Systems Exam 3 - Excore Instrumentation, Ps & Cs Flashcards

(48 cards)

1
Q

SR SHTDN FLUX HI alarm

A

→annunciates if flux increases to 300 cps or 5x background
→can be blocked
→this alarm also activates containment evacuation alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

SR FLUX DBLG Alarm

A

→annunciates if SR flux doubles in 9 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Source Range Detector

A

→BF3 Proportional Detector
→Rx Trip at 10^5 cps (can block above P-6)
→Pulse Height Discriminator: Eliminates pulses due to gamma ionization

Note: high voltage switching operations (or lightning) can spike SR detectors, causing trips.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Intermediate Range Detector

A

→Compensated Ion Chamber (gamma interactions in both chambers are cancelled out by adjusting voltage of gamma only detector (inner can)
→Rx Trip when detector current output = 25% Rx Power
Overcompensated (high compensation voltage) causes detector output to decrease (read lower than actual)
Undercompensated (low compensation voltage) causes detector output to increase (read higher than actual)

Note: if one channel is undercompensated, you may not get the unblock of SR trips; can manually unblock SR trips at CB in this case

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Power Range Detector

A

→Uncompensated Ion Chamber
→amount of gammas compared to amount of neutrons is insignificant
→amount of background gammas is directly proportional to power level

Nuclear Engineering has estimated that the effect on PR NIS is approximately 0.8 % per degree at 100% power. The effect is decreased proportionally with power. For example at 50% power, the effect is halved or 0.4% per degree.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Tech Spec 3.3.1 & 3.9.3 Source Range:

A

→Source Range Instrumentation is required in Mode 2 (below P6) through Mode 6
→in Mode 6, only visual count rate indication is required in the Control Room
→in Mode 3-5 the T.S. only applies if the Rod Control System is capable of withdrawal and one or more rods not fully inserted.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Tech Spec 3.3.1 Intermediate Range:

A

The Intermediate Range Instrumentation is required in Mode 1 (below P-10) and Mode 2 (above P-6)

1 IR Channel inoperable, Mode 1 (<P-10) & 2 (>P-6):
→reduce THERMAL POWER to <P-6 in 24 hours, or
→increase power to >P-10 in 24 hours
→Mode 2 (<P-6) - Restore to operable prior to increasing power above the P-6 setpoint

Both IR channels inoperable Mode 1 (<P-10) & 2 (>P-6):
→suspend operations involving positive reactivity additions immediately, and
→reduce power to <P-6 in 2 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Tech Spec 3.3.1 Power Range:

A

2 PR Channels Inoperable, enter LCO 3.0.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

RX > 50% PWR UP PR DET FLUX DEV HI alarm:

A

any one detector deviating by > 5% of the average of all upper detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

RX > 50% PWR LWR PR DET FLUX DEV HI alarm:

A

any one detector deviating by > 5% of the average of all lower detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Power Range Deviation alarm:

A

deviating by >5% of the average of all detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

From 100% power, approximately how long after a trip do we take to come down to where Source Range instruments are energized?

A

→approx. 15-18 minutes
→10^-10 cps
→Startup Rate = -1/3 dpm
→approx. 6 decades

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where are the overlaps between SR, IR, and PR instruments?

A

→0% power on PR ≈ 10^-5 amps on IR
→3 to 5 x 10^4 cps on SR ≈ 10^-10 amps on IR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

P-6

→What is it?
→Setpoint
→Coincidence

A

→source range reactor trip block permissive
→Setpoint: >10^-10 amps
→Coincidence: 1/2 IR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

P-6

What does it do?

A

→Allows manual block of SR Hi Flux trip (2/2 block switches)
→Block switches also de-energize SR Hi Volts
→When <5x10-11 amps on 2/2 channels then: SR Hi volts re-energized, SR trip and Flux Doubling protection re-instated (aforementioned occurs automatically)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

P-7

→What is it?
→Setpoint
→Coincidence

A

→at power permissive
→Setpoint: none
→Coincidence: P-10 or P-13 met
(2/4 Excore NI >10% or 1/2 Turb Impulse Press >10%)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

P-7

What does it do?

A

Following Rx trips re-instated with P-7 met:
→PZR Lo Pressure
→PZR Hi Level
→RCP Undervoltage
→RCP Underfrequency
→Low Flow in 2 RCS Loops
Above trips are blocked when P-7 no longer met.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

P-8

→What is it?
→Setpoint
→Coincidence

A

→3 loop flow permissive
→Setpoint: >48%
→Coincidence: 2/4 PR channels

“8 and 3 look almost alike”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

P-8

What does it do?

A

→Allows for Rx trip when low flow condition is sensed on 2/3 channels on 1 RCS loop.
→Automatically blocked with 3/4 NIS channels < 48%.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

P-9

→What is it?
→Setpoint
→Coincidence

A

→turbine trip permissive
→Setpoint: >50%
→Coincidence: 2/4 PR channels

21
Q

P-9

What does it do?

A

→When met, generates Rx Trip if Turbine Trip occurs
→Automatically blocked when <50% on 3/4 PR channels.

22
Q

P-10

→What is it?
→Setpoint
→Coincidence

A

→nuclear at power permissive
→Setpoint: >10%
→Coincidence: 2/4 PR channels

23
Q

P-10

What does it do?

A

When met it performs the following:
→Feeds P-7
→Automatically blocks SR Trip and de-energizes SR Hi Volts
→Allows blocking of IR Trip and C-1
→Allows blocking of PR Trip (Low setpoint)
→SR Hi Flux at Shutdown annunciator and CNTMT Evacuation alarm defeated

When 3/4 PR channels <10% the following are automatically re-instated:
→IR Trip
→C-1
→PR Trip (Low setpoint)
→Removes permissive to P-7

24
Q

C-1

→What is it?
→Setpoint
→Coincidence

A

→IR Rod Stop (prevent reaching IR & PR Hi flux trips)
→Setpoint: IR amps ≈ 20% PR
→Coincidence: 1/2 IR channels

25
C-1 What does it do?
→Stops outward rod motion in auto AND manual. →Can be manually blocked when P-10 is met (2/2 switches) →Automatically unblocked when P-10 no longer met.
26
C-2 →What is it? →Setpoint →Coincidence
→PR Rod Stop (prevent reaching PR hi flux trip) →Setpoint: 103% →Coincidence: 1/4 PR channels
27
C-2 What does it do?
→Stops outward rod motion in auto AND manual. →Can be bypassed at the NIS cabinets.
28
C-3 →What is it? →Setpoint →Coincidence
→OTN16 Rod Stop & Turbine Runback →Setpoint: 3% < OTN16 Rx Trip setpoint (115 ± penalties) →Coincidence: 2/4 N-16 channels
29
C-3 What does it do?
→Stops outward rod motion in auto AND manual. →Generates Turbine runback (runback works as follows, on for 1.5 sec @ 200%/min then off for 28.5 sec, cycle continues until C-3 clears).
30
C-4 →What is it? →Setpoint →Coincidence
→OPN16 Rod Stop & Turbine Runback →Setpoint: 3% < OPN16 Rx Trip setpoint (>109%) →Coincidence: 2/4 N-16 channels
31
C-4 What does it do?
→Stops outward rod motion in auto AND manual. →Generates Turbine runback (runback works as follows, on for 1.5 sec @ 200%/min then off for 28.5 sec, cycle continues until C-4 clears).
32
C-11 →What is it? →Setpoint →Coincidence
→Control Bank D Rod Withdrawal Limit →Setpoint: 223 steps →Coincidence: N/A
33
C-11 What does it do?
→Stops outward rod motion in auto only.
34
Tech Spec 3.2.4 Quadrant Power Tilt Ratio (QPTR)
→action required once ≥1.02 →applicable in Mode 1, >50% →For each 1% QPTR above 1.00, reduce power 3% →verify QPTR every 12 hrs →perform evaluation to allow continued operation →if completion time not met, reduce power to <50% Note: this one is tricky. Action isn't required until 1.02, but you must take the action based on the amount above 1.00
35
Tech Spec 3.2.3 Axial Flux Difference
→applicable in Mode 1 >50% →Spec not met when **two or more** PR NIs indicate out of spec →30 minutes to be <50% - no time for correction Background Info: →AFD = ΔI →inside the doghouse = acceptable; outside the doghouse = unacceptable "Half power, half an hour"
36
Source Range Hi Flux Rx Trip →What does it protect against? →Setpoint? →Coincidence?
Source Range Hi Flux Rx Trip →Startup Accident →≥10^5 cps →1/2 Source Range Detectors
37
Source Range Hi Flux Rx Trip Notes/What does it do?
Source Range Hi Flux Rx Trip →Can be manually blocked (2/2 switches) when P-6 is met. →Auto blocked when P-10 is met →When P-6 no longer met, trip is automatically reinstated. →Can be manually unblocked when P-10 no longer met
38
Intermediate Range Hi Flux Rx Trip →What does it protect against? →Setpoint? →Coincidence?
Intermediate Range Hi Flux Rx Trip →Startup Accident →IR current ≈ 25% PR →1/2 IR Detectors
39
Intermediate Range Hi Flux Rx Trip Notes/What does it do?
Intermediate Range Hi Flux Rx Trip →Can be blocked manually when P-10 is met. →When P-10 no longer met, trip is automatically reinstated.
40
Power Range Hi Flux "Low Setpoint" Rx Trip →What does it protect against? →Setpoint? →Coincidence?
Power Range Hi Flux "Low Setpoint" Rx Trip →overpower condition, uncontrolled RCCA bank withdrawal →≥25% →2/4 PR detectors (alarm on 1/4)
41
Power Range Hi Flux "Low Setpoint" Rx Trip Notes/What does it do?
Power Range Hi Flux "Low Setpoint" Rx Trip →Can be blocked manually when P-10 is met. →When P-10 no longer met, trip is automatically reinstated.
42
Power Range Hi Flux "Hi Setpoint" Rx Trip →What does it protect against? →Setpoint? →Coincidence?
Power Range Hi Flux "Hi Setpoint" Rx Trip →DNB →109% →2/4 PR Detectors (alarm on 1/4)
43
Power Range Hi Flux "Hi Setpoint" Rx Trip Notes/What does it do?
Power Range Hi Flux "Hi Setpoint" Rx Trip →Cannot be blocked.
44
Power Range Hi Positive Trip Rate Rx Trip →What does it protect against? →Setpoint? →Coincidence?
Power Range Hi Positive Trip Rate Rx Trip →rod ejection →+5% w/time constant of 2 seconds →2/4 Channels (alarm on 1/4) "Five-two, peeeeewww!!!"
45
Power Range Hi Positive Trip Rate Rx Trip Notes/What does it do?
Power Range Hi Positive Trip Rate Rx Trip →Must be manually reset at NIS cabinets →Setpoint is variable based on rate of power increase (i.e. 2.5 % in 1 second will actuate trip, 5% increase in 2 seconds will actuate trip, 10% increase actuates immediately)
46
Source Range and Level Trip Bypass Switch
Note: losing power has the same effect as pulling fuses.
47
Intermediate Range and Level Trip Bypass Switch
Note: losing power has the same effect as pulling fuses.
48
Gammametrics
→2 ranges: Low range (0.1 cps to 10^5 cps) and Wide range (10^-8 to 200% power) →fission chamber detector →designed to operate under accident conditions; PAM equipment →indicates on MCB and RSP