Systems Exam 2 - Pressurizer Pressure & Level Control Flashcards

(48 cards)

1
Q

Pressurizer Pressure and Level Control systems are designed to accommodate what transients without a reactor trip?

A

→Loading or unloading at a rate of 5% per minute with automatic rod control
→Instantaneous load changes of 10% with automatic rod control
→Step-load reductions of 50% with automatic rod control and steam dumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the 0% power Program PZR Level and T-ave?

What is the 100% power Program PZR Level and T-ave?

A

0%
→25% level,
→557°F no load T-ave

100%
→60% level
→585.4°F (589.2°F)

(Level controlled by average T-ave, not power)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the function of PZR handswitch PS-455G?

A

Selects what pressure channel feeds the PZR chart recorder on CB-05.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

PZR Handswitch PS-455F top channel feeds what?
PZR Handswitch PS-455F bottom channel feeds what?

A

→Top: PORV PCV-455A
→Bottom: PORV PCV-456

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the function of PZR Handswitch PS-455F?

A

3 position selector switch used to select which 2 channels will be used for pressure control.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

PZR Pressure Hi Alarm setpoint

A

2310 psig

(also spray full open)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

PK-455A feeds what?

A

→PCV-455A
→Pressurizer pressure Deviation High alarm
→Pressurizer pressure low, backup heaters on
→Backup heater control
→Variable heater control
→PK-455B (loop 1 spray)
→PK-455C (loop 4 spray)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

‘Pressurizer Pressure Deviation High’ alarm comes in at what pressure?

A

> 75 psig above set point
(2310 psig)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Pressurizer pressure low alarm and turning on backup heaters actuate at what pressure?

A

> 25 psig below setpoint
(2210 psig)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does PK-455B feed?
What does PK-455C feed?

A

→PK-455B: PZR Spray valve PCV-455B, loop 1
→PK-455C: PZR Spray valve PCV-455C, loop 4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At what pressure do PORVs open?

At what pressure do PORVs close?

A

Open: 2335 psig

Close: 2315 psig

(blocked from opening below 2185 psig)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How are the PORV accumulators sized?

A

Designed to allow cycling 100 times in a 10 minute period

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If a conflict occurs between Level Control and Pressure Control which takes priority?

A

Level control is dominant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

PORV rated flow

A

210,000 lbm/hr

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When do pressurizer heaters energize?

A

→Decreasing pressure (PK-455A output at ~42%)
→Pressurizer Level 5% above program

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How is LT-462 calibrated, and when should it be used?

A

→Cold calibrated: Low temperature conditions (70°F).
→Whenever RCS temperature is < 450°F.
→Note: cold cal always indicates lower than hot cal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What does LK-459 provide control for?

A

→PDP speed
→FCV-121 position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What is the PZR lower program level limit and what is it designed to prevent?

A

→Lower program level limit of 25%
→Prevents emptying PZR on Rx trip and from uncovering heaters on normal transient.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is the PZR upper program level limit and what is it designed to prevent?

A

→Upper program level limit of 60%
→Leave enough room for surges
→Prevents Rx trip on high level for transient
→Prevents water going out the safeties on a load reduction of 100%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What occurs if a PZR bottom level control channel fails low, with no operator action?

A

→LCV-460 Closes
→Orifice isolation valves close
→All heaters de-energize
→PDP Speed decreases or FCV-121 throttles closed as actual level increases
→Actual level will increase (very very slowly) until Rx Trip occurs on hi level.

21
Q

What occurs if a PZR top level control channel fails high, with no operator action?

A

→All heaters energize (insurge of > 5% above program)
→PDP Speed goes to min or -FCV-121 throttles closed
→Actual level decreases until 17% is reached which causes letdown to isolate and heaters to de-energize
→Actual level will increase (very very slowly) until Rx Trip occurs on hi level.

22
Q

What occurs if a PZR top level control channel fails low, with no operator action?

A

→LCV-459 Closes
→Orifice isolation valves close
→All heaters de-energize
→PDP Speed goes to Max or FCV-121 goes full open
→Actual level increase until Rx Trip occurs

23
Q

What occurs at 17% PZR level with a decreasing level?

A

→17% on the Primary Control Channel causes LCV-459 to close (letdown isolation)
→17% on the Secondary Control -Channel causes LCV-460 to close (letdown isolation)
→Orifice isolation valves close (either control channel)
→PZR Heaters de-energize (either channel)
→Low Level Alarm

24
Q

High Failure of PZR top pressure Channel 455 or 457

A

→Spray Valves go FULL OPEN
→Heaters go to FULL OFF
→PORV PCV-455A sees an actuation signal and lifts since actual plant pressure, as sensed by channel 458, is above the interlock setpoint of 2185 psig.
→Plant pressure lowers rapidly
→At 2185 psig, the interlock signal from channel 458 is removed to allow PCV-455A to close.
→Pressure continues to lower due to the open spray valves.
→An OT N-16 turbine runback occurs (could also provide Rx trip)
→The reactor trips on lead-lag compensated low pressure because channels 456, 457, and 458 are still available to provide the necessary 2 of 4 logic at 1880 psig for the reactor trip.
→Plant pressure continues to drop after the plant trip. At 1820 psig an SI occurs.

25
What occurs if a PZR bottom level control channel fails high with no operator action?
→Hi level alarm (70%) →1 of 3 coincidence on Rx trip on Hi-Hi Level (92%)
26
Which level transmitters are 'Post Accident Environmentally Qualified'?
LT-459/460/461
27
What is the function of LR-459?
Used to select which level channel inputs into the level recorder on CB-05
28
What is the function of LS-459D?
→Used to select which channels provide control functions. →Normal position is 459/ 460.
29
What is the function of LT-462 and LT-459F?
→provide level indication only →no control functions.
30
Per ABN-705 in response to a PZR PT failure...
PK-455A is taken to manual and then an alternate channel is selected if failed channel in control, this is to mitigate the possibility of a PORV opening due to the Proportional/Integral function of the controller
31
PZR Safety design
Designed for the maximum surge rate resulting from a complete loss of steam flow to the main turbine, w/o a reactor trip, automatic control response (rod control, condenser steam dumps, pressurizer PORVs, etc.) or operator action. Peak RCS pressure is limited to less than 110% of design pressure by the safeties during a design basis transient.
32
PORV and Block Valve Power Supplies
→PORVs: train related 125 VDC →Block Valve u8000A: uEB3-2 →Block valve u8000B: uEB4-2
33
Arming Interlocks
Interlock signals from PT-457 (for PCV-456) and PT-458 (for PCV-455A) are used to allow PORVs to open on hi pressure however if pressure drops below setpoint of 2185 psig then the signal is removed and the PORV is blocked from opening (or PORV is closed if open)
34
PORV Accumulator sizing
→sized for cycling 100 times in 10 mins →located CTMT 905' →alarm provided on MCB for <90 psig in Accumulator
35
Heater Control Group after trip
Control Group C H/S must be taken to ON to reclose supply breaker after trip
36
Backup Heaters After Trip
After trip, backup heater breakers will energize if demanded UNLESS they were ON before trip then they will need to be reset by taking H/S to OFF then to AUTO
37
PZR Heater Power Supplies
→A: uEB3 →B: uEB2 →C: uEB1 →D: uEB4 "CBAD" for uEB1, 2, 3, then 4
38
PZR Heatup and Cooldown Limits
→100° F per hour heatup →200° F per hour cooldown (minimizes fatigue stress in accordance with ASME requirements)
39
1 Hour or Less PZR TS
→3.4.10 Pressurizer Safety Valves - 15 minutes →3.4.11 Pressurizer Power Operated Relief Valves (PORVs) - 1 hour
40
Low Level in a Reference Leg of the PZR Level Detector channel can be identified by...
...comparing the level channel indications. If a reference leg leaks, its PZR level channel will read erroneously high.
41
If steam inside containment significantly raises ambient temperature, how might that affect PZR level indication?
The water in the reference leg could boil away, causing level indication to read erroneously high. Could potentially affect all channels at the same time.
42
What is the thumb rule for finding what the programmed level for the pressurizer should be?
U1: (Actual T-avg - 557) x 1.23 + 25% U2: (Actual T-avg - 557) x 1.09 + 25%
43
What is the thumb rule for determining demand on the master pressure controller?
→Demand signal is 50% at 2235 psig. →Every pound of pressure above or below 2235 changes demand by 0.31%.
44
What is the thumb rule for knowing demand vs what will happen in the pressurizer?
→If demand ↑, spray is at the top, so spray turns on. →If demand ↓, heaters are at the bottom, so heaters turn on.
45
What level does the Hi PZR Level Alarm come in?
70%
46
What level does the Hi PZR Level Rx Trip come in?
92%
47
What does the top PZR level control channel control?
→LK-459 (PDP speed and FCV-121) →heaters on - high level deviation →closes LCV-459 (17%) →heaters off (17%) →orifice valves closed (17%) →low level deviation alarm →low level alarm
48
What does the bottom PZR level control channel control?
→high level alarm →low level alarm →closes LCV-460 (17%) →heaters off (17%) →orifice valves closed (17%)