Systems Exam 4 Full Comprehensive Deck for Review Flashcards

(252 cards)

1
Q

How is pH controlled in the Main Steam System?

A

During power operation morpholine is used for pH control.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is shrink, and how does it affect SG level?

A

Shrink:
→caused by events that suddenly decrease steam flow (rapid load decrease, RCP trip, control valve closure)
→feedwater flow > steam flow
→SG riser level decreases due to decreasing void fraction
→downcomer flow temporarily decreases to equalize downcomer/riser pressures
→less moisture is being returned to downcomer due to reduced steam flow
→SG level goes down
→will continue until conditions stabilize and steam/feed flow are balanced

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is swell, and how does it affect SG level?

A

Swell:
→caused by events that suddenly increase steam flow (steam break, rapid load increase)
→steam flow > feedwater flow
→SG riser level increases due to increased void fraction
→more moisture is entrained in the steam exiting the tube bundle
→downcomer flow temporarily decreases to equalize downcomer/riser pressures
→more moisture is returned to the downcomer due to increased moisture entrainment
→SG level goes up
→will continue until conditions stabilize and steam/feed flow are balanced

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does recirculation ratio follow power level?

A

→higher recirculation ratio at low power
→lower recirculation ratio at high power

(recirculation flow / feedwater flow)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the design differential pressures for the SG tubes and tubesheet?

A

→primary to secondary ΔP = 1600 psig
→secondary to primary ΔP = 670 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the Primary and Secondary SG pressure boundary designs?

A

→Primary: 2485 psig and 650°F in RCS
→Secondary: 1285 psig and 600°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Steam Generator Flow Restrictor

A

→7 Venturi nozzles at SG outlet
→little flow restriction during normal operation (low ΔP, 2-3 psid)
→flow measurement for SGWLC
→limits steam flow in the event of a steam break; limits size of break to 1.388 sq ft
→protects against DNB/fuel integrity from cooldown rate/positive reactivity addition
→protects containment integrity by limiting rise of containment pressure and temperature for IRC steam break
→reduces thrust forces on main steam line
→limits stresses on SG internal components like tubesheet (RCS boundary)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

TDAFWP Steam Supplies

A

→tap off main steam lines 1 & 4 before MSIVs
→Fail open AOV’s
→upstream check valve prevents backflow from feeding steamline break
→u-HV-2452-1 Train A from SG 4 (uED1-1)
→u-HV-2452-2 Train B from SG 1 (uED2-1)
→valves have accumulators that allow for maintaining valve closed for 7 hrs, plus 30 mins to allow for closing manual isolation

Open on ‘BLA’:
→Blackout (OL)
→Lo-Lo SG Level on 2/4 SGs (2/4 detectors per SG)
→AMSAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

MSIV Auto Close Signals?
(a.k.a. Main Steam Isolation signals)

A

MSIV’s Auto Close on:
→CNTMT Hi-2 (2/3) at 6.2 psig
→Lo Main Steam Line Pressure of 605 psig (rate compensated, blockable when < P-11)
→Main Steam Line Negative Rate - 100 psig per sec with 50 sec Time Constant (enabled when Lo MSL Pressure blocked)
→Manual 1/2 handswitches
→Control transfer of MSIV from MCB to RSP

Note: MSL Isolation also closes the before MSIV drip pot isolation AOVs, and a manual closure of an MSIV will close its associated upstream drip pot valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

ARV Accumulators

A

→provide minimum capacity to modulate an ARV 15 times over 4 hours
→1 full stroke and 14 modulations each equal to 10% of the valve full open capacity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Atmospheric Relief Valves

A

→not credited for overpressure protection; used for cooldown purposes (during SGTR)
→prevent safeties from lifting
→valve normally set to open @ 1125 psig but may be varied depending upon plant conditions (sat pressure/130 = pot setting)
→takes about 15%-20% output on controller to open valve initially due to pilot plug, but once open can be throttled below this point
→two required for adequate cooling capacity for U1; one required for U2
→considered operable if they can be manually cycled from the CR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where can ARVs be operated from?

A

→can be operated from MCB or RSP
→control must be transferred to RSP via junction boxes and Amphenol connectors; junction boxes located in ARV Accumulator room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How can ARV’s be opened from Control Room? Is that a unit difference?

A

→U1 ARVs provided with OPEN/OFF keyed switch, used to fully open ARV using separate solenoid powered from opposite train
→switches required per analysis for D-76 generators to prevent overfill of generator during a tube rupture in conjunction with a loss of a single train of power
→analysis requires 2 SGs for max cooldown. (U1 D-76 SGs have smaller steam space volume therefore would fill up faster during the tube rupture)
→U2 ARV only has single solenoid supplied from 1 train

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Main Steam Line Rad Monitors:
→What type detectors and what are their ranges?
→EXPECTED Response for N-16 rad monitor with power changes?

A

2 types:
→Geiger-Mueller Tube on outside of pipe upstream of safeties
→N-16 scintillation detector just upstream of MSIVs

→GM Tube can detect 2.5 gpm primary to secondary tube leak; leak detection based upon 1% fuel failure
→N-16 detector can 1.0 gpd with a range of 1.0 to 150 gpd, Red Alarm at 15 gpd

→N-16s aren’t accurate below ≈40% power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

SG Safeties Setpoints

A

Setpoints:
→1185 psig
→1195 psig
→1205 psig
→1215 psig
→1235 psig

Other Info:
→ASME code overpressure protection for SGs
→for any one safety valve, the relieving capacity may not exceed a maximum design flow rate of 970,000 lbm/hr (≈25% SG rated steam flow)
→prevent steam line pressure from exceeding 110% of its design pressure of 1185

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What action must be taken if SG Safety acoustic sensor control logic loses power?

A

Each safety is provided with an acoustic sensor that sends a signal to the plant computer. If the control logic experiences a loss of power, computer interface must be reset via interface in CSR.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the minimum N2 pressure required to close the MSIV within the required stroke time?

A

minimum N2 pressure ≈ 1839 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

How are MSIVs locally operated?

A

→2 local manual overrides provided per MSIV
→may be operated in the clockwise direction to relieve hydraulic oil pressure back to the reservoir and allow N2 to close the MSIV
→wrenches for operation located outside MSIV room in safe shutdown cabinet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What are the mode restrictions and DP constraints for opening MSIVs and their bypasses?

A

Mode 1:
→all 4 bypasses locked closed

Modes 2, 3, or 4:
→only 1 MSIV bypass valve can be opened at a time to satisfy CNTMT Isolation requirements
→other three bypass valves locked closed and associated MSIVs are closed
→bypass valve is opened 1/4 turn at a time
→once DP is ≤15 psid, MSIV can be opened

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

→How does an MSIV work?
→What is its failure mode?

A

→air driven hydraulic pump to open
→N2 to close
→designed to stop flow within 5 sec
→on trip signal, hydraulic solenoids energized to open and dump fluid, and N2 closes valve
→loss of power to air solenoid for hydraulic pump fails open, causing the MSIV to open if hydraulic bleed solenoid valves have failed closed
→ensuring uD2 is aligned to battery charger prevents MSIVs from opening (operators are dispatched on an SI to align BCuD24 so that air solenoid remains closed)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Operation of Upstream (before) MSIV Drip Pot Isolation Valves

A

→fail closed AOVs
→close when MSIV given closed signal
→can be manually opened

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

In the case of a steam generator tube rupture, how are conditions in the penetration rooms improved?

A

Eductor action on exhaust piping removes steam from penetration room when steam is flowing through pipe.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

How should MSR’s be removed from service?

A

→main turbine operation time without MSRs in service should be minimized - limited to 300 hrs/yr
→without MSRs, increased erosion of the LP turbine blades will occur
→if MSRs to be shut down, BOTH right and left MSRs should be shut down simultaneously to maintain a balanced steam flow
→MSRs may be taken out of service if steam flow is adjusted so that the max generator output is 1130 MWE (97%)
→single MSR operation NOT allowed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

MSR Info

A

→steam flows from HP turbine exhaust to moisture separator chevron section
→shell drain collects removed moisture and drains to shell drain tank
→shell drain tank drains to Heater Drain Tank via level control system
→3 MSR safeties - lift at 181 psig, 184 psig, and 187 psig
→main turbine HP stop valves should not be opened during MSR pre-warming to prevent cross connecting main steam and aux steam

Note: when pre-warming the MSRs, ΔT between tubesheets of left and right MSRs shall not >25°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
MSR Reheat
→comes from inlet of HP turbine →4 passes with drains to 2 drain tanks at the end of 2nd and 4th passes →reheater drain tanks drain to FWH 1
26
Tech Spec 3.7.1 Main Steam Safety Valves
→5 safeties per SG required, Modes 1-3 →ensures secondary system pressure will be limited to within 110% of its design pressure of 1185 psig during the most severe anticipated system operational transient →max relieving capacity associated with turbine trip from 100% coincident with an assumed loss of condenser heat sink One or more SGs with 1 MSSV inoperable and MTC 0 or negative: → <68% power in 4 hrs More than one MSSV inoperable on one or more SG or one inoperable with positive MTC: →4 operable, reduce to ≤61% →3 operable, reduce to ≤43% →2 operable, reduce to ≤26%
27
Tech Spec 13.7.32 SG Pressure and Temperature Limits
→required at all times →both primary and secondary sides shall be >70°F →whenever pressure on either side >200 psig →reduce to <200 psig in 30 mins
28
Tech Spec 3.7.2 MSIVs
→required to have 4 in Modes 1-3 except when MSIVs are closed and deactivated →one out in Mode 1 - restore in 8 hrs or Mode 2 in 6 hrs →one out in Modes 2 & 3 - close in 8 hrs and verify closed every 7 days
29
Tech Spec 3.7.4 Atmospheric Relief Valves
→required to have 1 per steam line in Modes 1-3 →one out - restore in 7 days →two out - restore in 72 hrs →three out - restore in 24 hrs
30
TR 13.7.31 ARV Accumulators
→pressure ≥80 psig →if not met, ARV is inoperable →immediate entry into TS 3.7.4
31
Tech Spec 3.3.4 Remote Shutdown System
→required in Modes 1-3 →SG pressure and SG water level indications →one from each SG on RSP
32
During a LOOP, CST steam release capacity through ARVs is...
→62,150 lbm/hr →allows plant to maintain hot standby for 4 hrs, then cool plant from no load T-ave (557°F) to 350°F (RHR cut-in) in 5 hrs at 50°F/hr before exhausting CST inventory
33
How do adjust the lift setpoint for the ARVs?
saturation pressure/130 = number of turns
34
Condensate to Gland Steam Condenser Unit Difference?
→U1 - GS Condenser uses orifice to direct flow thru condenser →U2 - uses valve locked in place, air operator disabled, to throttle flow
35
Main Condenser Level / Vacuum Alarms
→Hi-Hi Hotwell Level 6' →Lo Hotwell Level 1.2' →0.2' Hotwell Lo-Lo Level trips condensate pumps (2/3) →Lo Condenser Vacuum 24" Hg (starts standby CEV Pump) →an SG tube leak will adversely affect vacuum due to an increase in non-condensable gases
36
Condensate Transfer Pump
→powered by uEB1-3 →200 gpm discharges upstream of CP system for initial system fill →Auto stops on Low Suction Pressure 7 psig →Load shed on SI
37
Main Condenser Interlocks
→Main Turbine Trip: 21" Hg if >900 rpm (2/3 on either condenser) →Steam Dump Actuation Block (C-9): 12.3" Hg (2/2) →Lo-Lo Level Condensate Pump Trip: 0.2' Hotwell Level →Main Feed Pump Trip: Low Vacuum in Aux Condensers (2/3); 2 sec TDPU → ≤17.5" Hg on 2 detectors OR → <21" Hg on one detector and 17.5" Hg on another detector
38
u-LV-2217A & B Hotwell Makeup Valves
→fail closed valves →Lo flow u-LV-2217A (4") opens 4-12 milliamps →Hi flow u-LV-2217B (8") opens 12-20 milliamps →Controller output = 4-12ma for 0-100% on 2217A, 12-20ma for 2217B 0-100% →maintain hotwell level at approx. 3 ft Note: Low flow valve u-LV-2217A immediately goes full open at <1.2' (separate solenoid drives valve full open), independent of M/A station setpoint.
39
u-LV-2211/12 Condensate (Hotwell) Reject Valve & Interlocks
→auto opens at Hi Level 5'6" to allow backflow through u-HV-2484 & 2485 →auto closes at Lo Level 4' →provided w/ seal in circuit (via open LS) to keep valve open after being manually opened; still auto closes on Lo Level. →LV-2211/12 blocked from opening (and will auto close) on any of the following: →PV-2286 is open (>15%) →both Condensate Pumps trip →either HV-2484 or HV-2485 is closed (auto close on AFW start or CST Hi Level) →Condenser Lo Level NPSH for pumps
40
Condensate Pumps: Motor Cooling & Seal Water
→motor cooled by TPCW →seal water provided via demin water (gravity feed from DWST)
41
Condensate Pumps: Trips and Interlocks
→trip on Lo-Lo Level in (0.2') hotwell (2/3 coincidence) →discharge valve and pump controlled via same H/S: taking H/S to start opens discharge valve; pump starts once valve is 10% open →if discharge valve doesn't reach 10% open, pump won't start →if pump doesn't start once discharge valve is 10% open, valve auto closes →overcurrent must be reset locally at breaker via keyswitch (normal for most of our non-safety pumps) Note: has been found that >80% RTP, MFPs will trip on Condensate Pump trip
42
PV-2286 Low Pressure Feedwater Heater Bypass Valve Interlocks
PV-2286 Interlocks: (ref: ABN-302) →auto opens on Lo MFP Suction Pressure (2/3 < 250 psig with generator output MWe > 15%) →will open (indirectly) if condensate pump trips Open Valve Causes: →LV-2211/12 Hotwell Reject Valve to close →FV-2239 Condensate Pump Recirculation Valve to close →alarm on ALB-8B "CNDS LP HTR BYP VLV OPEN" Initial Action if Valve Opens: →Verify Control Rods in Auto and MANUAL Runback to 900 MWe →2286 is sized to provide 96% of rated flow to MFPs
43
PV-2242 Condensate Polishing System Bypass Valve Interlocks
→fails open →auto opens on Hi system D/P: modulates open at 35 psid; full open at 40 psid →auto opens on Lo MFP Suction Pressure <280 psig (2/3) →auto opens on valve misalignment on IN-SERVICE CP Vessel (any IN-SERVICE vessel isolates at power)
44
FV-2239 Condensate Pump Recirc Valve Interlocks
→AOVs - fail open on loss of air; fail closed on loss of power →power supplied from uD3 →provided with Trip to Auto Enable or Disable toggle switch on M/A station →in Enable, valve can be manually controlled and auto open can occur →opens <6,000 gpm →closes >12,000 gpm →5 sec lockout TD until valve can be switched to manual after low flow condition →in Disable, only manual control can occur; valve will not auto open on a low flow Interlocks: →auto closes when 2286 opens (<250 psig MFP suction pressure 2/3 and >15% RTP) →<190 psig 2/3 both MFPs trip after 30 sec TD (MFP A) and 45 sec TD (MFP B) →<170 psig 2/3 with 4 sec TD, both MFPs trip
45
FV-2611A/B FV-2612A/B Feedwater Heater Isolation and Bypass Valves Interlocks
→auto close on Hi-Hi Level in associated heater train →2611A/B for 5A/6A FWH, 6A Drain Cooler →2612A/B for 5B/6B FWH, 6B Drain Cooler →single H/S for both valves in a train →bypass valve LV-2611/2612 opens on close signal to any of these valves →u-LV-2611A/B - uB3-1 →u-LV-2612A/B - uB4-1 →u-LV-2611/12 - uB3-1
46
SOP-303 Flow Limits for Condensate Pumps
SOP-303 Flow Limits for Condensate Pumps: →Do NOT operate two (2) Condensate Pumps until total flow is >8,000 gpm to prevent flow imbalance between the two pumps. →A minimum flow rate of 3,000 gpm per operating Condensate Pump SHALL be maintained. →A maximum flow rate of 14,700 gpm per operating Condensate Pump SHALL NOT be exceeded.
47
Tech Spec 3.7.6 CST Minimum Level (Modes 1-3)
→Minimum level of 53% (244,000 gallons) →applicable in Modes 1-3 → if level OOS - verify SSW backup within 4 hours AND restore within 7 days or, Mode 3 in 6 hrs & Mode 4 in 12 hours →Bases: Volume is sufficient to hold the unit in Mode 3 for 4 hrs followed by a C/D to RHR entry conditions at 50°F/hr for 5 hrs →To satisfy accident analysis assumptions, the CST must contain sufficient cooling water to remove decay heat following a reactor trip from 102% RTP, and then to cool down the RCS to RHR entry conditions, assuming a coincident loss of offsite power and the most adverse single active failure.
48
TS 3.7.18 Secondary Specific Activity (Modes 1-4)
→Specific activity of the secondary coolant shall be <0.10 μCi/gm Dose Equivalent I-131 (Modes 1-4) →if not met, Mode 3 in 6 hrs & Mode 5 in 36 hours Bases: →minimizes releases to the environment because of normal operation, anticipated operational occurrences and accidents →limit is lower than the activity value that might be expected from a 1 gpm tube leak of primary coolant at the limit of 1 μCi/gm
49
How does the plant respond if PV-2286 opens? (LP FWH Bypass Valve)
→efficiency goes down →RCS T-cold goes down →Steam Pressure goes down →Rx power goes up →SG Level goes up (a.k.a. swell)
50
Condensate Storage Tank
→taps for makeup/reject located 23'9" above bottom of tank →ensures 53% (or 244,000 gal) for Aux Feedwater following a Design Basis Accident →ensures capability to maintain hot standby for 4 hrs, then cool down RCS from 557°F to 350°F in 5 hrs
51
Turbine Exhaust Hood Spray Valve
→solenoid valve opens at 194°F with >1340 rpm →sprays condensate into the area to lower temps →happens mostly at low power with low steam flow available to cool area →condensate line taps off header before drain coolers →solenoid valve must be manually closed once temp restored, but will auto close when high temp clears if LP turbine inlet steam pressure ≥7 psia →separate MOV provided if solenoid valve insufficient to maintain temps →if exhaust temp can't be maintained <212°F, turbine is manually tripped
52
Long Path Recirc
→top of Condenser A →after LEFM →one Condensate Pump running
53
Full Flow Recirc
→bottom of Condenser →before LEFM →two Condensate Pumps running
54
What is the maximum flow through a Condensate Pump?
14,700 gpm
55
SG Normal Level Setpoints
→Unit 1: 67% →Unit 2: 64% →controlled by SGWLC →Level Dominant System
56
SG Lo-Lo Level Setpoints
→Unit 1: 38% →Unit 2: 35.4% →causes Rx Trip →causes AFW Auto Start (1/4 SGs for MDAFWPs, 2/4 SGs for TDAFWP)
57
SG Hi-Hi Level Setpoints
→Unit 1: 84% →Unit 2: 81.5% →P-14: →MFPs trip →turbine trips →Feedwater Isolation signal →2/3 detectors on any 1 SG (ch 1 not used SGs 1&4; ch 2 not used SGs 2&3)
58
Main Feed Pump Trips (10)
**→Manual** **→SI** from either train (also trips Main Turbine and causes FWI) **→Low Turbine Bearing Oil Pressure** - U1 ≤5.5 psig, U2 ≤4 psig; (2/3) 2 sec TDPU **→Low Pump Bearing Oil Pressure** - U1 ≤10psig, U2 ≤7 psig; (2/3) 2 sec TDPU **→Low Vacuum Aux Condensers** (2/3) ≤17.5" Hg on 2 detectors OR <21" Hg on one detector and 17.5" Hg on another detector; 2 sec TDPU **→Low MFP Suction Pressure ≤190 psig** (2/3); 30 sec TD MFP A, 45 sec TD MFP B; staggered trip **→Low MFP Suction Pressure ≤170 psig** (2/3); 4 sec TD (trips both simultaneously) **→Thrust Bearing Wear** ≥32 mils (2/3) **→Electrical Overspeed** ≥5600 rpm (2/3) **→Mechanical Overspeed** ≈5720 rpm (5663-5773 rpm, 5720 ± 57 rpm or ±1% tolerance) **→P-14 SG Hi-Hi Level** (2/3 on any one SG); also trips Main Turbine and causes FWI
59
How does loss of uD2 affect MFP's?
Loss of uD2 will prevent an electrical trip of the MFPs due to loss of the control system. Quickly shut down the MFPs if: →radial bearing metal temp >225°F →any other bearing metal temp >215°F →any oil temp >215°F →radial bearing vibration >5 mils
60
What produces a Feedwater Isolation Signal (FWI) signal?
→Hi-Hi S/G Water Level (P-14), resettable
61
Feedwater Isolation Signal (FWI) closes the following valves:
Feedwater Isolation Signal (FWI) closes the following valves: →u-FCV-510 through 540 Flow Control Valves →u-LV-2162 through 2165 Flow Control Bypass Valves →u-HV-2134 through 2137 Feedwater Isolation Valves →u-HV-2185 through 2188 Feedwater Isolation Bypass Valves →2-FV-2193 through 2196 Feedwater Pre-Heater Bypass Valves (U2 only) →2-FV-2181 through 2184 Feedwater Split Flow Bypass Valves (U2 only) Valves Close in Order To: →prevent excessive RCS cooldown →prevent uncontrolled SG filling →limit mass addition to CNTMT in event of DBA
62
What action must be taken if LEFM is lost?
→reduce power to <98.6% if lost →LEFM is a high accuracy flow measuring device which uses acoustic energy pulses to determine the final feedwater mass flow, and is used in calorimetric
63
Describe MFP Turning Gear Operation
→turning gear engaged via Instrument Air, driven by motor →starts when speed ≤2 rpm (via low speed switch on MFP turbine) AND adequate lube oil pressure
64
Feed Water Isolation Valves (HV-2134 through 2137) Minimum N2 Pressure / Power Supplies / Minimum Temp
Feed Water Isolation Valves (u-HV-2134/2135/2136/2137) →hydraulically opened, nitrogen to close, 2040 psig minimum pressure to be operable →pressure less than 2040 may result in exceeding surveillance stroke time →provided with train related solenoids to dump hydraulic pressure and close valves within 5 secs →hydraulic pumps powered from: uEB1-3 for SGs 1 and 3, uEB2-3 for SGs 2 and 4 → **maintain ≥90°F at all times per IPO-002, based on fracture toughness (TR 13.7.38)**
65
Feed Pump Recirc Valves FV-2289/2290 Auto Operation
→in Auto, valves throttle to maintain 5,000 gpm suction flow (MFP trip reset will open if in Auto) →driver card failure enables a separate solenoid which causes the valve to open at 4,275 gpm and close at 6,625 gpm →at normal power this would keep it closed →fails open on loss of air →fails closed on loss of signal →fails closed on MFP trip if both HP and LP steam supplies are shut
66
Feed Pump Discharge Valves HV-2109/2110 Interlocks
Feed Pump Discharge Valves HV-2109/2110 Interlocked with MFP status →auto opens on feed pump turbine start signals →auto close on a trip of the feed pump turbine OR closure of both HP and LP steam valves →trip signal overrides start signal →can auto open after trip signal reset
67
Water Hammer Interlocks
Water Hammer Interlocks are satisfied when: →no Feedwater Isolation signals present →FWIBV full open for 50 minutes →IRC feedwater temp >250°F for 10 minutes AND feedwater ΔT across cntmt penetration <10°F →total feedwater flow is >500,000 lbm/hr per SG →admin limits: SG pressure >605 psig and NR level >5%
68
Once Water Hammer Interlocks are met it causes the following:
Water Hammer Interlocks met causes the following: →allows opening FIV (will auto open if in Auto after Open) →once FIV open, FIBV/FPBV auto close and FSBV opens
69
Water Hammer Interlocks - removed by any of the following:
Water Hammer Interlocks are removed by any of the following: →Feedwater Isolation Signal is received →both FWIV and FWIBV go full closed →FSBV doesn't have open signal and total FW flow to SG is <475,000 lbm/hr →total FW flow to SG decreasing to <475,000 lbm/hr in conjunction with either IRC feedwater temp decreasing to <250°F OR ΔT across cntmt penetration increasing to >10°F
70
Split Flow Bypass Valves HV-2181 through 2184 Auto Close on:
→any MDAFWP auto start signal →Feedwater Isolation →Water Hammer Interlocks not met
71
Full Flow Flush Interlocks
To open FWP flush bypass valves (HV-2122 & 2124): →both FWPs tripped (both HP and LP steam valves closed) →both FWP suction valves (HV-2321 & 2323) closed.
72
TR 13.7.32 - SG Pressure/Temperature Limitations
TR 13.7.32 - SG Pressure/Temperature Limitations Establishes the temperature limits for primary and secondary coolants in the Steam Generators when the pressure of either coolant is greater than 200 psig. (requires the temperatures of the Primary and Secondary coolants to be > 70°F when the pressure of either coolant in the SG is > 200 psig)
73
Main Feedwater Pump Lube Oil Pumps
→2 AC oil pumps and 1 DC oil pump →1 AC pump normally in service →AC pumps are dual stage - 1st stage supplies 55 psig header; 2nd stage supplies 200 psig header
74
What happens on a loss of 2EC1 or 2EC2?
FWIVs close and FWPBVs open due to loss of water hammer interlocks.
75
Main Feedwater Pump Lube Oil Pump Auto Starts
→standby AC pump starts at 175 psig header pressure on the 200 psig header →DC pump auto starts at 25 psig bearing header pressure →only supplies 55 psig bearing header; bypasses lube oil coolers and filter
76
Failures: SG Level High
Failures: SG Level High LT-551 →Level error closes FCV which causes MFP speed to decrease →Feed flow decreases →flow error tries to offset level error, but doesn't →SG level decreases until Lo-Lo SG Level causes Rx trip
77
Failures: SG Level Low
Failures: SG Level Low LT-551 →Level error opens FCV which causes MFP speed to increase →Feed flow increases →flow error tries to offset level error, but doesn't →SG level increases until P-14 actuates
78
Failures: Feed Flow High
Failures: Feed Flow High FT-510 →steam flow / feed flow mismatch →flow error causes FCV to close →FCV D/P increases, causing MFP speed to decrease →Feed flow decreases →SG level decreases →as SG level decreases, level error increases until level error = flow error →SG level stabilizes at level < normal
79
Failures: Feed Flow Low
Failures: Feed Flow Low FT-510 →steam flow / feed flow mismatch →flow error causes FCV to open →FCV D/P decreases, causing MFP speed to increase →Feed flow increases →SG level increases →as SG level increases level error increases until P-14 actuates
80
Failures: Steam Flow High
Failures: Steam Flow High FT-512 →steam flow / feed flow mismatch →flow error causes FCV to open →FCV D/P decreases, causing MFP speed to increase →Feed flow increases →SG level increases →as SG level increases, level error increases until level error = flow error →SG level stabilizes at level above normal Note: if this occurs at lower power levels, then a Hi-Hi Level may occur, causing a Turbine/MFP trip.
81
Failures: Steam Flow Low
Failures: Steam Flow Low FT-512 →steam flow / feed flow mismatch →flow error causes FCV to close →FCV D/P increases, causing MFP speed to decrease →Feed flow decreases →SG Level decreases →as SG level decreases, level error increases →flow error drives to Lo-Lo setpoint, causing Rx trip
82
Failures: Feed Header High Pressure
Failures: Feed Header High Pressure PT-508 →MFPs speed decreases →Feed flow decreases →SG level decreases →Level error opens FCV fully →Feed flow continues decreasing →SG Level decreases until Lo-Lo level causes Rx trip
83
Failures: Feed Header Pressure Low
Failures: Feed Header Pressure Low PT-508 →MFP feed increases →Feed flow increases →SG level increases →Level error causes FCV to close →eventually, FCV closes enough that feed flow = steam flow →SG level stabilizes a few percent above normal
84
Failures: Steam Pressure High
Failures: Steam Pressure High PT-514 →steam flow / feed flow mismatch →flow error causes FCV to open →FCV D/P decreases, causing MFP speed to increase →Feed flow increases →SG Level increases →as SG level increases, level error increases, thereby offsetting flow error until steam flow = feed flow
85
Failures: Steam Pressure Low
Failures: Steam Pressure Low PT-514 →steam flow / feed flow mismatch →flow error causes FCV to close →FCV D/P increases, causing MFP speed to decrease →Feed flow decreases →SG Level decreases →as SG level decreases, level error increases →flow error drives to Lo-Lo setpoint, causing Rx trip
86
Loss of uPC1/uPC2 effect on SGWLC?
→steam pressure channel fails low causing program D/P to lower →MFP speed decreases to match actual D/P to program D/P →FCVs open to increase flow →steam pressure channel failing low also causes steam flow channel to fail low due to loss of density compensation, causes flow error →flow error wants FCV to close →level channels then fail low, causing level error →flow error and level error are competing effects →system is level dominant →FCV slowly opens to restore level →For uPC1 SGs 1 & 4 affected →For uPC2 SGs 2 & 3 affected
87
Loss of uPC3 effect on SGWLC?
No Impact
88
Loss of uPC4 effect on SGWLC?
SG Alarms for channel IV will annunciate and then clear. →alarms come in because of channel IV failure →alarms clear due to loss of multiplexer
89
Level Deviation Alarm
Level Deviation Alarm: actual level ± 5% from program level
90
How does selection of SG Level input to SGWLC affect P-14 and Tech Specs?
→2/3 logic used for P-14 →Tech Specs require 3 operable channels for P-14. →only channels that don't input into SGWLC can be used for P-14 →the level channel normally used for control does not input into P-14; based on the assumption that the controlling channel will fail, and will likely fail low →SGs 1 & 4 use channel 1 for control, so channels 2, 3, & 4 are used for P-14 →SGs 2 & 3 use channel 2 for control, so channels 1, 3, & 4 are used for P-14 Note: when one of the 3 operable P-14 channels is used as a controlling channel, then the P-14 bistable for that channel shall be placed in a tripped condition within 72 hrs (TS 3.3.2)
91
How is Program ΔP derived for SGWLC?
Program ΔP is fed via summing circuit that sums steam flow from all 4 generators to equate to a given power level.
92
How is total steam flow used to determine proper ΔP to maintain across Flow Control Valve?
→Program ΔP is determined using total steam flow from all 4 SGs and is →Program ΔP is compared to Actual ΔP across FCV using PT-507 (main steam flow) and PT-508 (feed flow). →as FCV opens, ΔP goes down and MFP speed goes up to compensate →as FCV closes, ΔP goes up and MFP speed goes down to compensate
93
How is Program ΔP calculated for MFP speed control?
→0-20% power ΔP is 80 psid →Unit 1: 20-100% power the ΔP ramps from 80- 181 psid →Unit 2: 20-100% power the ΔP ramps from 80-193 psid →To solve for new Program D/P: →U1 Program ΔP = (101/80) x (Actual Power - 20%) + 80 →U2 Program ΔP = (113/80) x (Actual Power - 20%) + 80
94
How do the Main Feed Pumps receive their speed control?
→pump speed based on maintaining ΔP across FCVs →Program ΔP vs Actual ΔP →actual calculation performed via 7300 system →7300 system feeds signal to T3000 controller Actual Pressure comes from PT-507 Steam Header Pressure
95
Does Main Feedwater or Main Steam operate at a higher pressure? Why?
Main Feedwater is at a higher pressure. If it wasn't, we wouldn't be able to inject into the steam generators. Main Feedwater normal operating pressure is approx. 80-180 psig higher than Main Steam normal operating pressure
96
How do steam flow instruments correctly measure mass flow rate instead of volumetric flow rate?
Steam flow instruments are density compensated using steam pressure instruments. As a result, failure of a steam pressure instrument could cause inaccurate steam flow readings.
97
Failures: SG Level High
Failures: SG Level High LT-551 →Level error closes FCV which causes MFP speed to decrease →Feed flow decreases →flow error tries to offset level error, but doesn't →SG level decreases until Lo-Lo SG Level causes Rx trip
98
Failures: SG Level Low
Failures: SG Level Low LT-551 →Level error opens FCV which causes MFP speed to increase →Feed flow increases →flow error tries to offset level error, but doesn't →SG level increases until P-14 actuates
99
Failures: Feed Flow High
Failures: Feed Flow High FT-510 →steam flow / feed flow mismatch →flow error causes FCV to close →FCV D/P increases, causing MFP speed to decrease →Feed flow decreases →SG level decreases →as SG level decreases, level error increases until level error = flow error →SG level stabilizes at level < normal
100
Failures: Feed Flow Low
Failures: Feed Flow Low FT-510 →steam flow / feed flow mismatch →flow error causes FCV to open →FCV D/P decreases, causing MFP speed to increase →Feed flow increases →SG level increases →as SG level increases level error increases until P-14 actuates
101
Failures: Steam Flow High
Failures: Steam Flow High FT-512 →steam flow / feed flow mismatch →flow error causes FCV to open →FCV D/P decreases, causing MFP speed to increase →Feed flow increases →SG level increases →as SG level increases, level error increases until level error = flow error →SG level stabilizes at level above normal Note: if this occurs at lower power levels, then a Hi-Hi Level may occur, causing a Turbine/MFP trip.
102
Failures: Steam Flow Low
Failures: Steam Flow Low FT-512 →steam flow / feed flow mismatch →flow error causes FCV to close →FCV D/P increases, causing MFP speed to decrease →Feed flow decreases →SG Level decreases →as SG level decreases, level error increases →flow error drives to Lo-Lo setpoint, causing Rx trip
103
Failures: Feed Header High Pressure
Failures: Feed Header High Pressure PT-508 →MFPs speed decreases →Feed flow decreases →SG level decreases →Level error opens FCV fully →Feed flow continues decreasing →SG Level decreases until Lo-Lo level causes Rx trip
104
Failures: Feed Header Pressure Low
Failures: Feed Header Pressure Low PT-508 →MFP feed increases →Feed flow increases →SG level increases →Level error causes FCV to close →eventually, FCV closes enough that feed flow = steam flow →SG level stabilizes a few percent above normal
105
Failures: Steam Pressure High
Failures: Steam Pressure High PT-514 →steam flow / feed flow mismatch →flow error causes FCV to open →FCV D/P decreases, causing MFP speed to increase →Feed flow increases →SG Level increases →as SG level increases, level error increases, thereby offsetting flow error until steam flow = feed flow
106
Failures: Steam Pressure Low
Failures: Steam Pressure Low PT-514 →steam flow / feed flow mismatch →flow error causes FCV to close →FCV D/P increases, causing MFP speed to decrease →Feed flow decreases →SG Level decreases →as SG level decreases, level error increases →flow error drives to Lo-Lo setpoint, causing Rx trip
107
Loss of uPC1/uPC2 effect on SGWLC?
→steam pressure channel fails low causing program D/P to lower →MFP speed decreases to match actual D/P to program D/P →FCVs open to increase flow →steam pressure channel failing low also causes steam flow channel to fail low due to loss of density compensation, causes flow error →flow error wants FCV to close →level channels then fail low, causing level error →flow error and level error are competing effects →system is level dominant →FCV slowly opens to restore level →For uPC1 SGs 1 & 4 affected →For uPC2 SGs 2 & 3 affected
108
Loss of uPC3 effect on SGWLC?
No Impact
109
Loss of uPC4 effect on SGWLC?
SG Alarms for channel IV will annunciate and then clear. →alarms come in because of channel IV failure →alarms clear due to loss of multiplexer
110
Level Deviation Alarm
Level Deviation Alarm: actual level ± 5% from program level
111
How does selection of SG Level input to SGWLC affect P-14 and Tech Specs?
→2/3 logic used for P-14 →Tech Specs require 3 operable channels for P-14. →only channels that don't input into SGWLC can be used for P-14 →the level channel normally used for control does not input into P-14; based on the assumption that the controlling channel will fail, and will likely fail low →SGs 1 & 4 use channel 1 for control, so channels 2, 3, & 4 are used for P-14 →SGs 2 & 3 use channel 2 for control, so channels 1, 3, & 4 are used for P-14 Note: when one of the 3 operable P-14 channels is used as a controlling channel, then the P-14 bistable for that channel shall be placed in a tripped condition within 72 hrs (TS 3.3.2)
112
How is Program ΔP derived for SGWLC?
Program ΔP is fed via summing circuit that sums steam flow from all 4 generators to equate to a given power level.
113
How is total steam flow used to determine proper ΔP to maintain across Flow Control Valve?
→Program ΔP is determined using total steam flow from all 4 SGs and is →Program ΔP is compared to Actual ΔP across FCV using PT-507 (main steam flow) and PT-508 (feed flow). →as FCV opens, ΔP goes down and MFP speed goes up to compensate →as FCV closes, ΔP goes up and MFP speed goes down to compensate
114
How is Program ΔP calculated for MFP speed control?
→0-20% power ΔP is 80 psid →Unit 1: 20-100% power the ΔP ramps from 80- 181 psid →Unit 2: 20-100% power the ΔP ramps from 80-193 psid →To solve for new Program D/P: →U1 Program ΔP = (101/80) x (Actual Power - 20%) + 80 →U2 Program ΔP = (113/80) x (Actual Power - 20%) + 80
115
How do the Main Feed Pumps receive their speed control?
→pump speed based on maintaining ΔP across FCVs →Program ΔP vs Actual ΔP →actual calculation performed via 7300 system →7300 system feeds signal to T3000 controller Actual Pressure comes from PT-507 Steam Header Pressure
116
Does Main Feedwater or Main Steam operate at a higher pressure? Why?
Main Feedwater is at a higher pressure. If it wasn't, we wouldn't be able to inject into the steam generators. Main Feedwater normal operating pressure is approx. 80-180 psig higher than Main Steam normal operating pressure
117
How do steam flow instruments correctly measure mass flow rate instead of volumetric flow rate?
Steam flow instruments are density compensated using steam pressure instruments. As a result, failure of a steam pressure instrument could cause inaccurate steam flow readings.
118
T-ave Mode: Load Reject Controller
→in use above 15% RTP →dead band of 5°F, so Bank 1 starts to open when Ave T-ave is 5°F above T-ref →demand increases by 9% per degree above the 5° deadband →PT-505 feeds T-ref
119
T-ave Mode: Plant Trip Controller
→P-4 Rx trip on RTB Train B swaps controller from Load Rejection to Plant Trip →controls Ave T-ave to 557°F No Load T-ave temp →no deadband; 2.5% demand increase per degree above 557°
120
Steam Pressure Mode Basics
→used when <15% RTP, during plant heat up (startup) and plant cooldown (shutdown) →maintains steam line pressure at setpoint set on the controller →auto normally set at 1092 psig or 6.86 turns to maintain 557°F →PT-507 Steam Header Pressure is used as the reference pressure signal →1.8 psid per percent demand on controller →if an issue exists that prevents SD from closing on Low T-ave taking Selector Switch to Steam Pressure Mode will close SD. Or take one of the interlocks to off.
121
How is C-7 reset?
C-7 is reset by taking STM DMP MODE SELECT to RESET.
122
How does Reactor Trip Bypass Breaker control fuse removal affect Steam Dump operation?
→Train A P-4 signal arms the Steam dumps in T-ave mode →Train B P-4 signal swaps T-ave Mode from the Load Reject Controller to the Plant Trip Controller Control fuses to the Reactor Trip Bypass breakers must remain installed even though the breaker is normally not connected. This is because the auxiliary relays powered by these fuses would not indicate proper breaker status if they were de-energized. Likewise, P-4 requires Rx Trip Breaker control power fuses to remain installed even if the breaker is racked out.
123
Steam Pressure Mode Inputs?
Steam Pressure Mode uses reference pressure from PT-507 (200-1500) and PK-507 controller
124
What control signals (%, mA) open Steam Dump Banks 1/2/3/4?
I/P Supplies: →4 - 8ma or 0 - 25% signal to open Bank 1 0 - 100% →8 - 12ma or 25 - 50% signal to open Bank 2 0-100% →12 - 16ma or 50 - 75% signal to open Bank 3 0 - 100% →16 - 20ma or 75 - 100% signal to open Bank 4 0-100%
125
How does the loss of uPC1 or uPC2 affect Steam Dump operation?
→loss of uPC1 - no arming signal for C-7; still available in Steam Pressure Mode →loss of uPC2 - no C-9, so no Steam Dumps
126
Steam Dump trip open and arming circuits receive power from...
Trip open and arming circuits receive power from uD2-3, not train related.
127
Steam Dump Trip Open Values
Load Reject Controller: →5°F deadband →Hi-1 10.6°F - all 6 Group 1 valves trip open (banks 1&2) →Hi-2 16.2°F - all 6 Group 2 valves trip open (banks 3&4) Plant Trip Controller: →no deadband →Hi-1 20°F - all 6 Group 1 valves trip open (banks 1&2) →Hi-2 40°F - all 6 Group 2 valves trip open (banks 3&4) There is no trip open circuitry for Steam Pressure Mode, only goes through I/P converter.
128
What arms Steam Dumps?
Steam Dumps are armed by meeting C-9 (condenser available) AND one of the following: →P-4, Train A only →C-7, load reject of 10% in 120 sec (PT-506 from uPC1) →Selector Switch in Steam Pressure Mode (ref pressure from PT-507, 200-1500 psig on PK-507 controller) Note: C-7 is reset by taking the Steam Dump Mode Selector Switch to "Reset"
129
How do we satisfy C-9 for condenser availability?
→Setpoint: >12.3" Hg vacuum (2/2; uPC2) →Coincidence: Condenser vacuum plus 2/4 Circ Water Pump **breakers** closed
130
When would we use ARVs to cool the RCS instead of Steam Dumps?
→LOOP (no CWPs, so no C-9) →Main Steam Isolation (no steam moving through lines to Steam Dumps/Condenser) →ARVs would control RCS temp down to 561°F
131
How quickly do Steam Dump valves open and close?
→trip open in 3 sec →modulate open in 20 sec →close in 5 sec
132
Steam Pressure Mode - Pot Settings, Demand, and Effects
→pot setting = (pressure - 200 psig)/130 →setpoint ↑, pressure ↑ (less steam flow), temp ↑, demand likely ↓ →higher temp results in negative ρ at EOL conditions but positive ρ at BOL when MTC is still +
133
C-7 →What is it? →Setpoint →Coincidence
→Loss of Load →Setpoint: 10% with time constant of 120 sec on PT-506 (uPC1) →Coincidence: based on turbine power load reduction
134
Steam Dump Interlock Select Switches
→OFF RESET sends signal to protection solenoids to close venting air, which closes steam dumps →BYP INTLK removes Lo-Lo T-ave 553°F trip block to allow cooldown with Bank #1 valves ONLY
135
P-12 →What is it? →Setpoint →Coincidence
→Lo-Lo T-avg permissive →Setpoint: ≤553 deg F →Coincidence: 2/4 channels
136
P-12 What does it do?
→When met automatically closes all steam dump valves →The 3 cooldown steam dump valves may be opened by using bypass switch.
137
PT-507 Failures
Fails High: →does nothing in T-ave Mode →in Steam Pressure Mode, will cause Steam Dumps to modulate open →SG pressure ↓, SG level ↑, RCS temp ↓, Rx Power ↑ Fails Low: →does nothing in T-ave Mode →in Steam Pressure Mode, will cause Steam Dumps to close →SG pressure ↑, SG level ↓, RCS temp ↑, Rx Power ↓
138
PT-506 Failures
Fails High: →does nothing in Steam Pressure Mode →in T-ave Mode, Load Rejection Controller, C-7 won't arm, so Steam Dumps won't open →If Trains A & B get P-4 signals on a Rx trip, then Steam Dumps will switch to Plant Trip Controller and work as designed Fails Low: →does nothing in Steam Pressure Mode →in T-ave Mode, Load Rejection Controller, C-7 arms, but with no demand, so Steam Dumps won't open →If Trains A & B get P-4 signals on a Rx trip, then Steam Dumps will switch to Plant Trip Controller and work as designed
139
PT-505 Failures
Fails High: →does nothing in Steam Pressure Mode →does nothing in T-ave Mode, Plant Trip Controller →in T-ave Mode, Load Reject Controller, results in T-ref being higher than Ave T-ave, so demand goes to zero Fails Low: →does nothing in Steam Pressure Mode →does nothing in T-ave Mode, Plant Trip Controller →in T-ave Mode, Load Reject Controller, results in T-ref being lower than Ave T-ave, so demand goes up, but without an arming signal, Steam Dumps will stay closed
140
What happens to the Steam Dumps on a loss of Instrument Air?
They will not open in any Mode.
141
Which pressures do these transmitters provide? →PT-505 →PT-506 →PT-507 →PT-508
→PT-505 - Main Turbine first stage impulse pressure →PT-506 - Main Turbine first stage impulse pressure →PT-507 - Main Steam Header Pressure →PT-508 - Main Feedwater Header Pressure
142
Failures of T-cold or N-16
Fail High: →nothing happens in Steam Pressure Mode →in T-ave Mode, for either controller, demand increases, but nothing happens without an arming signal Fail Low: →nothing happens in Steam Pressure Mode →in T-ave Mode, for either controller, demand decreases, but nothing happens without an arming signal
143
What happens if the plant trips and there is no P-4 signal from Train B?
→T-ave Mode will remain in Load Reject Controller and not swap over →RCS temp stabilizes at 562°F (5°F above 557°F)
144
What is the function of the Heater Drains System?
The Heater Drains System functions to aid in regeneratively heating feedwater by cascading the higher energy drains through successively lower energy stages of feedwater heaters.
145
How do Normal and Alternate drain valves fail?
→normal - fail closed →alternate - fail open
146
Why don't Feedwater Heaters 5 & 6 have MOVs or check valves?
→not enough stored energy →located inside main condenser, so have limited accessibility for operation/maintenance →feedwater heaters have anti-flash baffles →condensate side of feedwater heaters provided with auto isolation on Hi-Hi Level
147
Drain paths for Heater Drain Tanks and Feedwater Heaters 1, 2, & 3
Heater Drain Tank 01: →MSR Separator Drains →MSR Shell Drains →SGBD Drain →HDT-01 drains to HDT-02 Heater Drain Tank 02: →Feedwater Heaters 1, 2, & 3 →FWH 1A/B drains to FWH 2A/B →FWH 3A/B have no alternate drains (dry heater) →U2 only: FWH 3A/B have vent isolations →HDT-02 provides suction to Heater Drain Pumps
148
What is the purpose and source of HDP Seal Injection?
→Seal Water and Cold Water Injection both supplied from Condensate →Cold Water Injection provided to prevent cavitation through HDPs & TV-2598
149
Heater Drain Pumps
→powered from uA1 and uA2 →oil coolers supplied by TPCW →minimum flow 1400 gpm →if one HDP trips, turbine will runback to <812 MWe (≈70%) at 35% per min Pumps Trip On: →Lo-Lo Level HDT-02 5%, ≤806'6" (2/2) →overcurrent, phase-to-ground →locked rotor →thermal overload (26 relay) →motor DOES NOT trip on motor overload; 74 relay is alarm only
150
Heater Drain Pump Recirc Valves FV-2589A/B
→fail open AOVs →minimum HDP flow is 1400 gpm. →auto open when HDP flow <1470 gpm (both valves open on low flow from either pump) →auto close when HDP flows >1520 gpm (both valves close when both HDP flows above setpoint) →auto close 10 sec after associated pump trip
151
Extraction Steam MOVs - Motor Operated Stop Valves
→close slower than check valves →protect turbine from water induction and high level Auto Close On: 1. Hi-Hi FWH Level 2. Turbine Trip Interlocked With: →associated power assisted check valve →upstream drip pot drain isolation valve →normal drain valve from its associated drains source
152
Extraction Steam Power Assisted Check Valves
→close fast →protect turbine from overspeed due to reverse flow Auto Close On: 1. Hi-Hi FWH Level 2. Turbine Trip
153
Hi-Hi Level in an MSR will...
...trip the Main Turbine.
154
Heater Drain Pump Temperature Limits
Shut down immediately if: →bearing temp >200°F →lube oil temp >160°F or it doesn't build lube oil pressure
155
Feedwater Heater Hi Level Limits
→Hi Level produces Control Room alarm →Hi-Hi Level FWH 1: →closes normal drains from RHDT to FWH 1 →closes Extraction Steam valve to FWH 1 →opens alternate drain valves to Main Condenser →Hi-Hi Level FWH 2: →closes normal drains from FWH 1 to FWH 2 →closes Extraction Steam valve to FWH 2 →opens alternate drain valves to Main Condenser
156
Heater Drank Tank Level Control Valves u-LV-2592 & 2594
The goal is to maintain HDT-02 Level at 50%. u-LV-2592: →comes off HDP discharge header; supplies MFP suction →PI Controller, uses auctioneered high level →HDT-02 Level >50% - valve opens further →HDT-02 Level <50% - valve closes further →if level goes too low, valve could close enough that forward flow is lost u-LV-2594: →comes off HDP-02; discharges to Main Condenser Shell B →Proportional Controller; uses auctioneered low level →HDT-02 Level >65% (approx.), valve modulates open →HDT-02 Level >70% (approx.), valve fully open
157
Heater Drank Tank Level Control Failures / Malfunction
HDP Common Discharge LV-2592 controlled by auctioneered HI signal from LT-2592A/B: →failing low has minimal impact →failing high will cause 2592 will go full open →could result in HDT level lowering to 2/2 level HDP trip (5%) HDT-02 Alt. Drain Valve LV-2594 controlled by auctioneered LOW signal from LT-2594B/C: →failing high will have minimal effect →failing low will cause 2594 to close if open Note: the Lo-Lo Level HDT-02 5% trip of the HDPs comes off of different level transmitters than the ones that control LV-2592 & 2594.
158
Feedwater Heaters Normal and Alternate Drains
159
Drain Tanks Normal and Alternate Drains
160
Extraction Steam Source and Application Points
161
Indication of a turbine runback in effect?
→ALB-6D Win 1.9 "ANY TURB RUNBACK EFFECTIVE" will be lit →will not be lit if already below runback power setpoint →for auto runbacks, the annunciator on Digital Control System (DCS) is illuminated for **9 minutes**
162
Auto Runbacks
→HDP Trip: 35% per min to 800 MW (70%) →MFP or Condensate Pump Trip: 35% per min to 700 MW (60%) →C3 / C4: 200% per min for 1½ sec, then off for 28½ sec; repeat until condition clears
163
Manual Runbacks
→preset buttons available to drive turbine to selected MW load →button provided for 50 MW @ 100 MW/Min; resets in 30 sec →load settings available: 900 and 700 MW at 35% per min →must be manually reset on DCS by turning OFF sub loop controller →for manual runback or load reduction, Runback Annunciator clears once actual load reaches load setpoint
164
Where does MSR heating steam come from?
HP Stop and Control valves share common body; MSR heating steam taps off between the two valves.
165
How does the Main Turbine Turning Gear work?
Turning Gear is supplied from 2 valves: →requires both valves to be open to initially roll the turbine →speed varies between 80 and 190 rpm dependent upon whether vacuum established →auto close if thrust bearing LO pressure 25# →alarm actuated if EITHER valve is open AND <9 rpm on main turbine →neither valve will open if generator breakers are closed u-HV-6554A Turning Gear Valve #1: →auto opens at 230 rpm decreasing →auto closes at 260 rpm increasing →manually operated <50 rpm due to lack on fine control at low speed u-HV-6554B Turning Gear Valve #2: →used to initially roll the turbine →auto closes at 15 rpm increasing →can be manually opened <15 rpm
166
MTOT Temperature Control
Temperature in MTOT is maintained between 90°F and 100°F via heaters installed in the side of the tank.
167
Turbine Exhaust Hood Spray Valve
→solenoid valve opens at 194°F with >1340 rpm →sprays condensate into the area to lower temps →happens mostly at low power with low steam flow available to cool area →condensate line taps off header before drain coolers →solenoid valve must be manually closed once temp restored, but will auto close when high temp clears if LP turbine inlet steam pressure ≥7 psia →separate MOV provided if solenoid valve insufficient to maintain temps →if exhaust temp can't be maintained <212°F, turbine is manually tripped
168
Main Turbine Aux Lube Oil Pumps
→3 pumps, A, B, & C →powered from uB1, uB2, uB3 →A and B auto start at 110 psig →C auto starts at 103 psig →during normal startup, Aux Lube Oil Pumps can be shut off around 1700 rpm because Main Oil Pump will have developed enough pressure
169
Main Turbine DC Lube Oil Pump
→powered from uD2 →auto starts at 32 psig bearing header pressure →only supplies bearings
170
Main Turbine Lube Oil Booster Pump
→used to prime the Main Lube Oil Pump →turbine driven; supplied from main header
171
Main Turbine Shaft Lift Oil Pump (SLOP)
→auto starts at 510 rpm decreasing →auto stops at 540 rpm increasing
172
Main Turbine Lube Oil Coolers
→3 lube oil coolers, 2 normally in service →cooled by TPCW →not normally shifted at power due to potential loss of lube oil and resulting Main Turbine damage
173
Main Turbine Main Oil Pump
→located in HP turbine front pedestal →driven by gear attached to HP turbine shaft →provides all the lubrication needs of the Main Turbine / Main Generator once turbine reaches 1800 rpm →during normal startup, Aux Lube Oil Pumps can be shut off around 1700 rpm because Main Oil Pump will have developed enough pressure
174
Shaft / Gland Seal Steam Systems
→initially supplied from Aux Steam; as turbine power increases, turbine becomes self-sealing at ≈40% turbine power →Gland Steam supply header maintained at 4” WC via AOVs (supply and leakoff); valves fail as is on loss of air or power →leakoff directed to FW Heaters 5 and 6 →leakoff header from Gland Seals and leakoff from stop and control valves is directed to Gland Steam Condenser →Gland Steam exhaust uGS-0141, 0142 vented to PPV to ensure monitoring if SG tube leak →opening the emergency bypass to atmosphere on either the Main or Auxiliary Gland Steam Condenser will result in an unmonitored release to atmosphere
175
EHC Pumps and Pressures
→3 dual stage pumps; stage 1 (LP) 114 psig, stage 2 & 3 (HP) 455 psig →normally 2 pumps in service; standby pump auto starts at 398 discharge pressure →powered from uB1, uB2, uB4 →red handswitches on CB-09 →114 psig control fluid supplies: →Main Turbine Control →tripping (protection) →HP Stop Valve actuators →455 psig control fluid supplies: →LP Stop Valve actuators →HP/LP Control Valves
176
EHC Operating Temperatures
→EHC fluid maintained at 131°F ± 9°F to maintain constant viscosity for proper operation of turbine valves →Fyrquel is used because of its high flashpoint (475°F)
177
EHC Control Fluid Pressure, Function
→114 psig fluid directed to Startup Fluid Solenoids, Trip Block Valve and EHC Converter →used to control the overall hydraulic system.
178
EHC Startup Fluid Pressure, Function
→114 psig fluid supplied from the Startup Fluid Solenoids and directed to Test Valves, which are used to stroke test stop and control valves →essentially used to reset the system for power operation.
179
EHC Trip Fluid Pressure, Function
→114 psig fluid supplied from the Trip Block Valve and directed to the EHC Converter, Test Valves, Reset Valve, Trip Test Valves and HP/LP Stop Valves →used to open the HP stop valves and is the source for Secondary Fluid. →Trip Fluid also ports 445 psig fluid to open the LP Stop valves
180
EHC Secondary Fluid Pressure, Function
→114 psig fluid coming from the EHC Converter and supplied to HP and LP Control Valves →used to control the HP and LP Control Valves by porting 455 psig fluid to actually operate the valves
181
Electro-Hydraulic (EHC) Converter
converts electronic control signal from the controller to hydraulic pressure and amplifies the pressure before sending it to the control valves
182
Digital Control System Load Rejection Feature
→designed to prevent overspeed of turbine in event of load rejection →initiated by: →any power level, load rejection >290MWe per second →lower loads, IF actual load drops below 160MWe, AND actual load is 160 Mwe lower than load target →when circuit initiated, EHC will transfer from load control to speed control →speed control setpoint automatically set to value ≈ current actual load →reset C-7 as required once desired load is reached to prevent instrument failure from causing spurious steam dump actuation
183
What do the HP and LP Stop and Control Valves do on a Turbine Trip?
Valves close to prevent overspeeding of the turbine. LP Control Valves only throttle down on large loss of electrical load to help overspeeding of the Main Turbine. Note: during normal operation at power, HP & LP Stop Valves are normally open with LP Control Valves fully open and HP Control Valves 50% open.
184
Main Turbine Speed Signal Probes
→total of 8 speed probes (6 used, 2 installed spares) →3 probes provide input to software overspeed →3 probes provide input to hardware overspeed →each of the six speed channels (3 for hardware overspeed, 3 for the software overspeed) is automatically tested once every 24 hours when turbine >40 rpm →tests verify that speed channels trip when speed is simulated >1980 rpm
185
Main Turbine Bearing Temperature Limit?
if bearing temp >245°F, turbine must be tripped immediately
186
How is 'Soak Time' determined during Main Turbine Startup?
→simulated shaft mid-wall temp (in TSE) is used during Main Turbine Startup for "Soak Time" determination while at 500 rpm shaft speed →if mid-wall temp <120°F, turbine must soak for ≈20 minutes at 500 rpm prior to increasing speed
187
During a turbine speed increase from 500 to 1700 rpm, if speed doesn't increase as expected...
...the control system will drive the turbine back to 500 rpm automatically.
188
Turbine Trip Hardware Overspeed Subsystem
Hardware Overspeed Sub-system utilizes a set of three dedicated speed channels, each of which provides a trip signal to the Relay Protection System. Upon receipt of trip signals from any two of these speed channels, the relay logic de-energizes all three output relays which subsequently de-energize all three Turbine Trip Block solenoid valves, causing the turbine to trip.
189
Revision Keys Function
→provided to keep Trip Solenoids energized while preventing actual trip signals from de-energizing the trip solenoid →should only be used during outages while on turning gear →only local manual trip available →revision keys block trip inputs into AGF cards →local manual trip still works
190
TR 13.3.33 Turbine Over Speed Protection
TR 13.3.33 Turbine Over Speed Protection At least one Turbine Overspeed Protection Sub-system shall be OPERABLE Applicable in Modes 1-3, except when the MSIVs are closed in Modes 2 and 3 →Provided to ensure that the Turbine Overspeed Protection instrumentation and the Turbine control valves are operable and will protect the Turbine from an excessive overspeed condition →Protection from Turbine excessive overspeed is required since excessive overspeed of the Turbine could generate potentially damaging missiles which could damage safety related components, equipment or structures.
191
Main Turbine Trips
→Hardware / Software Overspeed >1980 rpm →Low lubricating oil pressure (2/3) 25 psig (2 sec time delay) →Condenser A (or B) (2/3) 21" Hg AND 900 rpm →Excessive shaft displacement (2/3 probes) > ± 39 mils →Trip Fluid Pressure <29 psig → **P-14 Hi-Hi SG Level** 84% U1, 81.5% U2 (2/3); controlling level channel not used → **P-4** → **PW Head Tank Lo Level** (2/2) <78% (if turbine >1710 rpm) → **PW Lo Flow to Stator** (2/2) <610 gpm (if turbine >1710 rpm) → **PW Lo Flow to Rotor** (2/2) <580 gpm (if turbine >1710 rpm) → **PW Low Flow to Bushings (A, B or C)** (2/3) <23.3 gpm (if turbine >1710 rpm) → **PW Hi Temp** (2/2) >140°F (if turbine >1710 rpm) → **MSR A or B Shell Level Hi-Hi** (2/3) → **Main Condenser Vacuum** <21" Hg (if turbine >900 rpm) →Generator terminal box high water level (2/3 level switches) →MSR A or B Separator Level Hi (2/3) →Generator Lockout 86-1 →Loss of Field →TG Protection →SSPS / AMSAC →Manual from MCB →Manual Local PB →SI (indirectly; not a direct trip)
192
Does the HP or LP turbine do more work?
HP turbine
193
Overpressure Protection in LP Turbine
rupture disc at 1 psia
194
SGBD HELB Isolation Valves u-HV-2397A through 2400A
→AFW Auto Start, Train B →HELB, Train B (120,000 lbm/hr, 240 gpm) →valves fail closed on loss of power or air →powered from uED2-1 HELB & SGBD Isolation - "AH, PHART."
195
SGBD Isolation Valves u-HV-2397 through 2400
→Train A uED1-1 →Train B uED2-1 →fail closed on loss of power or air →failure of either train solenoid will result in closure of valves Valves Close On: →P - Phase A (train related solenoid) →H - HELB, Train A (120,000 lbm/hr, 240 gpm) →A - AFW auto start (train related solenoid) →R - Rad Hi SGBD Sample Rad Monitor (RE-4200), Train A →T - Temperature Hi >150°F downstream of SGBD HX, Train A HELB & SGBD Isolation - "AH, PHART."
196
What is the max flow through SGBD filters?
→360 gpm per filter before resin beds →both filters normally in service
197
What sort of leakage are the SGBD demins designed to handle?
20 gpd primary to secondary leak with RCS activity equivalent to 1% fuel defect
198
→Max blowdown flow per SG? →Max blowdown flow total (all 4 SGs combined)?
→150 gpm →600 gpm
199
What is the max flow through SGBD bottom nozzles on the SGs?
→Unit 1 - 104 gpm →Unit 2 - 35 gpm Difference is due to difference in SG material wear properties.
200
How is flow rate from SGs to SGBD controlled?
→flow after HX throttled to ~200 psig through PV-5180 →manually controlled at CB-08 →this is what starts/stops flow when aligning
201
Once SGBD passes through the containment penetration, how many valves does each blowdown line have? What are they?
Each line has three valves: →SGBD Isolation Valves (CIVs) u-HV-2397-2400 ("PHART" Valves) →HELB Isolation Valves u-HV-2397A-2400A ("HA" valves) →flow balancing valves HV-5175-5178
202
Supplemental SG Blowdown Valves HV-2440 through 2443
→not always required to be open for U1 since bottom blowdown rate is much higher →fail open AOVs →position indication from ZL lights on MCB →no auto functions
203
How would the loss of SGBD affect the plant?
→SG pressure/temp rises (provides more steam to main turbine) →turbine control valves would close due to control circuit sensing that load has increased with no change in steam demand →amount of energy removed by Main Turbine remains the same; RCS temp would increase →Rx power would go down due to negative reactivity from temp increase →600 gpm flow ≈2.5% Rx power
204
SGBD Relief Valves
→HX Outlet Relief SB-0040 lifts at 1200 psig →relief downstream of PV-5180 (controls flow) lifts at 280 psig (alarm at 159 psig) →both relieve to main condenser
205
SGBD High D/P Alarms
→HX outlet filter Hi D/P 25 psid →cation resin trap Hi D/P 50 psid →mixed bed resin trap Hi D/P 50 psid
206
How does SGBD discharge location affect flow?
→when flow is directed back to HX (to Heater Drains via HDT-01), Condensate = SGBD flow (preferred) →when flow is not directed back to HX (going to Main Condenser, CST, or Turbine Bldg Sump), Condensate = 2x SGBD flow →maintain condensate temp 35°F below Heater Drain Tank temp →prevents flashing to steam
207
What are the temperature limitations for SGBD?
→outlet temp from SGBD HX should be maintained <130°F to protect demin resin from damage
208
Primary Water Turbine Trips
Turbine Speed ≥1710 rpm **AND** one of the following: →Stator Flow Lo <650 gpm (2/2) →Rotor Flow Lo <580 gpm (2/2) →Phase Flow Lo <23.3 gpm (2/2 on any phase) →Inlet Hi Temp >140°F (2/2) →Head Tank Level Lo <78% (2/3)
209
Primary Water Important Head Tank Levels
→Normal Band 90-94% →Hi Level alarm 97% →Lo Level alarm 85% →Turbine Trip 78% Makeup is from Demin Water
210
How should Primary Water temperature compare to H2 gas temp?
Gas temp should always be colder than Primary Water temp to prevent condensation on the stator bars/current carrying components within the generator. →Primary Water temp should not fall below 77°F →Primary Water temp maintained ≥9°F above H2 temp →alarm when PW and H2 temps get within 5.4°F to alert that condensation is possible →alarm when temps get within 1.8°F to manually unload and de-excite the generator
211
What components in the Main Generator are cooled by Primary Water?
→rotor →stator →terminal bushings →phase connectors
212
In the event of a Turbine trip, how long is the Main Generator trip delayed? Why?
→delayed for 30 seconds →extends RCP coast down time →minimizes chance of Main Turbine overspeed
213
What are the Primary Water Coolers cooled by?
→TPCW →6 total, 5 normally in service (20% capacity each)
214
How do we circulate hydrogen through the Main Generator?
Fans are provided on each end of the rotor to provide motive force for moving the hydrogen.
215
Generator Core Monitor Function
→detects aerosols in hydrogen that are indicative of insulation breakdown →provides early detection of abnormal heating by →monitoring H2 environment for thermally produced particulates →interlocked with turbine speed →provides local alarms only at >1690 rpm
216
When activated either generator lockout relay (86-1/1G or 86-2/1G) will initiate the following:
→Turbine trip →opens Generator output breakers 8000/8010 (U1) or 8020/8030 (U2) →Exciter Field Breaker opens →trips non-safeguards normal supply breakers to 6.9 kV from UTs →stops MT cooling →stops UT cooling →stops Isophase Bus Duct cooling →enables transformer fire protection deluge valves
217
The following events will initiate a generator lockout: (17)
The following events will initiate a generator lockout: **1. Total loss of field** 2. 345 KV system voltage less than 85% in conjunction with a total loss of field 3. Field ground 4. Pilot exciter short **5. Generator phase differential** 6. Stator ground **7. Distance protection/ Main transformer ground: the distance protection or a ground on either main transformer has a 1.4 second time delay; trips make up step 2 in the ground fault protection scheme** 8. Main transformer sudden pressure 9. Unit auxiliary transformer phase differential 10. Primary trip signal for generator output breaker 8000 or 8010 (8020 or 8030) 11. Volts per hertz **12. Generator-transformer phase differential** 13. Unit auxiliary transformer sudden pressure 14. Unit auxiliary transformer over current 15. Backup trip signal for generator output breaker 8000 or 8010 (8020 or 8030) **16. Generator negative sequence** 12% 17. Generator terminal box water level high or PW Head Tank Level <78%; coincident with a reverse power
218
AC Seal Oil Pumps
→1 in service, 1 in standby →79 gpm PDP →Pump A powered from uB3-1 →Pump B powered from uB4-1 →normal seal oil pressure maintained at 12-15 psid →standby pump auto starts on low system pressure of 10 psid
219
DC Seal Oil Pump
→powered by uD2-2 →auto starts on low system pressure of 5 psid →if no seal oil pumps can be started within an hour, shut down the unit and reduce H2 pressure to 2 psig (per ABN-402) →recirc solenoid valves auto close on loss of seal oil pressure (<1.5 psid) to prevent H2 leakage
220
Exciter Enclosure Emergency Ventilation Purpose and Setpoint
→provided to permit continued operation in the event of a cooler failure →louvers in the hot (lower compartment) and cold (exciter enclosure) air compartments are automatically opened by actuators admitting air from outside the exciter enclosure and discharging the hot air through openings below the coolers. →Setpoint: 122°F
221
Excitation System
→consists of the pilot exciter, the voltage regulator, the main exciter and the rectifier wheels →overall, we control DC amperage to the Main Rotor in order to control Main Generator output voltage Sequence: →AC - Pilot Exciter induces 3-phase AC in the Pilot Stator via permanent magnets mounted on the exciter shaft →DC - Voltage Regulator (TVR) provides variable DC current to the stator of the main exciter by rectifying/controlling 3-phase AC current from the Pilot Exciter using thyristor sets →AC - variable DC is then applied to the Main Exciter Stator, which generates 3-phase AC →DC - 3-phase AC from the Main Exciter is then sent to the Rectifier Wheels, which convert it to DC →AC - Rectifier Wheels then send DC to the Main Rotor to generate a magnetic field which in turn causes 3-phase AC to be generated in the Main Generator Stator Note: Rectifier Wheels, housed in their own enclosure, act as fans to draw air in at the ends and expel the warmed air to a compartment beneath the exciter.
222
During turbine roll up, depressing the HOLD Setpoint will...
...take speed to 500 rpm until operator resumes startup. If Upper TSE Margin stops the Main Turbine prior to 1765 rpm, the Main Turbine should immediately be lowered to 500 rpm.
223
When Main Turbine speed increases above 1765 rpm, then...
...stop ALL running Auxiliary Oil Pumps and place in Auto.
224
Excitation Current Flowpath
→Pilot Exciter: permanent magnets send AC to TVR →TVR sends variable DC to Main Exciter stator →Main Exciter Stator sends AC to Main Exciter Rotor →Main Exciter Rotor sends AC to to Rectifier Wheels →Rectifier Wheels send DC to Main Generator Rotor (a.k.a. field winding) →Rotor rotation feeds AC to Main Generator Stator →Main Generator Stator feeds AC to electrical system grid
225
What is generator "negative sequence" current?
→unbalanced generator loading = unequal phase currents →can induce negative phase sequence current component →can result in localized heating of the rotor →Main Generator is capable of continuous operation with a negative sequence current of 5% →alarm comes in at 4% →Turbine Trip at 12%
226
How do we ensure that Instrument Air doesn't mix with hydrogen inside the Main Generator?
When Instrument Air is not in use, it is physically disconnected, so there is no flow path into the generator.
227
What is used for AFW when the CST is empty?
→normal is SSW if CST Level <6%, unit is in ERGs, and with Shift Man approval →if SSW is unavailable, then provisions provided to fill CST with Fire Protection water
228
What happens to U2 Main Feed on an AFW Pump start?
→FSBV closes on AFW Pump Start →U2 AFW connects to MFW before CTMT penetration, same line used by FSBV and AFW to feed SG
229
Aux Feed Design
→designed to cool down RCS from 557°F to 350°F for RHR use →can provide normal cooling load up to 7% RTP
230
FRS-0.1 Aux Feed flow requirements
→response to ATWT →AFW is required to be >860 gpm to ensure sufficient decay heat removal →normally 460 gpm is sufficient since normal S/D decay heat is lower
231
ABN-803 (Control Room Evacuation) Actions
TDAFWP is tripped on the MCB to prevent overfeeding the SGs when a SFGDs Bus is deenergized at the RSP.
232
Motor Driven Aux Feed Pump capacity and shut off head
570 gpm at a maximum developed head of 1370 psig
233
Motor Driven Aux Feed Pump Recirc Valves 2456 & 2457
→minimum flow recirc line with orifice 200gpm →close on >200gpm →open <227gpm →fail open on loss of air or power →normally maintained open in standby →common line back to CST →valves have an accumulator to allow 2 strokes for 30 mins (from same air accumulator as MDAFW Pump flow control valves)
234
Motor Driven Aux Feed FCV Accumulator design
Each associated flow control valve provided with a safety class air accumulator sized for five full cycles, plus leakage and steady state consumption for 30 minutes (same accumulator as recirc valves).
235
MDAFW Pump Flow Control Valves
→normally open AOVs →fail open on loss of air or power →PV‐2453A & 2453B for train A to SGs 1 & 2 →PV‐2454A & 2454B for train B to SGs 3 & 4 →air accumulators for 5 full cycles for 30 minutes (shared accumulator with pump min flow valve) →on start of MDAFW Pumps, M/A stations trip to auto and go 100% open →after 10 sec time delay, manual operation can be selected →each feed line has an orifice to limit flow to 700 gpm
236
Turbine Driven AFW Pump
→1145 gpm at 4075 rpm and a maximum developed head of 3236 ft (1433 psig) →overspeed occurs at 4750 ± 50 rpm (116% rated speed) →overspeed mechanism will reset itself at 3000 rpm →Trip & Throttle Valve will need to be locally reset →on loss of air or electrical power, turbine speed governor will fail to max speed
237
Turbine Driven AFW Pump Local Control Panel
→powered from 125VDC uED1‐1 →local panel shows valve position T&TV and turbine speed →SI on Train A removes control power to local panel →prevents the following remote indication and control (on MCB): →indication of turbine speed →turbine overspeed light indication →no annunciator for turbine overspeed →T&TV position indication →cannot trip the turbine from the control room →turbine will still start and come up to speed, just without indication →can locally trip pump OR close steam supply valves from MCB to stop the turbine →power to local control panel can be restored after SI on Train A is reset by depressing OPEN push button 2452H on CB‐09 →this restores full functionality of the turbine
238
ABN-305
Per ABN-305, once TDAFWP trip issue is fixed u-SK-2452A is adjusted to 0% prior to opening the T/T valve and at this time the speed will go to 2000 rpm and can be adjusted by the operator
239
Turbine Driven Pump FCV Accumulator design
Each associated flow control valve provided with a safety class air accumulator sized for five full cycles, plus leakage and steady state consumption for 30 minutes
240
AFW CNTMT Isolation MOVs
→each SG has ONE handswitch that controls BOTH the MDAFW & TDAFW MOV isolation valves →MOVs powered from opposite train from FCVs →opposite train power supplies ensure that we can still isolate flow to an SG on loss of one train
241
CST Design Criteria
→500,000 gal tank →53% (244,000 or 249,100 gals, depending on reference given) reserved for AFW per revised TS 6-30-2011 →10-inch line to suction of both MDAFW pumps →a second 10-inch line to suction of TDAFW pump →CST minimum volume (53%) ensures that water is available to maintain the RCS in Hot Standby for 4 hours followed by a cooldown to 350°F at a rate of 50°F/hr for 5 hours
242
TDAFW Pump Auto Starts
BLA →B - Blackout-OL opens MS supply valves #1, B Train; #4, A Train →L - Lo-Lo Level 38% U1, 35.4% U2 in 2 SGs (2/4 Level Transmitters) →A - AMSAC "There's no T in turbine."
243
MDAFW Pump Auto Starts
BLAST →B - Blackout (Train related) →L - Lo-Lo Level 38% U1, 35.4% U2 in 1 SG (2/4 Level Transmitters) →A - AMSAC →S - SI in conjunction w/ SI Sequencer →T - Trip of both Main Feed Pumps
244
AFW Auto Start Plant Response
→SG Blowdown isolates →SG Sampling isolates →CST discharge valves HV-2484/2485 (Makeup/Reject Valves) close →Split Flow Bypass Valves (U2 only) close →Motor Driven AFW flow control valve trip to Auto 100% open
245
How to reset the trip and throttle valve:
1) Manually reset the overspeed trip linkage by physically repositioning the trip linkage. The overspeed device plunger mounted on top of the turbine bearing casing should drop back into the plunger housing. 2) Depress clutch lever to engage handwheel. Clutch must remain depressed through steps 3 and 4 below. 3) Turn handwheel CW until the latch mechanism is fully engaged. 4) After latch mechanism is fully engaged, turn handwheel CCW until actuator is fully up. 5) Release the clutch lever. Note: the turbine on the TDAFW pump must be at rest for 15 seconds before resetting governor speed setting
246
What is the minimum recirc flow for the TDAFW Pump?
→130 gpm on mini flow line →limited to 20 min to prevent pump damage
247
What controls are available for AFW at the RSP?
→TDAFW speed control and BOTH steam supplies →both MDAFW pump breakers →FCVs to all four SGs from MDAFW and TDAFW pumps →M/A stations on RSP set in Auto allow MCB operation of FCVs from MDAFW and TDAFW Pumps to all 4 SGs
248
What happens if AFW actuates at power with no additional operator actions?
Power Excursion. We send cold water to the SGs, which needs to be heated up, raising Rx power without additional steam demand. Operator response is to lower load by 50 MWe.
249
MFP trip signals energize to actuate. How do we keep from starting AFW when shutting down and tripping both MFPs?
→we remove fuses that send MFP trip signals to start MDAFW Pumps →Train A comes through BOP Aux Relay Rack #1 →Train B comes through BOP Aux Relay Rack #2
250
TDAFW Pump Steam Supply
→supplied by Main Steam lines #1 & #4 before MSIVs →normally closed AOVs with accumulators to allow isolation on loss of air →accumulators allow isolation within 30 mins + 7 more hrs to keep valves closed →valves fail open to ensure turbine acceleration to rated speed in 85 sec
251
What is the flow limitation for MDAFW Pumps?
Do not exceed 800 gpm flow on any MDAFW Pump.
252
Tech Spec 3.7.5 Aux Feedwater
Three AFW trains shall be operable in Modes 1-3. If three AFW trains are inoperable: →initiate action to restore one AFW train to operability immediately. →LCO 3.0.3 and all other LCO Required Actions requiring Mode changes are suspended until one AFW train is restored to operable status (LCO 3.0.4b is NOT applicable) Note: SR 3.7.5.2 verifies developed head of each AFW pump. For TDAFW Pump, it is NOT required to be performed until 24 hours after ≥ 532 psig in the steam generator.