When do rakes start in the Screen House?

A

Rakes start at 0700, 1500, 2300 or when DP reaches 4”.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When do screens start in the Screen House?

A

Screens start at 1100, 1900, 0300 or when pumps run with screens.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What triggers the lead pump (SW-P-1A/B) to start?

A

The lead pump starts first out of PTL and load sheds on ES with 27/86.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens when strainers start in the Screen House?

A

Strainers start on pump start with backwash at 9# and a 10# high DP alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What does 15 minutes of rake and 20 minutes of screen continuous operation indicate?

A

It gives an alarm and indicates elevated debris.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the operability criterion for river equipment in the Screen House?

A

Operability is based on DP < 6”.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the functions of vacuum breakers in the Screen House?

A

Vacuum breakers prevent high starting current, seal damage, siphon effect (flow reversal) on pump trip, and water hammer on pump start.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the backup for River Water Lube Pumps (WT-P-33A/B)?

A

Domestic Water is the backup.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the minimum flow required for River Water Lube Pumps (WT-P-33A/B) protection?

A

20 gpm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the purpose of Screen House Fans (AH-E-27A/B)?

A

Maintain room temperature below 120°F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When do Screen House Fans (AH-E-27A/B) auto-start?

A

On ES Block 4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the maximum inlet temperature for de-icing operations?

A

37°F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the procedure for de-silting operations regarding SWPs?

A

All three channels may be taken out of service, and DP must be checked every 2 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

At what Susquehanna flow level does flooding occur, and what action is required?

A

Flooding occurs at 284.2’; Tech Spec shutdown is required at >302’.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What actions are required if the river level drops below 277’?

A

Initiate shutdown per 3.0.1; Trip Rx and RCPs at <274’; go to CSD in 36 hours if river temperature is ≥95°F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What happens to river pumps in the event of a total loss of the York Haven Dam?

A

All river pumps retain suction.

17
Q

Can all river pumps be secured during de-silting operations?

A

Yes, all river pumps can be secured.

18
Q

What is the source of de-icing water at 33°F river temperature and 21°F air temperature?

A

De-icing water comes from Nuke River (NR).

19
Q

What happens if fire destroys the 1R/1T 480V Bus?

A

AOP-005 is entered, Rx is tripped, RCPs are tripped, and emergency boration is commenced.