Ch.9 Flashcards
4 main types of sprinkler systems:
- Wet pipe systems
- Dry pipe systems
- Deluge systems
- Preaction systems
According to NFPA, about ____ % of fires in sprinkled buildings are either extinguished by sprinklers or held in check until FD.
96%
Valve that controls the flow of water from the domestic water supply system and/or on-site fire pumps:
Main control valve
The main control valve is an ____________
indicating valve
- Should always be chained or locked open
- Located under the sprinkler alarm valve.
Main control valave
Most common type of main water control valve:
Outside screw and yoke (OS&Y)
Outside Screw and Yoke Valve:
- stem is visibly outside of the valve, valve is open
- stem is not visible, valve is closed
- Valve has no visible stem, it is inside post
- has window with movable target with words OPEN and SHUT
- Operating handle is attached and secured on the side of the post
Post Indicator Valve (PIV)
The Post Indicator Valve has words ______ and _____
OPEN and SHUT
This valve protrudes horizontally from a structures wall
Wall post indicator valve (WPIV)
Stopcock Valves are for both _______ and ________
- system drainage
- alarm silencing
Globe Valves are used for ________ and _________
- system drainage
- test valves
- manually operated
- Non-indicating type
_______ and ______ ensure the water can flow in only one direction.
Check valve or clapper valve
_________ are used to drain the sprinkler system automatically once the pressure on the system has been relieved.
Automatic drain valve
___________ is used to simulate actuation of the sprinkler system to ensure it is working properly.
Alarm Test Valve or Inspector Test Valve
- Common in ALL sprinkler systems
- This drain piping and valve combination is used to drain the system to replace heads
- To conduct system repairs
- To test the system
Main Drain
The water flow alarm indicates water flow and is activated either ______ or ________
hydraulically or electronically
Water movement within the system drives the alarm water gong in a __________
hydraulic alarm
*Local alarm used to alert building personnel of passerby of water flow in the buildings system
When water movement presses against a diaphragm that activates a switch to operate the alarm
Electronic Alarm
*can be local or connected to a monitoring company
Every sprinkler system must have a water supply that is ________, _______, and ________
- Reliable
- Automatic
- Of adequate volume and pressure
Every sprinkler system must be able to provide a minimal residual pressure of ____ psi to the HIGHEST and FARTHEST sprinkler head.
15 psi
The water supply for sprinkler systems can be provided from the ________, _________, or _________
- Domestic water supply
- Gravity tanks
- pressure tanks
An indication that a fire pump is present is a __________, which looks like a wall hydrant with multiple 2 1/2” outlets that are used for testing the fire pump.
Test Heaader
The number of outlets on a Test Header is determined by _____________
Required flow for occupancy