Indirect Waste Flashcards

Understand the requirements and design of indirect waste systems. (25 cards)

1
Q

Fill in the blank:

Except for refrigerator coils and ice-making machines, the size of the indirect waste pipe in a food handling establishment shall be not smaller than ______.

A

1 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

The indirect waste pipe for ice making machines shall be not less than______.

A

3/4 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

True or False:

For walk-in coolers, floor drains shall be permitted to be connected to a separate drainage line discharging into an outside receptor.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

The developed length for an indirect waste pipe for a bar or fountain sink shall not exceed ______.

A

Five feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the maximum length for an indirect waste line from a sterilizer to the waste receptor?

A

fifteen feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

True or False:

The indirect waste receptor for a sterilizer is not required to be located in the same room as the sterilizer.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

True or False:

The trap for indirect waste pipes exceeding 5 feet, but less than 15 feet in length shall not be required to be vented.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fill in the blank:

The standpipe for a clothes washer shall not extend less than ______ inches above the trap weir.

A

18

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

Appliances such as stills and sterilizers shall be drained through a(n) ______.

A

air gap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

True or False:

A drinking fountain shall not be permitted to be installed with indirect wastes.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

Steam or hot water sumps, condensers or intercepting tanks that are constructed of concrete shall have walls and a bottom that are not less than ______ inches in thickness.

A

4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

Sumps and condensers for steam and hot water drainage shall contain a volume ______ the volume of water removed from the boiler.

A

Not less than twice

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fill in the blank:

Chemical or liquid industrial wastes that could damage the sanitary sewer system shall be ______ before discharge into the drainage system.

A

pretreated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

True or False:

Clear water wastes from water lifts or expansion tanks are required to discharge through an indirect waste.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum slope for an indirect condensate drainpipe serving an air-cooling coil or condensing appliance?

A

1%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the minimum drain line size for indirect waste condensate overflow?

17
Q

What is the minimum indirect waste pipe size for a drain receiving condensate from equipment having a capacity of 20 tons of refrigeration?

18
Q

True or False:

Air-conditioning condensate waste pipes are allowed to connect indirectly through an air break.

19
Q

True or False:

Condensate waste from air-conditioning coils are permitted to discharge by direct connection into a lavatory tailpiece.

20
Q

True or False:

When installing indirect waste piping, female plastic screwed fittings shall be used with male metal fittings and metal threads.

21
Q

True or False:

Plumbing fixtures or receptors that receive indirect waste are required to be readily accessible.

22
Q

True or False:

The trap for a clothes washer is permitted to be installed below the floor.

23
Q

True or False:

Copper or copper alloy tubes shall be permitted for use for chemical indirect waste disposal.

24
Q

True or False:

Condensate wastewater shall be permitted to drain over a public way.

25
What is the minimum indirect waste pipe size for a drain receiving condensate from equipment having a capacity of 100 tons of refrigeration?
1 1/2"