P-Signals & C-Signals Flashcards

(20 cards)

1
Q

P-4

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Reactor Trip (Protection Grade signal)
Setpoint: reactor trip breakers open
Coincidence: train associated trip breaker AND bypass breaker open or not connected

Notes / What does it do?
→Arms Steam Dump system to allow steam dump operation in the T-ave mode from Plant Trip Controller
→Activates Main Turbine trip
→Blocks auto re-actuation of SI after manually resetting SI
→Will generate a FWI signal IF T-avg is below Low T-ave setpoint of 564°F (does NOT trip MFPs)
→Seals in FWI signal due to SI or HI-HI S/G level (P-14)

Note: P-4 signals processed by SSPS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

P-6

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Source Range Reactor Trip Block Permissive
Setpoint: >10^-10 amps
Coincidence: 1/2 IR

Notes / What does it do?
→Allows manual block of SR Hi Flux trip (2/2 block switches)
→Block switches also de-energize SR Hi Volts
→When <5x10^-11 amps on 2/2 channels then: SR Hi volts re-energized, SR trip and Flux Doubling protection re-instated (aforementioned occurs automatically)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

P-7

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

At Power Permissive
Setpoint: none
Coincidence: P-10 or P-13 met
(2/4 Excore PR NIs >10% or 1/2 Turb Impulse Press >10%)

Notes / What does it do?
Following Rx trips re-instated with P-7 met:
→PZR Lo Pressure
→PZR Hi Level
→RCP Undervoltage
→RCP Underfrequency
→Low Flow in 2 RCS Loops
Above trips are blocked when P-7 no longer met

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

P-8

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

3 Loop Flow Permissive
Setpoint: >48%
Coincidence: 2/4 PR channels

Notes / What does it do?
→Allows for Rx trip when low flow condition is sensed on 2/3 channels on 1 RCS loop.
→Automatically blocked with 3/4 NIS channels <48%

“8 and 3 look almost alike”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

P-9

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Turbine Trip Permissive
Setpoint: >50%
Coincidence: 2/4 PR channels

Notes / What does it do?
→When met, generates Rx Trip if Turbine Trip occurs
→Automatically blocked when <50% on 3/4 PR channels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

P-10

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Nuclear At Power Permissive
Setpoint: >10%
Coincidence: 2/4 PR NI channels

Notes / What does it do?
When met it performs the following:
→Feeds P-7
→Automatically blocks SR Trip and de-energizes SR Hi Volts
→Allows blocking of IR Hi Flux Trip and C-1
→Allows blocking of PR Hi Flux Trip (Low setpoint)
→SR Hi Flux at Shutdown annunciator and CNTMT Evacuation alarm defeated

When 3/4 PR channels <10% the following are automatically re-instated:
→IR Trip
→C-1
→PR Trip (Low setpoint)
→Removes permissive to P-7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

P-11

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

PZR SI Block Permissive
Setpoint: <1960 psig
Coincidence: 2/3 protection channels (doesn’t use channel 4)

Notes / What does it do?
When met allows manual blocking of:
→Low PZR Pressure SI
→Low Steam Line Pressure SI
(once blocked the High Negative Rate Steam Line Pressure Steam Line Isolation is armed)

Once PZR Pressure is >1960 psig on 2/3 channels, then:
→Low PZR Pressure SI armed
→Low Steam line Pressure armed
→Negative Steam Line Pressure High Rate is blocked and sends an OPEN signal to SI Accumulator isolation valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

P-12

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Lo-Lo T-ave Permissive
Setpoint: ≤553 deg F
Coincidence: 2/4 channels

Notes / What does it do?
→When met automatically closes all steam dump valves
→The 3 cooldown steam dump valves may be opened by using bypass switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

P-13

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Turbine At Power Permissive
Setpoint: turbine power > 10% (PT-505/506)
Coincidence: 1/2 turbine impulse pressure channels

Notes / What does it do?
→Feeds P-7 permissive
→Automatically removes signal to P-7 when no longer met

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

P-14

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Steam Generator Hi-Hi Level (Protection)
Setpoint: U1 84%, U2 81.5%
Coincidence: 2/3 detectors on any 1 SG

Note: control channels don’t count for the 2/3 detectors and are considered inoperable.
→Normal: Channel 1 for SGs 1&4, Channel 2 for SGs 2&3
→Alternate: opposite of normal - Channel 1 for SGs 2&3, Channel 2 for SGs 1&4

Notes / What does it do?
→Trips Main Turbine
→Trips Main Feed Pumps
→Generates Main Feedwater Isolation signal

Note: does NOT directly trip Rx; don’t fall for that distractor on an exam.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

C-1

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Intermediate Range Rod Stop (prevent reaching IR & PR Hi flux trips)
Setpoint: IR amps ≈ 20% PR
Coincidence: 1/2 IR channels

Notes / What does it do?
→Stops outward rod motion in auto AND manual.
→Can be manually blocked when P-10 is met (2/2 switches)
→Automatically unblocked when P-10 no longer met

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

C-2

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Power Range Rod Stop (prevent reaching PR Hi Flux trip)
Setpoint: 103%
Coincidence: 1/4 PR channels

Notes / What does it do?
→Stops outward rod motion in auto AND manual
→Can be bypassed at the NIS cabinets
→Loss of any PC bus will cause a C-2 because of required coincidence

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

C-3

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

OTN-16 Rod Stop & Turbine Runback
Setpoint: 112 ± penalties (3% below OTN-16 Rx Trip setpoint)
Coincidence: 2/4 N-16 channels

Notes / What does it do?
→Stops outward rod motion in auto AND manual.
→Generates Turbine runback (runback works as follows, on for 1.5 sec @ 200%/min then off for 28.5 sec, cycle continues until C-3 clears)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

C-4

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

OPN-16 Rod Stop & Turbine Runback
Setpoint: 109% (3% below OPN-16 Rx Trip setpoint)
Coincidence: 2/4 N-16 channels

Notes / What does it do?
→Stops outward rod motion in auto AND manual.
→Generates Turbine runback (runback works as follows, on for 1.5 sec @ 200%/min then off for 28.5 sec, cycle continues until C-4 clears)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

C-5

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Low Power Interlock
Setpoint: ≤ 15% turbine power
Coincidence: 1/1 from PT-505 or 506

Notes / What does it do?
→Based on which turbine 1st stage pressure transmitter is selected to input to rod control system.
→Stops outward rod motion in auto w/ power <15%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

C-7

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Loss of Load
Setpoint: 10% with time constant of 120 sec
Coincidence: based on turbine power load reduction

Notes / What does it do?
→Allows dump valves to open in T-ave mode following load rejection. (Arms the Steam Dumps)
→Setpoint is variable based on rate of load rejection i.e. 5%/min will actuate C-7 in 1 min, 10% step change will actuate C-7 immediately
→Must be manually reset by taking the Steam Dump Mode Selector Switch to “Reset”

17
Q

C-9

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Condenser Interlock
Setpoint: >12.3” Hg vacuum (2/2; uPC2)
Coincidence: Condenser vacuum plus 2/4 Circ Water Pump breakers closed

Notes / What does it do?
→Allows steam dumps to open when C-9 is met

“C-9, condenser’s fine”

18
Q

C-11

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Control Bank D Rod Withdrawal Limit
Setpoint: 223 steps
Coincidence: N/A

Notes / What does it do?
→Stops outward rod motion in auto only

19
Q

C-16

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

Stop Turbine Loading (prevent excessive T-ave droop)
Setpoint: 553°F auctioneered low T-ave OR auctioneered low T-ave < T-ref by 20° F
Coincidence: N/A

Notes / What does it do?
→Stops turbine loading when met

20
Q

C-20

→What is it?
→Setpoint
→Coincidence
→Notes / What does it do?

A

AMSAC
Setpoint: >40% turbine power, no TD
Coincidence: 2/2 from PT-505/506

Notes / What does it do?
→Enables AMSAC actuation circuit
→505 or 506 <40% Blocks AMSAC after 260 sec. TDDO, this actually turns on PCIP light