ALL SAQ Block 3 Flashcards

(32 cards)

1
Q

What should be done if signs of heat stress or damage are detected in the diffusers?

A

Replace the diffusers immediately

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What should be done daily to maintain burners, according to Cleaver Brooks?

A

Check the start-up and operation of the burner pilot and main flames

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What should be checked monthly for cleanliness and proper condition, according to Cleaver Brooks?

A

Flame scanner

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What should be used to clean the surface contaminants from flame rods?

A

Scotch-Brite pad or steel wool

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What tool can be useful as a gap gauge for ignition electrodes?

A

Allen Key

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How often should the peepsite and sightports be checked for cracks in the lens?

A

Weekly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the purpose of optical detectors in burners?

A

To detect flame presence

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is flame impingement?

A

When the flame contacts other surfaces within the appliance

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What should be checked and replaced before closing up a boiler or remounting a burner?

A

Gaskets

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What should be checked annually for proper calibration, according to Cleaver Brooks?

A

Gauges and thermometers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Which components might need to be accessed by opening up the burner?

A

Ignition electrode, flame rod, oil nozzle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What can insufficient combustion air cause?

A

Overheating of the burner

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How can cracks in ceramic insulation around electrodes be identified?

A

By visual inspection and tapping with a screwdriver

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the maximum flame signal that can be achieved for Honeywell flame safeguards during recommissioning?

A

5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the standard electrode setting for burners, according to Cleaver Brooks?

A

1/8” to 3/16”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When should the oil in the air compressor be changed according to Cleaver Brooks?

A

After 500 hours of operation

17
Q

How often should the air-fuel ratio be checked according to Cleaver Brooks?

18
Q

What is the final step for a wide-open upstream monitor installation during setup?

A

Reduce the downstream working pilot setting to normal outlet pressure.

19
Q

How should the pilot adjusting screw be turned to increase the downstream pressure?

A

Turned into the spring case.

20
Q

What is the function of the main valve in the Fisher EZR regulator?

A

To handle maximum inlet pressures and pressure drops.

21
Q

What should be done for a wide-open downstream monitor installation during setup?

A

Adjust the downstream monitoring pilot to the desired monitor takeover pressure first.

22
Q

What should you ensure before turning on the gas to the regulator(s)?

A

The regulator(s) can handle the incoming pressures.

23
Q

What happens to the Type 112 restrictor at the “0” setting?

A

It has the smallest flow passage but never completely shuts off.

24
Q

In a Wide-Open Monitor System, what happens during normal operation?

A

The monitoring regulator remains wide open, while the working regulator manages the reduction to distribution pressure.

25
What should the monitor pressure setting be adjusted to in relation to the working regulator pressure setting?
At least two times the pilot proportional band pressure above the working regulator pressure setting.
26
Which position of the Type 112 restrictor provides the largest flow and is most stable?
8
27
What occurs during a wide-open Type EZR monitoring system lockup?
The working regulator on both an upstream monitor and a downstream monitor controls the system lockup.
28
What is the recommended restrictor setting for the initial startup of a regulator?
8
29
What should you always check and follow when setting up a pilot-operated regulator?
The manufacturer's specifications and procedures.
30
What does the restrictor setting control in a regulator?
Proportional band (droop) and speed of response.
31
What is the function of the Type 112 restrictor in a regulator?
To control the regulator's proportional band (droop) and speed of response.
32
What is the correct sequence for opening valves during regulator setup?