What is the amp limit for the 1N high side breaker as measured on the 4kV meter side?
<70A.
What happens if the 1J cross-tie breaker exceeds its limit?
It will trip on overload.
What is the basis for the amp limit on the 1N high side breaker?
Cable protection.
What happens to RCP motor currents when grid voltage lowers?
They rise towards the trip setpoint.
What is the compensatory action for lowering grid voltage?
Raise generator MVAR output.
Does the Load Tap Changer (LTC) affect the 6.9kV bus?
No, the 6.9kV bus is on a fixed tap.
Does the 1Y 480V disconnect switch have a kirk key interlock?
No, it does not.
How should the 1Y 480V disconnect switch be opened under load?
Procedurally opening the 480V feeder to minimize arc damage.