Zach Stubby's Heavy Hitters - Electrical Systems Flashcards

(54 cards)

1
Q

How does air receiver tank pressure affect EDG Emergency Start capability?

A

→Engine will rotate with air until > 200 rpm or pressure in both receivers < 150 lbs.
→Emergency start blocked if air receivers < 150 lbs.
(can still try normal start below 150 lbs)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What automatic protective features does EDG have after Emergency Start?

A

Automatic protective features are disabled except:
—>mechanical overspeed (115%)
—>generator differential (86-1 lockout).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How are full automatic protective features restored to EDG after Remote Manual Emergency Start?

A

→RLMS to LOCAL
→CR DG Emergency HS to STOP
→RLMS to REMOTE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the FO Storage Tank Tech Spec Minimum Volumes?

A

→Modes 1-6 for both
→FO Storage Tank Min volume 86,000 gal for 7 day supply
→FO Storage Tank Min Volume 74,600 gals for 6 day supply

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Air Receiver Tank Pressure Limits
(both TS and Admin)

When does the low pressure alarm come in?

A

Tech Spec: ≥180 lbs

Admin: ≥184 lbs

Alarm: < 210 lbs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Day Tank Tech Spec Minimum Volume

A

1440 gal
(37” or 62%)

Note: EDG will actually run for ~2.8 hours based on 8-12 gpm fuel use

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which trips can’t be overridden with an emergency diesel start?

A

Phase to Phase Fault or Phase Differential (86-1)
Mechanical Overspeed (115%)
(must be manually reset at overspeed pivot lever)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When does the “Ready to Load” red light illuminate?

A

READY TO LOAD (red):
→engine speed ≥ 425 rpm
→generator output voltage ≥ 6210 VAC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the limitations for running EDGs unloaded?

A

Minimize running the EDG unloaded
→ ≤ 5 minutes recommended
→ if operated for >30 mins unloaded, then machine must be loaded to remove any unburned fuel in the exhaust system
→when loaded, should run at minimum of 3.5 MW for 60 mins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If an EDG is connected to the grid during fluctuations…

A

…open the output breaker to prevent damage to the EDG.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

EDG Response to Restart after Shutdown

A

→Normal: won’t restart in Normal for 2 minutes after shutdown

→Emergency: taking H/S to stop will stop EDG, but it will restart once < 200 rpm due to emergency start signal being locked in

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where is field flash powered from?

A

a train related DC bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Which Tech Specs apply to the EDG system?

A

TS 3.8.1 - Requires OPT-215 when declaring an EDG inoperable (Modes 1-4)

TS 3.8.2 - one required offsite source and one required DG operable (Modes 5-6); if not met, check 6.9 kV and 480 VAC flashcard deck for actions

TS 3.8.3 - 7 day fuel oil and lube oil requirements, 48 hours to complete, if not met then declare EDG inoperable

TR 13.8.31 - AC Sources (Diesel Generator Requirements) - This TR LCO contains the surveillance requirements and associated actions for DG surveillances that are not absolutely necessary for EDG OPERABILITY, but still a good idea to be performed. It includes certain 18 month and 10 year TRS’s that send you to the applicable Tech Spec if not met.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens to the EDGs if they lose DC control power?

A

No field flash, no start signals. Won’t start on Normal or Emergency, locally or remotely.

If already running, can’t be stopped via handswitch. Must use local pneumatic trip button.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the Top 3 High Safety Significant Components?

A

→TDAFW Pump
→SSW
→EDG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If the EDG is tied to the bus for testing and an actual SI occurs, what is the EDG response?

A

→EDG will keep running unloaded
→EDG output breaker will open as long as normal or alternate feeder breaker is closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

How is the spare inverter supplied?

What can the spare inverter supply?

How does it provide this supply?

A

The spare inverter can be supplied from either train related DC bus or dirty power.

It can supply power to any of the 4 train related Instrument buses.

Through the appropriate inverters being replaced via removing from service a static transfer switch on the inverter itself.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

When uEC1 and uEC2 are on Bypass power, their train related Blackout Sequencer is…

A

Inoperable

→on a loss of offsite power the sequencers will de-energize.
→also on a loss of power to these panels the EDG will trip if running normally and not start in auto or manual due to 86-2
→it will however start in Emergency Manual or SI.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What occurs on a loss of 2EC1 and 2EC2?
(Unit difference)

A

Unit 2 Only

Loss of 2EC1 or 2EC2 will result in:
→loss of Water Hammer interlocks, resulting in
→Feedwater Isolation, and requiring a
→Manual Reactor trip

(Unit 1 doesn’t have water hammer interlocks because of SG replacement)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Static Switch Auto Transfer Criteria

A

→DC input voltage ≤105 VDC
→AC output voltage drops to 50% normal value (~59 VAC)
→Output load current rises to 120% of rated value (~175 Amps)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

AC Essential Lighting
(powered from 480 VAC via step down transformers)

A

Supplies lighting in areas essential to the safe shutdown of the plant (ECB, Aux Bldg, U1 and U2 SFGDs)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

DC Emergency Lighting

A

Provided as a backup to AC lighting systems in locations where safety related functions are performed and for personnel safety in access and egress routes

In areas where the DC Emergency Lighting is provided, 8-hour rated battery packs or station batteries are provided

23
Q

118 VAC Operability

A

→The individual distribution panels must be powered from an inverter which is supplied from a 125 VDC bus.
→When the swing inverter is used it must be supplied from the same DC bus as the inverter it is replacing.
→The off-going inverter must be removed from the DC bus prior to placing the swing inverter on the same DC bus.

24
Q

Which breakers feed normal and alternate supplies to bus XA1?

What components does the XA1 bus carry?

A

XA1-2: normal
XA1-1: alternate
(backwards from normal)

XA1 carries vent chiller 5-9

25
Grounding Schemes
6.9 kV - low impedance 480 V & EDG - high impedance
26
6.9 kV Anti-Parallel Interlock
As soon as alternate supply breaker is closed, the normal supply breaker opens, and vice versa. DOES NOT apply to the EDG breaker.
27
Non-Safeguards Bus Fast Transfer (Live Bus Transfer)
-0.25 seconds -40° phase angle -If alternate breaker doesn't close in 0.25 sec, then slow transfer (dead bus transfer) will occur.
28
Safeguards Slow Bus Transfer (Dead Bus Transfer)
-Voltage drops and normal breaker opens. -As voltage continues to drop (approximately 70% of normal voltage) the BOS will actuate the Operator and Automatic Lockouts (OL and AL) -As voltage continues to drop (approximately 30% of normal voltage) at this same time a 1 sec TDPU timer starts in order to start the EDG, a 0.3 sec TDPU timer starts to unload the bus and a permissive is set to allow the alternate power supply breaker to close.
29
If 6.9 kV buses fast or slow auto-transfer to alternate sources due to undervoltage, will they auto-transfer back when voltage returns to acceptable levels?
No
30
What is the only trip for DC BKRs?
Overcurrent
31
DC Bus Operability
For a DC Bus to be considered operable it must have the following: →Operable battery charger connected to the bus (each bus has installed spared) →Operable battery connected to the bus →Maximum of 2 inverters per DC Bus →Batteries are rated for 4 hours at full load
32
Effects of Loss of Train "A" 125 VDC:
NOTE: Effects are similar for Loss of Train "B". →Train A Rx Trip and Bypass Breaker shunt trips not available/ UV available →Feedwater valves fail closed →Train A EDG will not start and cannot flash field/ can't stop from CR if running →Steam Dumps fail closed →TDAFWP speed indication lost →PZR Aux Spray fails closed →PORV 455A fails closed →VCT Level control lost →Letdown isolates →SGBD and Sample valves close →TDAFWP Train Steam Supply fails open →Train A MDAFWP flow control and recirc valves fail open →Loss of control power to Train A 6.9kV and 480 LC breakers
33
What do the DC buses do for the EDG controls? What happens if we lose the DC buses?
→field flash →the diesel won't start on either normal or emergency start signals →if diesel already running, it could no longer be remotely shutdown from CR
34
Ensure an operable battery charger is aligned to panel uD2 during EOP-2.0 to....
...prevent the MSIVs from re-opening →a steam leak in the MSIV room(s) could cause the hydraulic dump solenoid valves to fail closed →as a result, if the oil pump were to supply oil to the MSIV in those conditions, the valve would open
35
What is the minimum operating voltage for the 345 kV switchyard?
340 kV
36
What is the minimum operating voltage for the 138 kV switchyard?
135 kV
37
What is distance relaying?
→an electrical protection scheme where protective devices (relays) which are geographically separated can communicate with each other to detect and isolate faults at the appropriate locations to minimize effect on the grid
38
Capacitor Bank Breaker 8435 closes when.... Capacitor Bank Breaker 8435 opens when....
→closes when grid voltage drops below 136.5 kV for 2 seconds →opens when grid voltage increases to 143 kV for 2 seconds (capacitor bank expected to raise 138 kV grid voltage by 1 kV when in service)
39
What are the common trips for 345 kV breakers?
→low SF6 gas pressure →transmission line fault (only for breakers tied directly to transmission lines) →pole disagreement →bus lockout “ltpb = light peanut butter”
40
What are the unit differences for the switchyard?
Unit 1 Safeguards Buses: →normal power is 345 kV (XST2) →alternate power is 138 kV (XST1) Unit 2 Safeguards Buses: →normal power is 138 kV (XST1) →alternate power is 345 kV (XST2)
41
What are the main generator breaker trips?
→common trips →main generator lockout →turbine trip
42
What auto-closes the XST1/XST1A High Speed Ground Switch?
→auto closes on fault of XSTA or XST1A →must be manually reset
43
What auto-opens 138 kV MOAS (8085/8095)? 8085: XST1 supply 8095: XST1A supply
→86-1 or 86-2 on associated transformer →associated transformer no-load relay energized
44
What conditions must be present for manually closing 138 kV MOAS (8085/8095)? 8085: XST1 supply 8095: XST1A supply
→86 lockout relays must be reset →ground switch GXST1 must be open →associated transformer no-load relay energized (transformer is unloaded)
45
Why do we control generator output breakers?
“Control” means any apparatus or mechanism that, if manipulated, directly affects the reactivity or power level of the reactor. Generator output can directly affect reactor power.
46
Tech Spec 3.8.1 AC Sources - Operating
→Modes 1-4 →two offsite sources must be available →two DGs must be available →automatic load sequencers for Train A and Train B Two offsite sources can be satisfied by: →"Stephen Parker" - 138 kV Stephenville with 345 kV Parker #1 OR Parker #2 →"Number 2 Bends" - 138 kV Carmichael Bend with any 345 kV line except for Mitchell Bend (138 kV Stephenville line crosses all 345 kV lines other than Parker 1 and 2)
47
Which transformers have inert gas oil preservation?
→1UT →2UT →XST1 →XST1A →XST2
48
Which transformers have Modified COPS Oil Preservation?
→1MT1/2 →2MT1/2 →1ST →2ST →XST2A
49
Which transformers DO NOT have deluge systems?
1ST, 2ST, XST2A (All others have deluge.)
50
What kind of lockouts do the Main Transformers have?
They only have a Sudden Pressure Relay that generates a Main Generator lockout if activated. This disconnects the transformer from its power source. (A sudden pressure relay is actuated by a sudden pressure increase due to an electrical arc vaporizing oil into gas.)
51
Do transformer alarms have reflash?
No. If an additional alarm comes in while there is already a trouble alarm in, the trouble alarm will not reinitiate.
52
What powers Unit 1 Safeguards Buses?
Normal: XST2 Alternate: XST1 Emergency: Diesel
53
What powers Unit 2 Safeguards Buses?
Normal: XST1 Alternate: XST2 Emergency: Diesel
54
What powers the non-safeguards buses?
Normal: UTs through main generators Alternate (or unit shutdown): STs