Indirect Waste Flashcards
Understand the requirements and design of indirect waste systems. (25 cards)
Fill in the blank:
Except for refrigerator coils and ice-making machines, the size of the indirect waste pipe in a food handling establishment shall be not smaller than ______.
1 inch
Fill in the blank:
The indirect waste pipe for ice making machines shall be not less than______.
3/4 inch
True or False:
For walk-in coolers, floor drains shall be permitted to be connected to a separate drainage line discharging into an outside receptor.
True
Fill in the blank:
The developed length for an indirect waste pipe for a bar or fountain sink shall not exceed ______.
Five feet
What is the maximum length for an indirect waste line from a sterilizer to the waste receptor?
fifteen feet
True or False:
The indirect waste receptor for a sterilizer is not required to be located in the same room as the sterilizer.
False
True or False:
The trap for indirect waste pipes exceeding 5 feet, but less than 15 feet in length shall not be required to be vented.
True
Fill in the blank:
The standpipe for a clothes washer shall not extend less than ______ inches above the trap weir.
18
Fill in the blank:
Appliances such as stills and sterilizers shall be drained through a(n) ______.
air gap
True or False:
A drinking fountain shall not be permitted to be installed with indirect wastes.
False
Fill in the blank:
Steam or hot water sumps, condensers or intercepting tanks that are constructed of concrete shall have walls and a bottom that are not less than ______ inches in thickness.
4
Fill in the blank:
Sumps and condensers for steam and hot water drainage shall contain a volume ______ the volume of water removed from the boiler.
Not less than twice
Fill in the blank:
Chemical or liquid industrial wastes that could damage the sanitary sewer system shall be ______ before discharge into the drainage system.
pretreated
True or False:
Clear water wastes from water lifts or expansion tanks are required to discharge through an indirect waste.
True
What is the minimum slope for an indirect condensate drainpipe serving an air-cooling coil or condensing appliance?
1%
What is the minimum drain line size for indirect waste condensate overflow?
3⁄4”
What is the minimum indirect waste pipe size for a drain receiving condensate from equipment having a capacity of 20 tons of refrigeration?
3⁄4“
True or False:
Air-conditioning condensate waste pipes are allowed to connect indirectly through an air break.
True
True or False:
Condensate waste from air-conditioning coils are permitted to discharge by direct connection into a lavatory tailpiece.
True
True or False:
When installing indirect waste piping, female plastic screwed fittings shall be used with male metal fittings and metal threads.
False
True or False:
Plumbing fixtures or receptors that receive indirect waste are required to be readily accessible.
True
True or False:
The trap for a clothes washer is permitted to be installed below the floor.
False
True or False:
Copper or copper alloy tubes shall be permitted for use for chemical indirect waste disposal.
False
True or False:
Condensate wastewater shall be permitted to drain over a public way.
False