Systems Exam 3 - Component Cooling Water Flashcards
(33 cards)
CCW Surge Tank Level HI-HI Alarm
Hi-Hi ≥ 88% (75% )
Refer to ABN-502 for leakage into CCW system.
CCW Surge Tank Level Lo Alarm
Lo ≤ 65% (46%)
→CAUTION: IF RMUW is used to makeup to the CCW Surge Tank while a blended flow to the VCT is in progress, THEN an inadvertent boration of the RCS could occur (bigger problem with U1 RMUW Pump than common)
→u-LV-4500 and u-LV-4501 should automatically close on a Surge Tank high level
→u-HS-4500-1, CCW Surge Tank RMUW Supply Valve must be manually closed; there is an alarm on MCB when open
CCW Surge Tk Normal Level Band?
Normal Makeup Supply?
Normal Level 65-77% (46-65%)
→Alarms to alert operator of level lowering & to initiate makeup
→Normal makeup is RMUW (lower dissolved O2) with Demin water as alternate
→Operator can open an individual compartment makeup valve or both, but must open 4500-1, RMUW MU VLV, to makeup to either compartment.
→Alarm to alert operator that 4500-1 is open
CCW Surge Tank Train A/B Empty Alarm
CCW Surge Tank Train A/B Empty ≤ 57% (33%)
AUTOMATIC ACTIONS:
→u-HV-4512, U1 Safeguards Loop Train A CCW Return Valve closes
→u-HV-4514, U1 Safeguards Loop Train A CCW Supply Valve closes
OR
→u-HV-4513, U1 Safeguards Loop Train B CCW Return Valve closes
→u-HV-4515, U1 Safeguards Loop Train B CCW Supply Valve closes
OPERATOR ACTIONS:
→Determine affected surge tank
→If surge tank level is <57% (33%), ensure affected safeguard loop is isolated
→Ensure both CCW pumps are in service
CCW Surge Tank Train A/B Level Lo-Lo Alarm
CCW Surge Tank Train A/B Level Lo-Lo Alarm ≤ 63% (39%)
→u-LV-4500-1, CCW Surge Tank RMUW Supply Valve opens
AND
→u-LV-4500, CCW Surge Tank Makeup Valve 4500 (Trn A) or 4501 (Trn B) opens
→makeup valve 4500 or 4501 will close at ≈77.5%
→u-LV-4500-1 must be manually closed
Refer to ABN-502 for leakage out of CCW system.
NOTE: Due to cut in surge tank partition plate, it will NOT be possible to determine affected CCW surge tank unless level decreases below approximately 60% level.
CCW Pump Auto Starts
→SIS
→BOS
→Low Pressure In Opposite Train CCW Supply Header: 64 psig (Blocked By AL)
→Auto Start Of Associated SSW Pump On Low Pressure In Alternate Train: 9.9 psig (Blocked By AL)
What signals isolate CCW Safeguards Loops?
CCW Safeguards Loop Isolations Close on:
→Containment Spray Actuation
→Associated Train Surge Tank Empty Alarm (57% U1 & 33% U2)
CCW Response to SI
→Pumps Start
→Recirc Valves Close
→RHR HXs CCW Out Valves throttle for 40% design flow (ABOUT 22% OPEN– blue light on H/S when throttled)
→CCW Isolated to Primary Sample Cooler
→Vent Chillers Isolated
CCW Response to Phase A
→CCW to/from Excess Letdown and RCDT HXs isolated
→CNTMT CCW Drain Tank flowpath isolated & pumps stop (because of valve limit switch)
CCW Response to CT Spray Actuation
→Train separation valves close
→CS HX CCW out valves (HV-4574 & 4575) fully open then throttle close to achieve 55% design flow,
→RHR HX CCW out valves (HV-4572 & 4573) fully open then throttle close to achieve 40% design flow (if not already in position)
“forty has an R in it, so RHR opens to 40% flow”
CCW Response to Phase B
→CNTMT isolation valves for CCW to/from RCPs close
→Non-Safeguards Loop isolation valves close
List Non-SFGDs CCW Loads
→Ventilation Chiller Condensers, 2 @ 2000 gpm
→Hydrogen Recombiner Heat Exchangers, 1 @ 10 gpm
→Waste Gas Compressor Seal Coolers, 1 @ 50 gpm
→Spent Fuel Pool Heat Exchangers, 1 @ 4000 gpm
→Letdown Heat Exchanger, 1000 gpm @ max temp
→Excess Letdown Heat Exchanger, 260 gpm
→Reactor Coolant Drain Tank Heat Exchanger, 225 gpm
→Seal Water Heat Exchanger, 375 gpm
→Reactor Coolant Pump Packages, 4 @ 535 gpm each
→PD Charging Pump Hydraulic Coupling Oil Cooler and Lube Oil Cooler, 81 gpm
→Process Sample Coolers, 60 gpm
→Instrument Air Packages, unit compressors #1 & #2 @ 43 gpm each (when operating)
→BTRS Letdown Chiller Package Condenser, 1 @ 415 gpm (not used)
→Boron Recycle Evaporator Package, 780 gpm
→Waste Evaporator Package, 780 gpm
→Floor Drain Evaporator Package, 780 gpm
List SFGDs CCW Loads
→Safety Chilled Water Chiller Condensers, 2 @ 300 gpm each
→Control Room A/C Unit Condensers, 2 per unit @ 250 gpm each
→RHR Heat Exchangers, 2 @ 7600 gpm each (design)
→Containment Spray Heat Exchangers, 2 @ 6080 gpm each (design)
→UPS A/C Unit Condensers, 1 @ 90 gpm per unit (normally in standby)
→Containment Spray Pump Seal Coolers, 4 @ 2 gpm each
→RHR Pump Seal Coolers, 2 @ 5 gpm each
→Post Accident Sampling System (P.A.S.S.) Cooler, 7 gpm (Train “A” Only)
What equipment will auto start when a CCW pump is started, if their control switches are in AUTO?
Any start of a CCW pump will automatically start the following equipment, if their control switches are in AUTO:
→Associated CCW pump room fan cooler
→Associated SSW pump
→Associated Safety Chilled Water recirc pump (which will then start associated safety chiller)
HV-4696 (RCP Thermal Barrier CCW Return IRC isolation valve) Interlock?
Closes on any RCP Hi Return flow of 64 gpm.
HV-4709 (RCP Thermal Barrier CCW Return ORC Isolation Valve) Interlock?
→closes on any RCP High Return Temp of 182.5° F.
→the affected RCP Isolation Valve will also close
CCW automatically isolates to what loads when they are placed in standby?
CCW flow from any of the following isolates when the chiller is placed in STBY:
→UPS
→CRAC
→Vent Chillers
→Safety Chillers
The CCW supply and return isolation valves to vent chillers isolate if…
flow is ≥ 3200 gpm for 30 secs.
U1 / U2 CCW Surge Tank Level Alarm Setpoints
Note:
→Lo-Lo causes the makeup valves to auto open
→Isolate associated safeguards loop, to protect safeguards equipment, train related; unfortunately this removes flow to non-safeguards equipment unless other train is operating and it does not have a lo-lo level also.
→Hi-Hi: 88% (75%)
→Hi: 77% (65%)
→Lo: 65% (46%)
→Lo-Lo: 63% (39%)
→Empty: 57% (33%)
Bottom of Surge Tank Partition Opening: 58% (37%)
When should non-essential flow be isolated and why?
EOP-0.0 Attachment 9 directs isolating non-essential loads if flow is >17,500 gpm to prevent runout
On a complete loss of CCW flow…
ABN-502 directs a reactor trip followed by a trip of all RCPs
CCW pump Amber mismatch light comes on when…
…the pump is taken to start and the pump does not start.
What are the CCW unit differences with regard to Instrument Air Compressors?
→Unit 1 IACs have one trim cooler cooled by CCW, and cooling is in series through IAC 1-02 first, followed by 1-01.
→trim cooler → IAC 1-02 → IAC 1-01
→Unit 2 IACs have cooling in parallel with one trim cooler each for IAC 2-01 and 2-02, cooled by CCW
(common IACs X-01 & X-02 cooled by TPCW)
Tech Spec 3.7.7 CCW Operability
Both trains of CCW must be operable in Modes 1-4
→one train inoperable: restore within 72 hrs (or RICT)
→can’t restore: mode 3 in 6 hrs, mode 5 in 36 hrs
Note: if any RHR train is made inoperable by CCW inoperability, must enter LCO 3.4.6