FIRE SERVICE SYSTEM Flashcards

1
Q

What are the required sources for the Fire Service System per AP-1038?

A

River, CW flume, and Altitude Tank (FS-T-1), with each source having >90K gallons.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How many pumps are required for the Fire Service System per AP-1038?

A

Two pumps.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the power source for FS-P-4 Jockey Pump?

A

1C ESV MCC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

At what pressure does FS-P-4 Jockey Pump turn ON?

A

108#.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

At what pressure does FS-P-4 Jockey Pump TRIP?

A

125#.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the purpose of FS-P-4 Jockey Pump?

A

Maintains Fire Service system pressure due to ~30gpm leakage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What triggers FS-P-2 IPSH Motor Driven pump to auto start?

A

90# header pressure or any deluge actuation (auto or manual).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens if FS-P-2’s breaker is closed without the other breaker racked in?

A

The pump auto starts.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What triggers FS-P-3 IPSH Diesel pump to auto start?

A

80# header pressure, any deluge actuation, or loss of 1E 4kV Bus after a 30-second time delay.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What triggers FS-P-1 CWPH Diesel pump to auto start?

A

70# header pressure or loss of 1A 4kV Bus after a 10-second time delay.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the required action if the fire suppression water system is inoperable?

A

Establish a backup within 24 hours or be in HSD in 1 hour and CSD in 30 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the difference between wet pipe sprinklers and deluge systems?

A

Wet pipe sprinklers flow water only from affected heads, while deluge systems open all heads.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the supervisory nitrogen pressure in the NDCT deluge system pilot lines?

A

30#.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What triggers the automatic pre-action system?

A

One fire alarm in adjacent groups OR one faulted alarm and one real alarm, AND loss of supervisory air due to fusible link melt.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum supervisory air pressure required for the automatic pre-action system?

A

≥24oz/in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is required if the automatic pre-action system is inoperable?

A

Establish a continuous fire watch within 1 hour per AP-1038.

17
Q

What triggers the CARDOX CO2 fire suppression system?

A

Any one of four HAD devices at 140°F after a 30-second time delay.

18
Q

What is the minimum operability requirement for CARDOX?

A

8500lbm CO2 (8.5 ft in tank) at a minimum pressure of 285#.

19
Q

What triggers the Halon system?

A

UV detectors or explosion (impact) detectors, but NOT accelerometers.

20
Q

What happens when Halon actuates?

A

All three deluge systems auto start FS-P-2/3.

21
Q

What is the design basis flow rate for the fire suppression system?

A

2575gpm for remote deluge and 1000gpm for hose use.

22
Q

Does FS-P-1 auto start on deluge actuation?

A

No, FS-P-1 does not auto start on deluge actuation.

23
Q

What is the response time requirement for fire brigade members?

A

Less than 10 minutes, and they must stay in the protected area (PA).

24
Q

What happens if one preaction detector alarms and another is removed?

A

The multimatic valve actuates, but no water flows.

25
What triggers AH-E-154 smoke detector in the OSF 2nd floor?
It trips the fan and closes dampers.
26
What action is required if FS-P-1 is found inoperable?
No action is required as long as two fire pumps remain operable.
27
What must be done manually to start FS-P-5A/B after AH-E-101 trips?
AH-E-101 must be manually stopped.
28
What triggers FS-P-5A/B to auto start?
Two of 15 temperature switches at 200°F.