The air temperature during testing should be between 0 degrees Fahrenheit - _________. The water temperature should be between _______ - 90 degrees Fahrenheit.

A

110 degrees Fahrenheit; 35 degrees Fahrenheit
pg 497

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

To monitor the serviceability of the hose throughout the test, a mark should be scribed where the ______ meet.

A

hose and couplings
pg 497

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If the scribed mark moves more than ___ from the coupling, stop the test and replace the hose.

A

3/8in
pg 497

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

A flowmeter indicates flow in GPM within ___% of accuracy.

A

5
pg 499

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

A vacuum test evaluated the

A

priming device, pump, and intake hose for air leaks
pg 500

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

According to NFPA 1910, fire pumps of 1,250GPM capacity must achieve prime in __ seconds or less, and those rated at 1500GPM must be primed within __ seconds.

A

30; 45
pg 501

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The _______ test evaluates the overall operation of the engine and fie pump.

A

pumping
pg 502