Rule 2-202 2) suitable barriers or covers shall be provided for bare live parts within ______ of non electrical components that may require servicing.

20
Q

Rule 2-308 1) working space of _____ shall be provided and maintained around electrical equipment that _______

A

1m, have renewable parts (fuses, breakers), disconnecting means, operating means, or require examination, operation, adjustment, or maintenance.

21
Q

Where can you find information about working space around equipment?

A

Section 2. 2-308, 2-310, 2-312, 2-314

22
Q

Where can you find enclosure types?

A

Section 2. 2-400. Table 65.

23
Q

Fuses provide ______ to protect ________, which table should you use to find the rating to protect the conductor

A

Overcurrent protection to protect conductors. Use table 13 to find rating or setting of overcurrent devices protecting conductors

24
Q

What minimum size disconnect switch is required on a capacitor circuit?

A

Rated not less than 135% of rated current of the capacitor. Rule 26-214

25
What conductor ampacity is used for a capacitor circuit branch or feeder circuits?
Not less than 135% of rated current.
26
How do you size tap conductors for a capacitor?
Find rated current (may be given), DO NOT adjust rated current by 135%, use tables 1-4 to find applicable wire size based on wire temp and current rating before 135% is applied, divide by 3 (rule 26-208 2 b), that amount is your minimum size required.
27
To what PF is a motor allowed to be corrected to when using a capacitor? What rule?
Not exceed no load to pf unity. 26-218 2 a
28
Where will you find information on branch circuits?
Section 26. 26-650
29
Which table do you find current flow in flexible cord
Table 12
30
Which rule applies to conductor derates?
4-004 Ampacity of wires and cables
31
Do you count neutrals when calculating conduit fill?
Yes
32
When you have ‘unmarked equipment’ where do you find temperature for it?
4-006 2
33
Where can I find information on working space
Section 2
34
The ampacity of conductors of different temperature ratings installed in the same raceway shall be determined by ________
The conductor having the lowest temperature rating
35
What is the temperature limitations for equipment rated under 100A?
60 degrees
36
What is the temperature rating for equipment rated more than 100A?
75 degrees
37
Consumer service conductors should be not less than ______
#8 Al, or #10 Cu