($$$$$) is essential for any building protected by fire suppression systems.
Pre incident planning
NFPA 13R
STANDARD FOR THE INSTILLATION OF SPRINKLER SYSTEMS IN RESIDENTIAL OCCUPANCIES UP TO AND INCLUDING FOUR STORIES IN HEIGHT
NFPA 13D
Standard for instillation of sprinkler systems in ONE OR TWO FAMILY DWELLINGS AND MANUFACTURED HOMES
($$$$$$) are not generally included in the NFPA 13r and 13d systems
Fire pumps
Commercial type automatic sprinkler system meetin the requirements of ($$$$$$) have an exceptional record of controlling fire.
NFPA 13
NFPA 13
Standard for sprinkler systems
NFPA 13e
Recommended practices for fire department operations in properties protected by sprinkler and standpipe systems
NFPA 13e fire department personnel should be knowledgable of and prepared to deal with the following three principal causes of unsatisfactory sprinkler performance.
NFPA 25
Standard for the inspection, testing, and maintenance of water based fire protection systems
When the system or part of the system is out of service, the system should be TAGGED as specified in NFPA 25
A tag shall be used to indicate that a system, or part thereof has been removed from service.
The tag shall be posted at each fire department connection and system control valve indicating which system, or part thereof, has been removed from service.
The authority having jurisdiction shall specify where the tag is to be placed
The system that is most often encountered is the ($$$$$$), which is very affective and one of the most reliable fire suppression systems.
Wet pipe sprinkler system
The ($$$$$$) is connected to a reliable water supply such as a water main or tank. The water is distributed and applied to the fire through sprinkler heads. Individual sprinkler heads are self contained detection/application devices.
Wet pipe sprinkler systems
($$$$$) are used in areas that might be subject to freezing temperatures.
Dry pipe sprinkler systems
The difference in a wet pipe and dry pipe systems is that the piping in a ($$$$$$) is filled with air that is under pressure instead of water.
Dry pipe
($$$$$) systems are filled with air that may or may not be under pressure. The one diffrence is that a sensing device , such as a smoke or heat detector, opens a valve, flooding the piping with water. If the sprinkler head is also fused , then water will come out of the sprinkler onto the fire.
Pre action sprinkler systems
In both systems, if the capacity exceeds 500 gal (1893 L) then ($$$$$) requires that the system be equipped with an accelerator or exhauster.
NFPA 13
($$$$$$) with this system, there is no water in the sprinkler piping, and all sprinkler heads are open. When activated a detector operated control valve (which is normally closed) opens, releasing water that fills the piping, and then discharges through the open sprinkler head into the protected area.
Deluge system
($$$$$$$) protect areas with high challenge fires, such as flammable liquids, conveyors moving combustible commodity s , and transformers.
Deluge systems
The most common operational error at properties protected by automatic sprinkler systems is ($$$$$)
Shutting down the system prematurely.
If a decision must be made between the use of hose lines and properly supplying the sprinkler system, it is usually best to supply the ($$$$$).
Sprinkler system
Several types of main valves are used to open and close sprinkler systems. The two most commonly used are ($$$$$$) and the ($$$$$$).
(OS&Y) outside stem and yoke.
(PIV) post indicator valve
A pumper connected to an adequate off site water supply should connect ($$$$) 2 1/2” or 3” hose line to the fire department connection.
Two
The water supply for this pumper (supplying the FDC) should be a ($$$$$$), ($$$$$$) or a ($$$$$).
Large diameter hose
Two 21 1/2” or 3” hose lines
Direct hydrant connection.
Some publications, including NFPA 13, recommend a pressure of ($$$$$$) at the FDC.
150 psi (1034 Kpa)