Pump 11 Flashcards
(MANUAL TRANSMISSION) once the potheads been properly activated and the pump is engaged, …. The vehicles sped odometer should show ($$$$)
0 mph
If it appears that the pump will be required to furnish more than 50% of its rated capacity it should be set to the ($$$$$$$$) position from the start.
Parallel volume
To avoid possible damage to the water system do not allow incoming pressure to drop below ($$$$$),
20 psi
The worst hydrants are typically ($$$$$)
Dead end mains
NFPA 291
Recommended practice for fire flow testing and marking of hydrants
Class AA, light blue,
1500 or greater
Class A, green
1000 to 1499
Class B orange
500 to 999
Class c red
Less than 500
There are two primary ways a fire department may use a hydrant. The first involves stopping at the hydrant, dropping the end of one or more supply lines at the hydrant, and proceeding to the fire location. This process is called a ($$$$$$)
Forward lay
When using 2 1/2 or 3 inch hotlines to supply the pumper directly off hydrant pressure, it is recommended that the lines be no longer than ($$$$3
300 feet
With the ($$$$$) hose is laid from the fire to the water source.
Reverse lay
If threaded couplings are used, hose beds set up for revers lays should be loaded so that the first coupling to come off is ($$$$)
Male
It is generally recommended that the hydrant valve be opened until the valve stem will pin no further and then close ($$$$$$$$$) to relieve the strain on the valves and the internal components.
One quarter turn
When a pumper is connected to a hydrant and not discharging water, the pressure shown. On the intake gauge is the ($$$$$$)
Static pressure