Which is not considered a point of delivery for natural gas systems?
a. the vertical gas riser coming out of the ground
b. the outlet of the service meter assembly
c. the outlet of the service regulator
d. the service shut off valve where no meter is present
a. the vertical gas riser coming out of the ground
True or False:
Minor installation of additional gas piping to piping already connected to a gas meter does not need to be inspected.
True
True or False:
If the AHJ disconnects gas piping which is not up to code standards, no notification is required.
False
Which of the following information is useful but not required on a gas piping sketch or plan?
a. number of fittings
b. location of piping
c. size of branches
d. load demands
a. number of fittings
Fill in the blank:
If the capacity of a gas system is inadequate for additional appliances, the existing system shall be ______ as required.
enlarged
Fill in the blanks:
Gas piping systems shall be sized to provide a supply of gas to meet the ______ demand and at least supply the ______ supply pressure to each appliance.
maximum, minimum
What is the approximate gas input for a typical warm air furnace in a single-family dwelling?
100,000 BTU
What is the approximate gas input for a 50-gallon tank water heater?
50,000 BTU
True or False:
Pipe, fittings, valves or other materials once used for a gas piping system shall never be used again.
False
Fill in the blank:
Threaded metallic pipe used for gas piping systems that is 3/4” in size shall have approximately ______ threads cut into the pipe.
10
Fill in the blank:
Metallic threaded fittings in sizes larger than ______ inches shall not be used for gas piping systems.
4
Fill in the blank:
Gas pressure regulators shall be ______ for servicing.
accessible
Fill in the blank:
In normal conditions, underground gas piping systems shall be installed with a minimum of ______ inches of cover.
12
True or False:
If an underground gas pipe cannot be installed with at least 12 inches of cover, the pipe shall be placed in a conduit.
True
What is the maximum spacing between supports for 1/2” steel gas pipe?
6 feet
What is the maximum horizontal spacing between supports for 1 1/4” steel gas pipe?
10 feet
True or False:
Gas piping supports shall be installed so as to restrict the free expansion and contraction of the piping between anchors.
False
Where gas piping is to be concealed, which of the following gas piping connections is not approved?
a. elbows
b. tees
c. couplings
d. unions
d. unions
True or False:
Concealed gas piping shall be permitted to be located in hollow partition walls.
True
Fill in the blank:
The unthreaded portion of gas piping outlets shall extend not less than ______ through finished ceilings or indoor walls.
1” inch
True or False:
For gas piping other than CSST, the piping shall be considered to be electrically bonded when connected to an appliance that is connected to a grounding conductor of the circuit supplying the appliance.
True
True or False:
Gas piping shall be permitted for use as a grounding conductor.
False
What is the maximum length for a non-metallic gas hose connector being used indoors to connect a laboratory appliance?
6 feet
Fill in the blank:
A shut off valve to a gas appliance shall be located within ______ feet of the appliance it serves.
6