MAIN FEEDWATER (401) Flashcards

(27 cards)

1
Q

What happens to FW-V-5A/B on a Reactor Trip Confirmed?

A

FW-V-5A/B CLOSE, but the interlock can be overridden by pressing and holding the OPEN button until fuses are removed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What must be done to reset FWPs if CO-V-9A/B is closed?

A

CO-V-9A/B must be OPEN to reset FWPs; FWPs will trip if CO-V-9A/B is closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the procedure for returning FW-V-16/17 to AUTO if they are in HAND?

A

Return the controlling valve to AUTO first. If both valves are controlling, return FW-V-17 to AUTO first.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does the ICS controller display for FW-V-16/17?

A

The ICS controller shows the demanded position, and the LED indicates the actual position.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Up to what power level does FW-V-16 control?

A

FW-V-16 controls up to 25% power.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the electronic trip conditions for FWPs?

A

Counting circuit, low oil pressure (<4#), CO-V-9A/B closed, vacuum ≤20” (2 of 3), and MCR trip.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the mechanical trip conditions for FWPs?

A

Overspeed at 5775 rpm and local handle operation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many pressure switches does each FWP have, and what are their functions?

A

Each FWP has 9 pressure switches: 4 for RPS, 2 for HSPS, and 3 for Turbine/ICS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When do the auxiliary AC motor-driven oil pump and emergency DC pump auto-start?

A

The auxiliary AC motor-driven oil pump auto-starts at ≤43#, and the emergency DC pump auto-starts at ≤36#.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What provides sealing steam during startup and normal operations for FWPs?

A

GS provides sealing steam during startup, and the turbine self-seals during normal operations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the steam sources for FWPs?

A

Aux Steam (manual transfer at 3-7% power), Main Steam via MS-V-5A/B until extraction steam is available, and AUTO transfer at 22-24% power to extraction steam from MO-T-2D/F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the function of the Motor Speed Changer (MSC) for FWPs?

A

MSC controls from 0–2600 rpm, and the Air Speed Changer takes over to 100%. MSC can control up to 5500 rpm using the ON switch.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What happens to control valves if stop valves are closed?

A

Control valves trip CLOSED if stop valves are CLOSED. Stop valves cannot be OPENED unless control valves are CLOSED.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens to FW-V-1A/B on FWP electrical trips?

A

FW-V-1A/B CLOSE and cannot be OPENED unless the FWP is reset.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens to FW-V-7A/B min recirc valve on loss of air or DC?

A

It OPENS and provides a minimum of 1000gpm recirculation through an orifice.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

At what flow rate does FW-V-7A/B min recirc valve OPEN and CLOSE?

A

It OPENS if FW flow is <2520gpm and CLOSES if flow is >2520gpm.

17
Q

What is the requirement for FW-V-12A/B RB Isolation check valves during a fault inside RB?

A

They must be closed within 1 hour to maintain containment integrity.

18
Q

What action is required if FWP vibrations reach 5 mils?

A

Manually trip the pump (M-1-3). If only one pump is running, trip the reactor, follow EOP-001, and trip the FWP.

19
Q

What should be done if FWP vacuum drops below 23”?

A

Start the standby auxiliary vacuum pump.

20
Q

At what thrust bearing temperature should the FWP be evaluated for securing and tripped?

A

Evaluate at 170°C and trip at 190°C.

21
Q

How many pressure switches does each FWP have, and what are their functions?

A

9 total: 4 for RPS (<75#), 2 for HSPS, and 3 for DTCS/ICS (runback to 560MWe / 68% and turbine trip).

22
Q

What happens when an FWP is in standby mode?

A

It is NOT reset.

23
Q

What occurs during chest warming with a steam leak in the IB on “A” OTSG?

A

CRO trips the reactor and closes MS-V-1A/B. “A” OTSG undergoes MFW isolation, EFW feeds the faulted OTSG (boils dry), and “B” OTSG loses MFW flow.

24
Q

Does FW-V-92A close on an HSPS signal or a reactor trip?

A

It closes on an HSPS signal, not a reactor trip.

25
What is the full power feedwater flow rate?
Approximately 10.8Mlb/hr.
26
During plant startup at 30% Rx power, what happens if FW-P-1A trips while FW-P-1B is reset and running unloaded?
EFW pumps will not start until OTSG levels reach 10” startup range.
27
What happens if FW-V-16/17 positioner/booster fails?
HSPS isolation signal at 97.5% or 600# will still close FW-V-16/17 due to special solenoid porting opening air.