Systems Exam 3 - Excore Instrumentation, Ps & Cs Flashcards
(48 cards)
SR SHTDN FLUX HI alarm
→annunciates if flux increases to 300 cps or 5x background
→can be blocked
→this alarm also activates containment evacuation alarm
SR FLUX DBLG Alarm
→annunciates if SR flux doubles in 9 minutes
Source Range Detector
→BF3 Proportional Detector
→Rx Trip at 10^5 cps (can block above P-6)
→Pulse Height Discriminator: Eliminates pulses due to gamma ionization
Note: high voltage switching operations (or lightning) can spike SR detectors, causing trips.
Intermediate Range Detector
→Compensated Ion Chamber (gamma interactions in both chambers are cancelled out by adjusting voltage of gamma only detector (inner can)
→Rx Trip when detector current output = 25% Rx Power
→Overcompensated (high compensation voltage) causes detector output to decrease (read lower than actual)
→Undercompensated (low compensation voltage) causes detector output to increase (read higher than actual)
Note: if one channel is undercompensated, you may not get the unblock of SR trips; can manually unblock SR trips at CB in this case
Power Range Detector
→Uncompensated Ion Chamber
→amount of gammas compared to amount of neutrons is insignificant
→amount of background gammas is directly proportional to power level
Nuclear Engineering has estimated that the effect on PR NIS is approximately 0.8 % per degree at 100% power. The effect is decreased proportionally with power. For example at 50% power, the effect is halved or 0.4% per degree.
Tech Spec 3.3.1 & 3.9.3 Source Range:
→Source Range Instrumentation is required in Mode 2 (below P6) through Mode 6
→in Mode 6, only visual count rate indication is required in the Control Room
→in Mode 3-5 the T.S. only applies if the Rod Control System is capable of withdrawal and one or more rods not fully inserted.
Tech Spec 3.3.1 Intermediate Range:
The Intermediate Range Instrumentation is required in Mode 1 (below P-10) and Mode 2 (above P-6)
1 IR Channel inoperable, Mode 1 (<P-10) & 2 (>P-6):
→reduce THERMAL POWER to <P-6 in 24 hours, or
→increase power to >P-10 in 24 hours
→Mode 2 (<P-6) - Restore to operable prior to increasing power above the P-6 setpoint
Both IR channels inoperable Mode 1 (<P-10) & 2 (>P-6):
→suspend operations involving positive reactivity additions immediately, and
→reduce power to <P-6 in 2 hours
Tech Spec 3.3.1 Power Range:
2 PR Channels Inoperable, enter LCO 3.0.3
RX > 50% PWR UP PR DET FLUX DEV HI alarm:
any one detector deviating by > 5% of the average of all upper detectors
RX > 50% PWR LWR PR DET FLUX DEV HI alarm:
any one detector deviating by > 5% of the average of all lower detectors
Power Range Deviation alarm:
deviating by >5% of the average of all detectors
From 100% power, approximately how long after a trip do we take to come down to where Source Range instruments are energized?
→approx. 15-18 minutes
→10^-10 cps
→Startup Rate = -1/3 dpm
→approx. 6 decades
Where are the overlaps between SR, IR, and PR instruments?
→0% power on PR ≈ 10^-5 amps on IR
→3 to 5 x 10^4 cps on SR ≈ 10^-10 amps on IR
P-6
→What is it?
→Setpoint
→Coincidence
→source range reactor trip block permissive
→Setpoint: >10^-10 amps
→Coincidence: 1/2 IR
P-6
What does it do?
→Allows manual block of SR Hi Flux trip (2/2 block switches)
→Block switches also de-energize SR Hi Volts
→When <5x10-11 amps on 2/2 channels then: SR Hi volts re-energized, SR trip and Flux Doubling protection re-instated (aforementioned occurs automatically)
P-7
→What is it?
→Setpoint
→Coincidence
→at power permissive
→Setpoint: none
→Coincidence: P-10 or P-13 met
(2/4 Excore NI >10% or 1/2 Turb Impulse Press >10%)
P-7
What does it do?
Following Rx trips re-instated with P-7 met:
→PZR Lo Pressure
→PZR Hi Level
→RCP Undervoltage
→RCP Underfrequency
→Low Flow in 2 RCS Loops
Above trips are blocked when P-7 no longer met.
P-8
→What is it?
→Setpoint
→Coincidence
→3 loop flow permissive
→Setpoint: >48%
→Coincidence: 2/4 PR channels
“8 and 3 look almost alike”
P-8
What does it do?
→Allows for Rx trip when low flow condition is sensed on 2/3 channels on 1 RCS loop.
→Automatically blocked with 3/4 NIS channels < 48%.
P-9
→What is it?
→Setpoint
→Coincidence
→turbine trip permissive
→Setpoint: >50%
→Coincidence: 2/4 PR channels
P-9
What does it do?
→When met, generates Rx Trip if Turbine Trip occurs
→Automatically blocked when <50% on 3/4 PR channels.
P-10
→What is it?
→Setpoint
→Coincidence
→nuclear at power permissive
→Setpoint: >10%
→Coincidence: 2/4 PR channels
P-10
What does it do?
When met it performs the following:
→Feeds P-7
→Automatically blocks SR Trip and de-energizes SR Hi Volts
→Allows blocking of IR Trip and C-1
→Allows blocking of PR Trip (Low setpoint)
→SR Hi Flux at Shutdown annunciator and CNTMT Evacuation alarm defeated
When 3/4 PR channels <10% the following are automatically re-instated:
→IR Trip
→C-1
→PR Trip (Low setpoint)
→Removes permissive to P-7
C-1
→What is it?
→Setpoint
→Coincidence
→IR Rod Stop (prevent reaching IR & PR Hi flux trips)
→Setpoint: IR amps ≈ 20% PR
→Coincidence: 1/2 IR channels