Sanitary Drainage Systems Flashcards
Learn about sanitary drainage systems and compliance requirements. (45 cards)
True or False:
Vitrified clay pipe is approved for use aboveground.
False
True or False:
Stainless steel drainage piping shall not be installed underground.
True
Fill in the blank:
Where stainless steel piping is used for drainage, it shall be kept not less than ______ inches above ground.
6
Cast Iron pipe is approved for use in which of the following drainage applications?
a. Underground DWV
b. Above Ground DWV
c. Building Sewer
d. All of the above
d. all of the above
Stainless steel 304 pipe is approved for use in which of the following applications?
a. Underground DWV
b. Above Ground DWV
c. Building Sewer
d. All of the above
b. Above Ground DWV
What is the minimum trap size for a bathtub?
1 1/2”
What is the minimum trap size for a domestic kitchen sink?
1 1/2”
Fill in the blank:
A private bathtub drain has a value of ______ Drainage Fixture Units (DFU).
2
Fill in the blank:
A private drinking fountain drain has a value of ______ Drainage Fixture Units (DFU).
0.5
Fill in the blank:
A private kitchen sink drain has a value of ______ Drainage Fixture Units (DFU).
2
Fill in the blank:
A public commercial food waste disposer drain has a value of ______ Drainage Fixture Units (DFU).
3
What is the minimum trap size for an indirect waste receptor that receives liquid waste from heavy demand commercial sinks or dishwashers?
2”
What is the maximum drainage fixture unit value for a 3” trap and trap arm?
6 DFU
What is the drainage fixture unit value for an intermittent flow of 8 GPM?
2 DFU
What is the maximum number of drainage fixture units for a 4” vertical drainage pipe?
256
What is the maximum vertical developed length in feet for a 3” horizontal drainage pipe?
212
What are the maximum drainage fixture units that can be served by a 1 1/2” vent pipe?
8
What is the maximum developed length for a 1 1/2” drainage vent pipe?
60 feet
What is the maximum developed length for a 2” drainage vent pipe?
120 feet
True or False:
A floor drain is required to be installed adjacent to a commercial sink.
True
Fill in the blank:
Cast-Iron caulked joints shall be packed with oakum and filled with molten lead to a depth of not less than ______ in one continuous pour.
1 inches
Which of the following is not an approved method for joining copper drainage pipes?
a. brazed joint
b. mechanical joint
c. soldered joint
d. caulked joint
d. caulked joint
True or False:
Transition solvent cement joint is permitted to be used between ABS and PVC pipe at the building drain and building sewer connection.
True
Which of the following bends are not listed as an approved fitting for creating a change of direction in drainage piping?
a. one-third bend
b. one-sixth bend
c. one-eighth bend
d. one-sixteenth bend
a. one-third bend