It is also important to check and make sure the regulator(s) that have been installed are able to handle what
the inlet pressure
increasing the restrictor setting gives you what
maximum stability (decreased opening speed, increased closing speed).
by decreasing the restrictor setting it gives you what
tighter control (increased opening speed, decreased closing speed);
(Maximum control)
A lower setting also provides what
narrower proportional band for better accuracy.
What position has the largest flow, is most stable and easiest for startup
8
What setting has the smallest (minimum) flow passage; at no point of rotation will the Type 112 restrictor be completely shut off.
0
After initial adjustment, the restrictor does not need to be adjusted for maintenance or startup.
True or false
True
In a Wide-Open Monitor System which regulator is the monitor regulator
Either
the monitoring regulator is set to what pressure
Slightly higher pressure
In the event of an open failure of the working regulator, the monitoring regulator does what
Takes over to ensure proper regulation
What can occur if the monitor regulator pressure setting is adjusted too closely to the working regulator pressure setting and/or if the monitor pilot supply regulator pressure setting is adjusted too closely to the monitor regulator pressure setting.
Low amplitude/high frequency monitor trim oscillations
The monitor pressure setting should be adjusted so it is at minimum is what
two times the pilot proportional band pressure above the working regulator pressure setting.
When adjustments are made what she be kept in mind to not exceed
These adjustments must be made such that other governing pressure limits, such as casing ratings, pilot maximum differential pressures or regulatory limits, are not exceeded.
How does a wide-open Type EZR monitoring system work
In a wide-open Type EZR monitoring system, system lockup will be that of the worker regulator on both an upstream monitor and a downstream monitor.
How does a series wide-open monitoring system work
series wide-open monitoring system, the diaphragm of the monitor regulator will change position with every load change. On an upstream monitor with the upstream pilot exhaust piped to downstream intermediate pressure, lockup will occur at the monitor’s setpoint and the diaphragm of the monitor regulator will be fully open during normal conditions.
For easy initial startup, set the restrictor to the what position
8
What is the first step for Setup and Adjustment
Make sure all block and vent valves are closed.
SLOWLY OPEN the valves in what order
(3)
Pilot supply and control line valve(s), if used
Inlet block valve
Outlet block valve
For a 161 Series pilot with Type 112 restrictor, turn the restrictor to position “?” or to the desired run position.
2
For wide-open downstream monitor how do you adjust the upstream and down stream pressures
Adjust the upstream working pilot until intermediate pressure is higher than the desired setpoint of the monitor pilot.
Adjust the downstream monitoring pilot to the desired monitoring takeover pressure.
Reduce the upstream working pilot to the normal outlet pressure setting.
For a wide-open upstream monitor how do you adjust the upstream and downstream pressure
Adjust the downstream working pilot to a setpoint higher than the setpoint of the monitor pilot.
Adjust the upstream monitoring pilot to the desired monitor takeover pressure.
Reduce the downstream working pilot setting to normal outlet pressure setting.