MAIN GENERATOR & AUXILIARIES Flashcards

(13 cards)

1
Q

What powers the GN-P-2 ESOP and when does it auto-start?

A

DC powered; auto-starts at 95# seal oil pressure and lowering.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the function of the GN-P-3 Vacuum Pump?

A

Removes non-condensable gases and routes oil to the vacuum pump for lubrication, cooling, and sealing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of the GN-P-4 Recirculation Pump?

A

Runs continuously to de-aerate and dry the oil.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does the Seal Oil Regulating Valve (SO-V-H19) maintain?

A

Maintains a ΔP of 8# (68# nominal) and ensures seal oil pressure is greater than gas pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How does the Seal Oil Pressure Regulator (SO-V-H12) function?

A

Works with H19 to regulate main seal oil pump discharge pressure and governs seal oil flow rate.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens on loss of MSOP and TB lube oil?

A

H2 purity degrades over time, and seal oil loses cooling. Loss of both MSOP and ESOP stabilizes gas pressure at 15-20# and requires a generator trip with emergency manual purge.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When does the standby Stator Coolant Pump (GN-P-5A/B) auto-start?

A

Auto-starts at 110# (100# backup) and low flow <403gpm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What does the GSC-V-Y07 Temperature Control Valve do?

A

Diverts flow around series coolers to maintain stator inlet temperature; stator coolant flow through coolers is not adjusted.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does the SLMS control and why?

A

Controls dissolved oxygen to promote formation of cupric oxide (good) to prevent corrosion versus cuprous oxide (bad) that plugs bars.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the thresholds for H2 leakage in the generator?

A

Normal: <10 ft³/day; Check next outage: >10 ft³/day; Remove generator from service: >200 ft³/day.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What triggers a stator coolant runback?

A

Flow of 381-400gpm (2 of 3 for 5 sec) or high outlet temperature of 80-82°C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the stator coolant runback limits?

A

Reduce to <25,474 amps (<95%) in 2 minutes and <9,322 amps (29.6%) in 3.5 minutes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What action is required for conductivity >9.9 in the stator coolant?

A

Reduce reactor power to <45% and trip the turbine.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly