IP example test questions Flashcards

(58 cards)

1
Q

Portion of a refractory that is toxic

A

Silica

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

-How to bend 7/8 copper tubing

A

With a ratchet bender

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Type of uncoated copper that can be direct buried

A

K

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Back filling under (commercial depth) parking lot, calculate volume

A

65ft length x
12” wide x 2’ 130cu ft . plus add 100% for compaction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Proper way to make up a compression fitting

A

Nut, ferrel, push pipe to end of
fitting, plus 1-1/2 turns.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

-Joining fused pipe what do you do

A

Cut ream bevel.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

-Joining plastic pipe

A

, by electro fusion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

3/4 inch to 1/2 inch reducing coupling

A

concentric

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

-8 inch branch to 4 inch field take off

A

No larger than 50% of the supply piping, no
less then 3/4” min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

-Bolt pattern for tightening a 4-bolt flange

A

Cross

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What pipe joints can be concealed?

A

Welded threaded and brazed, or flange, or
grounded union

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

-2” steel pipe 115 ft how many hangers?

A

115 ÷ 10 = 11.5 round up and add 1 = 13

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

-Max pressure Drop of a 20 psi system,

A

10 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

-How large must a gas line be before it requires purging may also relate to a decommissioning question?

A

4” or larger.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

-Minimum pressure on a gauge for a 50 lb test

A

A. 50 B. 60 C. 75 D. 100
15% in excess of test pressure = 57.5 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Test dial face size

A

3” diameter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

After testing with air 6” pipe,

A

purge with nitrogen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

-Gas piping identification in a commercial building?

A

Every 20’ for steel.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

-3/4 inch to 1/2 inch reducing coupling

A

eccentric or concentric?

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

GVR for a corrugated chimney liner

A

20 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

5 Pa Calculate vent stack with 2 natural draft and 2 fan assisted appliances.

A

. 50’ b
vent multistory, what is the single wall common vent size?

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

CAT IV, how to vent

A

Determine exit, measure and assemble

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

-How to attach joints of commercial drier duct

A

foil tape

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

S cleat and drive cleat required for duct assembly. 12’ length in four 3’ sections,
how many drive and “S” cleats and what length?

A

12 x 18 transition to 18 x 24 on
one end, 8 of s cleats at 18”, 8 of drive cleats at 14”.

25
-Combustion damper,
, End switch interlocked with gas valve?
26
-Calculate grill size restrictions
10 of 1/16" width 8 of 1/16" Height ignore cross coverage.
27
-Size power burner air supply, 3 appliances
Remember 2015 code Fan-assisted and power-fan assisted are grouped with atmospheric appliance calculations
28
-3 phase motor, how to read amperage?
? Find motor leads with motor running, take readings on all 3.
29
-Sensors ground wire on both end or just one end.
1 in control panel
30
Know how to calculate volts amps,
voltage is amps x ohms Watts is volts x ohms
31
-Replacing a VFD on MUA,
, with same settings as previously programmed
32
Dual voltage motor amperage, calculate max. amperage from name plate
. Name plate states cont duty, SF 1.15
33
-RS-485 interface is not communicating what do you check? Combo of somewhat of the following
, Baud rate, address.
34
-minimum gauge for bonding conductor
#6 Copper / #4 Aluminum
35
- Install air damper inside combustion air hood for thermal fluid boiler, what do you install?
End switch and in series with safeties?
36
End switch and in series with safeties?
6"
37
-Stationary engine over 1.5 million
needs additional automatic safety shutoff valve piped in series and wired in parallel.
38
-50 million appliance what else do you need?
needs an extra SSOV
39
Max pressure on a low-pressure steam boiler?
15 psi
40
-Low fuel pressure switch setting
based on lowest low fire.
41
High fuel pressure switch setting
based on highest pressure for high fire.
42
-Liquid propane valve train, what additional requirement is needed for between valves?
Pressure relief valve
43
-What 2 objects can you vent together?
Regs. add vent area then times 2. (no relief)
44
-How to vent devices with line relief.
100% of largest + 50% of the sum of remaining)
45
-Fill propane tank
Fill by volume
46
What size propane tank at btu load of 500000 at -30 deg with 7 days run time?
Table I-9 / B-149.2
47
Copper fin boiler
failure from reduced water flow
48
Burner is warped from
too low of gas pressure.
49
Max. pressure for LP steam boiler
15 psi
50
Line heater gas line layout v
valve, strainer, vaporizer, vapour reg., valve
51
-1 of 2 hot water tanks not firing due to
damper end switch failure
52
Stationary engine brake horsepower to btu
4 cycle equals 10000 btu per bhp
53
20% excess air have 14% CO2
decrease fuel pressure?
54
-Calculation of NET stack temp
Measured flue gas temp. less combustion air (room) temp
55
How much CO2 produced by a 650000 btu/h boiler
650 cu ft of CO2
56
Amount of CO2 per cubic foot of CH4 is in the table at the back of the code
Table I.2 B-149.1 = 1 CF
57
When used in an incinerator a draft regulator shall be of what type
Single acting other installations double acting
58
Where an infrared heater is of the unvented type how should it be sized
Ventilation volume of at least 300cfm for each 100000 BTU input