Block 2 exam questions Flashcards
(51 cards)
Best reading you can get with a meggar
OL
Higher Voltage affects current leakage in what way
Higher Leakage
What must be done if a control system for a registered boiler is going to be upgraded to a different system
The new control system must be approved by the provincial safety manager
What is a negative result of using too much excess air to lower the CO levels in the products of combusion
Reduced efficiency and increased NOx emissions
What can be done to the combustion process to lessen NOx production
Add insert gas into the burner
What burner component is commonly used to control CO
flame retention heads
How does refractory help reduce CO in flue gasses
It promotes higher temperature in the combustion chamber
How do vanes operate to control CO
They control the amount of air that enters the burner
CO and NOx vary in relation to each other in which way
Inversely
How is a ladder logic diagram organized
It is organised in a hierarchical structure
WHat is PLC ladder logic used for
To control the operation of industrial machinery
What is the purpose of a back pressure regulating valve in an oil supply line
To maintain a constant supply pressure to the fuel metering valves
What type of O2 sensor is used for burner applications such as boiler O2 trim systems or bismoass systems
Zirconia
What is an important consideration when selecting a gas flow meter
Accuracy
How is a seal achieved between the ICI appliances burner and the combustion chamber
A rope or fiber gasket
Which of the following documents are required when a program logic controller is used as a burner management system
A list of all error and alarm messages, their meaning and suggested operator actions
When replacing the refractory that is integral to the burner, how should the remaining gap between the burner and the castable refractory materials be filler
Using a ceramic fiber insulation
Why are flexible connectors recommended on all piping connecting to ICI burners
To reduce stress on the piping system
How is a burner supported in an ICI appliance
Most often the burner flange mounting system is enough to support the burner
When must product approval process be undertaken
Only for non-certified gas appliances
How does a direct-fired kiln operate
It releases hot gases directly inside the kiln
Vibration damping mounts are used to reduce the amplitude and frequency of vibrational waves for which of the following
large motors and industrial machines, air heaters and fans, heavy duty HVAC equipment
What are the most common types of atmosphere generators used in the heat treating industry
Exothermic and endothermic generators
Vibration isolation prevents which of the following
Excessive noise, energy transmission, damage to equipment