IP example test questions Flashcards
(58 cards)
Portion of a refractory that is toxic
Silica
-How to bend 7/8 copper tubing
With a ratchet bender
Type of uncoated copper that can be direct buried
K
Back filling under (commercial depth) parking lot, calculate volume
65ft length x
12” wide x 2’ 130cu ft . plus add 100% for compaction
Proper way to make up a compression fitting
Nut, ferrel, push pipe to end of
fitting, plus 1-1/2 turns.
-Joining fused pipe what do you do
Cut ream bevel.
-Joining plastic pipe
, by electro fusion
3/4 inch to 1/2 inch reducing coupling
concentric
-8 inch branch to 4 inch field take off
No larger than 50% of the supply piping, no
less then 3/4” min
-Bolt pattern for tightening a 4-bolt flange
Cross
What pipe joints can be concealed?
Welded threaded and brazed, or flange, or
grounded union
-2” steel pipe 115 ft how many hangers?
115 ÷ 10 = 11.5 round up and add 1 = 13
-Max pressure Drop of a 20 psi system,
10 psi
-How large must a gas line be before it requires purging may also relate to a decommissioning question?
4” or larger.
-Minimum pressure on a gauge for a 50 lb test
A. 50 B. 60 C. 75 D. 100
15% in excess of test pressure = 57.5 psig
Test dial face size
3” diameter
After testing with air 6” pipe,
purge with nitrogen
-Gas piping identification in a commercial building?
Every 20’ for steel.
-3/4 inch to 1/2 inch reducing coupling
eccentric or concentric?
GVR for a corrugated chimney liner
20 percent
5 Pa Calculate vent stack with 2 natural draft and 2 fan assisted appliances.
. 50’ b
vent multistory, what is the single wall common vent size?
CAT IV, how to vent
Determine exit, measure and assemble
-How to attach joints of commercial drier duct
foil tape
S cleat and drive cleat required for duct assembly. 12’ length in four 3’ sections,
how many drive and “S” cleats and what length?
12 x 18 transition to 18 x 24 on
one end, 8 of s cleats at 18”, 8 of drive cleats at 14”.