Engine Company Flashcards
Flashover is the ignition of combustibles in an area heated by _____ . The action may be one of sudden ignition in a particular location followed by rapid spread or one of a “flash” of the entire area. The later action is more likely to happen in an open area.
A. Radiation.
B. Convection.
C. Conduction and convection.
D. Convection, radiation or combination of both.
D. Convection, radiation or combination of both.
The word “coverage” as used here means of the assignment of companies to particular portions of the fire ground for size-up and to accomplish any or all of the objectives of a firefighting operation. Both front and rear (and both sides when possible) must be covered quickly in order to establish effective control of the fire. You respond to a mercantile occupancy and the main body of fire is in the rear of the store. This fire should be attacked:
A. Primarily from the front or unburied side of the building.
B. Primarily from the rear or fire area of the building.
C. Primarily from the outside of the building.
D. Primarily from the corners of the building.
A. Primarily from the front or unburied side of the building.
If initial attack lines are not gaining control of a fire, is probably that the streams are not reaching into the seat of the fire or that these hoselines are not delivering enough water to cool the area. If a 2 1/2 inch hose line with spray nozzle is used for the initial attack, the backup lines should be:
A. Master stream devices.
B. 2 inch hoseline with spray nozzle.
C. 2 1/2 inch hoseline with smoothbore tip.
D. 2 1/2 inch hoseline with spray nozzle.
C. 2 1/2 inch hoseline with smoothbore tip.
If initial attack lines are not gaining control of a fire, is probably that the streams are not reaching into the seat of the fire or that these hoselines are not delivering enough water to cool the area. Went two 1 3/4 inch hoselines are used for initial attack, the backup line should be a:
A. One 1 3/4 inch hose line. B. Two 1 2/3 hose lines. C. Three 1 3/4 inch hose lines. D. One 2 1/2 inch hose line. C.
D. One 2 1/2 inch hose line.
If initial attack lines are not gaining control of a fire, is probably that the streams are not reaching into the seat of the fire or that these hoselines are not delivering enough water to cool the area. When a fire is so serious that the heaviest hoselines must be used for the initial attack (2 1/2 inch hose with 1 1/8 inch and 1 1/4 inch tips), _____ must be available for backup.
A. Additional 2 1/2 inch hoselines.
B. Additional pumpers.
C. Master stream appliances.
D. Foam extinguishing agents.
C. Master stream appliances.
If backup lines are placed in service, the initial attack lines should be shut down. The latter have already proved to be ineffective against the fire; there is little that they can do in support of the heavier streams. After the backup lines have gained control of the fire and an advance have been made, the smaller lines can be used to perform:
A. Back up for the larger lines.
B. Extinguishment and overhaul operations.
C. Rescue operations.
D. An emergence exit path for disoriented firefighters.
B. Extinguishment and overhaul operations.
According to EOC: In addition to backup lines, a rapid intervention crew of at least _____ firefighters equipped with full PPE, SCBA, and necessary tools and equipment should be standing by ready to enter the building. This group consists of personnel who may be needed to respond immediately to assist in locating or removing a lost or trapped firefighter or to any incident involving a firefighter in distress.
A. 2.
B. 3.
C. 4.
D. 6.
C. 4. (According to ECO p.109)
NFPA 1901 requires a minimum of _____ of 1/2 inch, 1 3/4 inch, or 2 inch fire hose to be carried on pumper fire apparatus.
A. 400 feet.
B. 600 feet.
C. 800 feet.
D. 1,000 feet.
A. 400 feet.
NFPA 1901, Standard for Automotive Fire Apparatus states that an engine itself should be equipped the pump having a rated pumping capacity of no less than _____ and a water tank that carries at least 300 gallons of water.
A. 500 gallons per minute.
B. 750 gallons per minute.
C. 1,000 gallons per minute.
D. 1,250 gallons per minute.
B. 750 gallons per minute.
NFPA 1901, Standard for Automotive Fire Apparatus states that an engine itself should be equipped the pump having a rated pumping capacity of no less than 750 gallons per minute and a water tank that carries at least ____ of water.
A. 250 gallons.
B. 300 gallons.
C. 500 gallons.
D. 750 gallons.
B. 300 gallons.
Wherever possible, 1 1/2 or 1 3/4 inch hose line should be preconnected to pump outlets. However, preconnected hose lines of 1 1/2 or 1 3/4 inch should not exceed _____ in length because excessive friction losses in longer lays. If these hose lines need to be extended a further distance, they should be connected to larger diameter hose lines.
A. 150 feet.
B. 200 feet.
C. 250 feet.
D. 300 feet.
C. 250 feet.
NFPA 1901 requires a minimum of _____ 2 1/2 inch or larger firehose.
A. 400 feet.
B. 500 feet.
C. 800 feet.
D. 1,200 feet.
C. 800 feet.
The NFPA requires the following nozzles to be carried on pumper apparatus… the exception is:
A. One combination spray nozzle, 200 gallons per minute.
B. Two combination spray nozzles, 95 gallons per minute.
C. One combination spray nozzles, 35o gallons per minute.
D. One playpipe, with shutoff and 1 inch, 1 1/8 inch, and 1 1/4 inch tips.
C. One combination spray nozzles, 35o gallons per minute. (FALSE)
Solid stream nozzles are classified according to nozzle diameter. Nozzles with tips up to 1 1/8 inch or perhaps 1 1/4 inch are generally considered for use on handlines (those normally held in hands). A _____ tip is the breaking point for handlines and streams at 50 PSI versus 80 psi.
A. 1 1/8 inch.
B. 1 1/4 inch.
C. 1 1/2 inch.
D. 2 inch.
B. 1 1/4 inch.
The 1 1/8 inch nozzle used with 2 1/2 inch hose line produces the so-called standard fire department stream of _____ at about 50 PSI nozzle pressure.
A. 150 GPM.
B. 200 GPM.
C. 250 GPM.
D. 300 GPM.
C. 250 GPM.
The ____ nozzle used with 2 1/2 inch hose line produces the so-called standard fire department stream of 250 GPM at about 50 PSI nozzle pressure.
A. 1 inch.
B. 1 1/8 inch.
C. 1 1/4 inch.
D. 1 1/2 inch.
B. 1 1/8 inch.
The 1 1/8 inch nozzle used with ____ hose line produces the so-called standard fire department stream of 250 GPM at about 50 PSI nozzle pressure.
A. 1 1/2 inch.
B. 1 3/4 inch.
C. 2 inch.
D. 2 1/2 inch.
D. 2 1/2 inch.
The 1 1/8 inch nozzle used with 2 1/2 inch hose line produces the so-called standard fire department stream of 250 GPM at about _____ nozzle pressure.
A. 50 PSI.
B. 80 PSI.
C. 100 PSI.
D. 150 PSI.
A. 50 PSI.
Tips from ____ to ____ are usually used on master stream appliances, such as monitors, deluge sets, or deck guns.
A. 1 1/8 to 2 inches.
B. 1 1/4 to 2 inches.
C. 1 1/2 to 2 inches.
D. 1 3/4 to 2 1/2 inches.
B. 1 1/4 to 2 inches.
Spray nozzles are also called fog nozzles and produce varying degrees of Waterspray. They may have a fix spray angle or maybe adjusted from almost a straight stream to a very wide angle spray. Many spray nozzles have predetermined pattern settings, usually at straight stream, ____ , ____ , ____ degree spray angles. The designated flow from a spray nozzle is usually rated at 100 PSI nozzle pressure.
A. 20-, 30-, and 40-.
B. 25-, 50-, and 75-.
C. 30-, 60-, and 90-.
D. 35-, 65-, and 95-.
C. 30-, 60-, and 90-.
Spray nozzles are also called fog nozzles and produce varying degrees of Waterspray. They may have a fix spray angle or maybe adjusted from almost a straight stream to a very wide angle spray. Many spray nozzles have predetermined pattern settings, usually at straight stream, 30-, 60-, and 90- degree spray angles. The designated flow from a spray nozzle is usually rated at _____ nozzle pressure, although there are now low-pressure spray nozzles operate at lower pressures.
A. 50 PSI.
B. 80 PSI.
C. 100 PSI.
D. 105 PSI.
C. 100 PSI.
The master stream appliance is a portable unit that can be used either mounted or detached from the pumper. It is capable of immediate application of a heavy stream. NFPA 1901 recommended master stream appliance of _____ minimum.
A. 500 GPM.
B. 750 GPM.
C. 1,000 GPM.
D. 1,200 GPM.
C. 1,000 GPM.
NFPA 1901 requires a minimum of ____ of soft suction or ____ of hard suction hose.
A. 10 feet ; 20 feet.
B. 15 feet ; 20 feet.
C. 20 feet ; 30 feet.
D. 25 feet ; 35 feet.
B. 15 feet ; 20 feet.
A hard-suction hose is generally available in sizes from 2 1/2 to 6 inches. Pumpers will carry a minimum of _____ section of hard sleeves (hard suction).
A. 10 feet.
B. Two 10 foot sections.
C. 20 feet.
D. Two 20 foot sections.
B. Two 10 foot sections.