1

Accessible toilets MUST be mounted at ___ to ___ AFF to top of toilet seat.

17", 19"

2

Two exit access doorways MUST be provided from any space where the Occupancy Load exceeds ___. Give Occupancy groups this applies to.

49 = Occupancy Groups A (Assembly), B (Business) and M (Mercantile); 29 = Occupancy Group S (Storage)

3

Audio/visual fire signal device mounting height

6'-8" to 7'-6" AFF

4

4 locations there MUST be a audio/visual fire signal device

restroom, hallway, lobby and general assembly area

5

ALL electrical receptacles MUST be ____ AFF.

18"

6

Clearnace of ____ deep MUST be provided in front of power panels.

36"

7

Door openings should have a ___" minimum clear space on the push side of the door

12

8

ALL acessible (barrier-free) upper cabinets or shelves located above a work surface MUST NOT exceed ____ AFF.

44"

9

Service (reception/transaction) counters over ____ in length MUST have an acessible height service counter, a minimum of ____ in length.

8'-0", 36"

10

Means of Egress minimum height clearance

7'-6"

11

MIMIMUM interior corridor width

44"

12

Accessible urinals MUST have an elongated rim at a maximum heihgt of ___ AFF.

17"

13

Fire extinguishers MUST be located no more than ____ from furthest occupant.

75 feet

14

What is the dimensions of the clear floorspace that must be provided in front of accessible lavatories, urinals, showers and bathtubs?

30" x 48"

15

Grab bars at toilets and showers to be mounted between ___ and ___ AFF.

33", 36"

16

All accessible (barrier-free countertops, sinks, service surfaces and horizontal work surfaces MUST NOT exceed ____ AFF with a ____ High clear knee space below.

34", 27"

17

ALL acessible (barrier-free) lower cabinets MUST have a ___ maximum depth and a ___ minimum toe-kick

6", 9"

18

Centerline of accesssible toilets MUST be ____ to ____ from side wall or partition.

16", 18"

19

Minimum # of fire extinguishers calculation

1 extinguisher per 3000 sq. ft.

20

Door assemblies in a 1-hour fire rated parition MUST have a minimum fire protection rating of...

20 minutes and be self-closing

21

Grab bar at rear of toilet to be ___ long.

36"

22

Common path of egress travel distance MUST NOT exceed ____ feet.

100

23

Dead end corridors MUST NOT exceed ____ in length.

20'-0"

24

Core drills MUST NOT be within ___ of any structural element.

18"

25

Emergency illumination shall be provided for a minimum of ____ hours in event of failure of normal lighting.

1.5

26

Minimum turning radius clearance at all changes of travel direction on any path of travel

60" radius

27

Doors opening from occupied spaces into the path of egress travel shall not project more than ___" into the required width.

7

28

Accessible showers MUST be a minim of ___ x ___.

30" x 60"

29

Three paritions that must be one hour fire rated

1. Demising partitions between tenant spaces

2. Paritions along public corridor

3. Demise an Assembly (with occupancy of 750 sq. ft. or greater)

30

Travel distance MUST NOT exceed ____ feet measured along path of travel.

250

31

Protruding objects minimum height along path of egress, including any corrior, aisle or passageway.

6'-8"

32

Exit access doorways MUST be placed at a distance that is equal or greater than one-_____ of the maximum overall diagnal dimension of the area being served, when it is or is not sprinkled?

half, NOT sprinkled; third, sprinkled

33

Door openings should have a ____" minimum clear space on the pullside of the door.

18

34

ALL accessible showers MUST have grab bars on ____ sides.

three

35

ALL acessible (barrier-free) wall-mounted controls MUST be located between ___ and ___ AFF for side reach.

9", 48"

36

Clearance around accessible toilets MUST be ____ along rear wall and _____ along side wall.

60", 56"

37

Maximum square inches for door or sidelight glazing in fire rated partition

240 sq. in.

38

ALL electrical receptacles located with in ___ of a water source MUST be ____.

36", GFI

39

All Objects located on a wall between ___" and ___" AFF MUST NOT protrude more than ___" into an egress path of travel.

27, 80, 4

40

Fire rating for storage rooms

1-hour rating if over 100 sq. ft.

41

Grab bar at long side of toilet MUST be ____ long.

42"

42

ALL acessible (barrier-free) wall-mounted controls MUST be located between ___ and ___ AFF for forward reach.

15", 44"

43

Accessible mirrors MUST be mounted with the edge of the reflective surface no higher than ____ AFF.

40"