Philippine Electrical Code Flashcards
These are electrical systems of 600 volts or less. These are used within a facility to supply power to lightings, general purpose outlets and utilization equipment.
Utilization system
These are electrical systems of voltages over 600 volts. These are used in large industrial facilities to supply large motors and other related type equipment and apparatus
Distribution Systems
What is the identifier of a grounding conductor as stipulated in the PEC
A white or gray outer finish, or by three continuous white stripes along its entire length.
Banks and Office buildings have the highest minimum lighting load at ___________
39 VA/m^2
Storage spaces like warehouses have the lowest minimum lighting load by occupancy at __________
3 VA/m^2
Barbershops/Parlors, Dwelling Units, Schools and Stores have the second highest minimum lighting load by occupancy at _________
33 VA/m^2
This is the most common lighting load by occupancy. Spaces like clubs, courtrooms, hospitals, hotels, industrial buildings and restaurants are rated to have this minimum lighting load.
22 VA/m^2
Outlets for HEAVY DUTY LAMPHOLDERS shall be calculated at a minimum of _________.
600 VA
Outlets for SIGN AND OUTLINE LIGHTINGS shall be calculated at a minimum of _________ for each required branch circuit.
1200 VA
RECEPTACLE OUTLETS shall be calculated not less than _____________ for each required branch circuit.
180 VA
All 125V and/or 250V, single phase, 15 and 20A receptacles installed is locations such as Bathroom, Garage, Outdoors, Crawl Spaces, Unfinished Basement, Kitchens, Laundry, Utility and Wet bar sink and Boathouses shall have ___________ for personnel.
GFCI
Ground-Fault Circuit-Interrupter
Appliance receptacle outlets installed in a dwelling unit for specific appliances, such as laundry equipment shall be installed within ____________ of the intended location of the appliance.
1800 mm (1.8 m)
Receptacles shall be installed so that no point measured horizontally along the floor line in any wall space is more
than _________ from a receptacle outlet.
1800 mm (1.8 m)
Receptacle outlets shall be located above, but not more than _________ above, the countertop.
500 mm (0.5 m)
For an Overhead Service-Drop Conductors and Underground Service-Lateral Conductors, the conductor shall not be smaller than ____________ copper or ___________ aluminum or copper-clad aluminum.
8.00 mm^2 (3.2 mm dia.), 14 mm^2
Overhead Service-Drop Conductors shall have a vertical clearance of not less than __________ above the roof surface. The vertical clearance above the roof level shall be maintained for a distance of not less than 900 mm in all directions from the edge of the roof.
2400 mm (2.4 m)
The ampacity of the service entrance conductors shall be the sum of the noncontinuous loads plus _________ percent of continuous loads.
125
These are loads that are connected for a long period of time (3 hours or more) such as lighting, computer terminals, copy machines, HVAC equipment and other devices and equipment found in offices.
Continuous Load
Are loads that are energized for duration less than three hours such as the general purpose receptacles (convenience) outlets, residential lighting outlets and so on.
Non-continuous loads
PEC and NEC require that the rating of the over-current device must be AT LEAST ____ of the continuous load.
125%
This is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. This is also described as the current rating or current-carrying capacity, it is the RMS electric current which a device can continuously carry while remaining within its temperature rating.
Ampacity
14 AWG = _____ sq. mm
2.0
12 AWG = _____ sq. mm
3.5
10 AWG = _____ sq. mm
5.5