FP Gaseous Flashcards

(43 cards)

1
Q

What 3 systems/areas does Halon support for suppression?

A

AEER, Records Management, Main Computer Room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the two AEER Halon Systems and how many bottles are associated with each?

A

Initial Discharge - 9 bottles; Extended Discharge - 5 bottles.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where are the AEER Halon Bottles Located?

A

U2 Trackway

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does the AEER Halon System Actuate?

A

Automatic - 2 smoke detectors
Manual Electronic - initiation button (must be held)
Manual Mechanical at bottles

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How do the manual initiation and abort switches function?

A

Two of each, must remove pin and hold switch in place. Pins can be inserted to hold. The switches are spring returns.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How do the cylinders/bottles initiate (what opens them)?

A

4 pilot valves - 2 on initial, 2 on extended.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

AEER Halon - What happens if you release the abort switch

A

If the abort switch is used, if released it does not reset timer. It starts a 10 second timer to release the Halon.
Operation of abort switch causes a trouble alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How do you reset any Halon initiation?

A

Resetting the XL-3 fire computer - locally or in MCR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How do you disable the AEER Halon System?

A

AEER Halon Solenoid Keylock Switch - located on north wall outside AEER - used during OOS or surveillances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How does Halon System Auto Activate?

A

Signal from AT LEAST 2 smoke detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How can you manually initiate Halon injection upon loss of control power?

A

Mechanically via lever at initials and valve at extendeds - each bank pilot bottles.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What interlock exists to contain Halon discharge in AEER?

A

Upon injection, ventilation dampers close

IF CONTROL SWITCHES ARE NOT IN PURGE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

For the Computer Room and Records Halon System: How many bottles are there?

A

2 each - 1 for initial, 1 for extended discharge.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the delay for each Halon System?

A

60 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

For the Computer Room and Records Halon System: Alternate initiation?

A

Manual Pull Station or Mechanical Pins on bottles.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What must be done to deactivate an initiated Halon discharge signal?

A

Hold the abort signal button until the system can be reset.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What happens to the halon system upon loss of 125vdc?

A

Nothing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What powers the Halon injection valves?

A

24VDC from XL3

19
Q

HALON TRM - How many initial and extended discharge cylinders are required to be operable for the AEER?

A

8 initial and 5 extended

20
Q

HALON TRM - For the Main Computere Room - How many halon cylinders must be operable?

21
Q

HALON TRM - When is the HALON TRM Applicable?

A

Whenever the projected equipment is required to be operable.

22
Q

HALON TRM - What actions are required if a Halon Subsystem is inoperable?

A

AEER - Dedicated fire watch with backup suppression equipment w/in 1 hour
Main Comp. room - Dedicated Roving Fire Watch w/in 1 hour
AND
restore or evaluate/write IR

23
Q

What is the purpose of the Fire Protection System?

A

Protect plant equipment and personnel from fire hazards

24
Q

What other purpose (other than protection) does the Cardox system provide?

A

Purges U2 and U3 main generators.

25
Where is the CO2 supplied from?
Cardox Tank - TB 517 44 line. Refilled from truck connection by nitrogen storage tanks.
26
What is the Cardox tank normally kept at (Temp/Pressure)?
0Deg. F, corresponding to 300psig | 7.5 ton tank
27
What are the start and stop sets for the CO2 compressor?
Start at 305psig, stop at 295psig. This cools the CO2
28
What are the primary flow paths for Cardox?
1) Each of the EDGs 2) Each Generator 3) Hose Reels 4) Alternate Supply to AEER * **EDGs and Generator on one header, Reels on second
29
What is the initiation signal for Cardox to EDG rooms?
Auto - Heat Detector Manual - Pull Station Manual - Lever Selector Valves
30
How do the Cardox Tank Master Pilot Valves Function?
1 for each header (EDG/Gen & Hose Reels) | Normally Energized closed by 125vdc, fail open on loss of 125vdc
31
How do the Cardox Selector Valves function?
Used to direct Cardox Header to the required area. Normally de-energized closed - fail closed on loss fo 125vdc. Energized to direct CO2 to required area.
32
How can the Cardox selector valves be activated?
Auto - Electrically by detection device Manually - push button by diesel room or exciter Manually - mechanically by lever in enclosed box.
33
How do the Cardox Hose Reels Actuate?
By removal of nozzle from holders, sends signal to open pilot valves. Light illuminates when power is available.
34
How does the Cardox system de-activate?
CO2 injected into different areas, which initiates a timer based on size of room and rate of discharge. After timer times out, selector valves close.
35
Cardox Hose Reel initiation sequence?
Nozzle removed from holder. Red light on holder extinguished CO2 discharge valve de-energizes and opens bleeder valves close pneumatically after time delay to purge air from piping.
36
What are the safety protection measures for the Cardox Tank?
Bleeder valve set to 341psig Relief Valve set to 357psig Rupture Disc
37
What provides power to the Cardox system and valves?
125vdc 2A-1, circuit 14
38
How does Cardox supply to AEER initiate?
MANUAL INITIATION from pushbutton (Main from 2A-1, Reserve from 3A-2, circuit 20; only one set of fuses which must be manually swapped) - 60 second delay, 3 minute timer starts initial CO2 discharge, 13 minute times starts extended discharge. * ***CAN BE STOPPED VIA PILOT VALVE LEVER RETURN TO NORMAL****
39
CARDOX TRM - What must be done with one or more CO2 system inoperable?
Establish hourly fire watch w/in 1 hour AND Restore w/in 14 days or write IR/evaluate
40
Cardox TRM - What is the minimum level and pressure for the Cardox Tank?
50% full, 250psig
41
Gaseous FP TRM - How many valves must be able to operate and be found in required position per subsystem to be operable?
ALL OF THEM
42
Halon TRM - What is the required weight and pressure (%) for each initial and extended discharge cylinder?
95% weight, 90% charge pressure
43
Where are the timers and relays for the DG and Exciter Cardox systems?
DG - 2253-53 Panel | Exciter - 2253 - 58 Panel